Sizing of district heating substations and optimum maintenance of domestic hot water circuits in Sweden Janusz Wollerstrand Lund Institute of Technology.

Slides:



Advertisements
Similar presentations
Modelling sustainability in water supply and drainage with SIMDEUM®
Advertisements

Institute of Energy & Sustainable Development De Montfort University
Heat Exchanger Network Retrofit
HEATING AIR © Commonwealth of Australia 2010 | Licensed under AEShareNet Share and Return licence.
Environmental Controls I/IG Lecture 14 Mechanical System Space Requirements Mechanical System Exchange Loops HVAC Systems Lecture 14 Mechanical System.
Unit 206: Domestic hot water systems
Technical Seminar on Refrigeration & Air Conditioning
AQ2511B0 Boiler Reset Panel – for Whole House Heating Control – Immediate Retrofit Opportunity !
Unit 206: Domestic hot water systems
Cold feed to hot water cylinder Sink Basin Bath Drain valve Stop valve WC cistern 100 litre (minimum storage cistern)
Learning Outcomes Upon completion of this training one should be able to: Identify open loop and closed loop campus-type hydronic water system applications.
UNEP - ECA network and thematic meetings in Ohrid – RAC meeting Ohrid, 21 May 2013 Slobodan Pejković Monitoring the performance in real-life of ground.
RUSSIAN ACADEMY OF SCIENCES PROGRAM SYSTEMS INSTITUTE Optimal Control of Temperature Fields for Cooling of Supercomputer Facilities and Clusters and Energy.
Nordic Show Room on Energy Quality Management, th August 2014, O. GUDMUNDSSON, DANFOSS A/S | 1| 1 Utilization of return water in district.
©2007 Armstrong International, Inc. Instantaneous Water Heater Flo-H 2 0 ™ Water to Water Instantaneous Water Heater Flo-H.
Increasing the energy efficiency of buildings Chris Cirone PhD Candidate, Agricultural and Biological Engineering.
How to be Cool Mike Dennis Department of Engineering.
Harnessing Free Heat. The Energy Harness provides hot water using multiple heat sources, making the best use of low grade heat. It improves the efficiency.
Unit 206: Domestic hot water systems
Refrigeration and Heat Pump Systems Refrigeration systems: To cool a refrigerated space or to maintain the temperature of a space below that of the surroundings.
CHANGES IN THERMAL ENERGY CONSUMPTION IN APARTMENT BUILDINGS OF ESTONIA Teet-Andrus Kõiv,
Adapted control systems for house service connection stations of huge performance – domestic hot water supply based on continuous flow system Faculty of.
10 Energy Saving Advices. 1- Lowering of the temperature at night Limit the lowering of the temperature at night. If the temperature is reduced too much,
Mirja Tiitinen 1 Dimensioning standard for domestic hot water Euroheat&Power RTD Workshop Brussels Mirja Tiitinen Finnish Energy.
Grundfos FLOW THINKING Air conditioning the Grundfos Way.
HVAC523 Basic Subsystems.
IEA HPP Annex 28 Calculation of compact units Workshop IEA HPP Annex 28 8 th International Heat Pump Conference, Las Vegas, 30 May 2005 Thomas Afjei, Institute.
District Heating Technology Improvement of district heating systems efficiency starts at the consumer New calculation tools help consumer and district.
PREVENTING FROZEN PIPES Efficiently and Thoroughly ©2012 TEMTROL deltaT Inc. - distribute freely unedited.
Practical Electricity. Recap…  5 important formulae: Q = Charge (Coulomb) I = Current (Ampere) t = time (second) V = Voltage or potential.
Euroheat & Power XXXII. Congress, Berlin, "CHP/DHC: The Whole Picture"
Geothermal Heat Pumps Connecticut Geothermal Association John Sima, PE.
Euroheat & Power, 2. RTD Workshop, High Efficiency – Improved Building Installations and Customer Comfort, Brussels 2-3 February 2006 Control components.
Zoning Hydronic Systems. Zone Control Divides the Space to be Heated 1.Each with its own heating needs and control systems 2.There are several reasons.
Learning Outcomes Upon completion of this training one should be able to: Identify hydronic chilled water system applications. Define the difference between.
1 Hospital Building and Campus Piping. 2 Hospital Building Occupancy – office and patient areas Patient areas: 24 hours per day Office areas: 8 am – 5.
Geothermal. Defining “Geothermal” Energy Dictionary definition – Relating to the internal heat of the earth The Earth acts as a giant solar collector,
Learning Outcomes Upon completion of this training one should be able to: Identify hydronic chilled water system applications. Define the difference between.
Esbe Rotary Motorized valves The ESBE Rotary Motorized valves (mixing valves and actuators) are used to control heating and cooling in buildings. We offer.
Optimum Performance of Radiator Space Heating Systems Connected to District Heating Networks via Heat Exchangers Patrick Ljunggren, Janusz Wollerstrand.
DISTRICT HEATING District heating is an infrastructure which allows heat generated in a centralized location to be distributed to residential homes and.
Oddgeir Gudmundsson Applications Specialist Danfoss
SARDAR VALLABHBHAI PATEL INSTITUTE OF TECHNOLOGY PREPARED BY: 1)BALDIWALA ALIABBAS ( ) 2)PARTH GUPTA ( ) 3)ANIL KHATIK ( )
Contract: EIE/07/069/SI Duration: October 2007 – March 2010Version: July 7, 2009 Calculation of the integrated energy performance of buildings.
Installation rules and guidelines
D.C.Generator.
HNC/D Engineering Science
Heat transfer Steady state conditions not for dynamic systems in buildings through walls, roofs, floors, windows, doors building structures and U-values.
Power Generation and Distribution
Lecture Objectives: Learn about thermal storage systems
Plumbing system fundamental and design course
Improved Hot Water Code Calculation
ARAC/H/F Air-cooled water chillers, free-cooling chillers and heat pumps Range: kW.
Maria Justo Alonso1, Rolf Ulseth2 and Jacob Stang1
Neutral current is zero
Connection methods in district heating networks
ELECTRICAL INSTALLATION AND MAINTENANCE (EIM) 5 INSTALL ELECTRICAL PROTECTIVE DEVICES FOR DISTRIBUTION, POWER, LIGHTING, AUXILIARY, LIGHTNING PROTECTION.
District Energy Networks
Hot water Systems Heaters.
Hot Water Systems Cylinders and Systems.
Calculations: Transformers and Service Conductor Calculations
Oddgeir Gudmundsson, Jan Eric Thorsen and Marek Brand
Sr. Lecturer in Electrical Engg. Govt. Polytechnic,Manesar
NEW ARISTON STORAGE BOILERS March, 2009.
Synthesis of Heat Exchanger Networks
Water Bath Heaters 101.
Sustainable Heating and Cooling in Sweden
Presentation transcript:

Sizing of district heating substations and optimum maintenance of domestic hot water circuits in Sweden Janusz Wollerstrand Lund Institute of Technology Department of Energy Sciences Sweden

Topics Balancing of DHW circulation circuits Dynamic sizing of control valves in domestic hot water (DHW) heaters Heat exchanger operation at overload condition Practical experiences

A district heating substation and secondary circuits in a residential building

T indoor 21-22ºC 55ºC

A district heating substation and secondary circuits in a residential building 50ºC 55ºC T indoor 21-22ºC

Connecting scheme of the domestic hot water circulating system in a large university building. Temperatures at end-points and some short-cuts resulting in low temperature in one of branches shown.

Thermostatic balancing valve Temperature registration Thermostatic balancing valve installed at the end point of DHW circuit

Connecting scheme of the domestic hot water circulating system in a large university building. Thermostatic balancing valves installed resulting in equalized temperature level in the circuit.

Strongly reduced valve size as a consequence of dynamic sizing being employed. Source: C. Forslund, Gävle Energy AB, Gävle New valve Replaced valve Valve actuator Heat exchanger

Reasons for oversizing of control valves in practice : overestimated design load values for DH substation overestimated operating conditions of the substation round up of the valve size in case of discrepancy between the calculated size and the available size (almost always) dynamics of the system not taken to consideration

Position changes of control valve in a hot water heater with varying valve size (field measurements performed by Gävle Energy AB) DH water flow rates in a hot tap water heater with different control valve sizes. The peak flow rate increases by increased valve size but at small loads the flow rate remains mainly unchanged Dynamic sizing of control valves in domestic hot water heaters – field measurements

Dynamic sizing of control valves in domestic hot water heaters as employed in Gävle, Sweden Size of the building Valve size k vs, m 3 /h Heat exchanger size, kW flatsk vs =0,63 m 3 /h80 kW flatsk vs =1,0 m 3 /h80 kW flatsk vs =1,6 m 3 /h140 kW Special case 1: Secondary distribution system – next higher valve size Special case 2: Floor heating or towel dryers supplied by domestic hot water circuit – next higher valve size Source: C. Forslund, Gävle Energy AB, Gävle

Outgoing hot water temperature and primary return temperature from a heat exchanger vs. hot water flow when the primary flow is limited. If mixing of the hot and the cold DHW at the tap is taken to account, 20% overload at 45ºC DHW temperature is possible

Domestic hot water (DHW) temperature measured at the outlet of the heater while short overload condition occurs Valve position DHW temperature DHW circul. temperature

Domestic hot water temperature measured at the tap during morning hours in a hotel

Theoretical flow characteristic of a control valve of logarithmic type. Control ratio: 1:100, k vs =10 m 3 /h. Logarithmic valve with k vs =10 m 3 /h size and the control ratio 1:100, with the o pening ratio limited to 50%, acts as a nearly logarithmic valve with k vs =1 m 3 /h and the control ratio 1:10 Adaptive limiting of capacity of existing control valve instead of replacing the valve by a smaller one − a promising solution

Number of flats with size of control valve employed in tap water heaters for a large group of residential buildings in Gävle, Sweden

Short tappings often do not coincide when hot water circulation is working well (the left picture) but are likely to coincide otherwise (the right picture).

Conclusions Dynamic sizing of control valves works well in practice The choice of the size of control valve strongly depends on proper functioning of DHW circulation Adaptive adjustment of control valve capacity − optimum solution Do not relay on DHW circulation return temperature as a minimum temperature of the circuit