Harmonics Problems in Distribution Systems Case Study AEP Texas Central Company Scott Lee, Reliability Engineer.

Slides:



Advertisements
Similar presentations
Shunt Capacitor Switching For Power Factor Improvement Clayton H Reid.
Advertisements

Copyright© Voltimum Experts – not to be reproduced without prior consent of Voltimum UK Voltimum Expert Topic – Power Harmonics.
QUALITY AND TECHNOLOGY
Siemens Building Technologies Building Technologies Variable Frequency Drives Harmonics Overview.
Who is Stellar Tech?  Stellar Tech Energy Services is a wholly owned Canadian company  Manufacturer of WellMax Datalogger / Controller  Specializing.
EMC in Electrical Power Systems Frithiof Jensen Power System Engineer November 12, 2013.
VARIABLE SPEED DRIVES HARMONIC EFFECTS & EFFECT OF USE WITH LONG CABLES (100 – 300m) Electric Motors & Drives ….OUR VISION, YOUR SOLUTION ……. TOGETHER.
2010 ASHRAE Rocky Mountain Chapter VFD Fundamentals April 16, 2010 Jeff Miller - ABB © ABB Month DD, YYYY | Slide 1 1.
© Copyright 2008 ABB. All rights reserved /29/2008 Results-Driven Roadshow Cincinnati, 2008 Common Cures for Harmonics Larry Stanley RSE,Nashville,TN.
VARIABLE SPEED DRIVES AND FILTERS CLASSIFICATION AND APPLICATION.
Effects of high penetration levels of photovoltaic generation Observations from field data Amir Toliyat, Alexis Kwasinski and Fabian Uriarte The University.
DYNAMIC LOAD RESPONSE: As a result of the impressed inverter output wave form. Presenter: Dr Gawie van der Merwe.
The X-Ray Circuit.
7154 VFD Presentation #3 May 2002 Paul Weingartner.
ELECTRIC DRIVES Ion Boldea S.A.Nasar 1998 Electric Drives.
EXPERIMENTAL STUDY AND COMPARATIVE ANALYSIS OF TRANSFORMER HARMONIC BEHAVIOUR UNDER LINEAR AND NONLINEAR LOAD CONDITIONS.
Dry type transformers Zaragoza Traction application
Understanding of Harmonics in Power Distribution System
Active Power in 1~AC mains Apparent / Reactive / Active Power ~ L ~ C ~ R pure resistor R : phase shift = 0° active power 1 pure reactance L : phase shift.
Unit Transformer Unit transformer are step up transformer which is connected to generating house & step up voltage from 15kV voltage to 132 voltage level.
Plant Utility System (TKK-2210)
PRODUCTS TRANSFORMERS ENERGY SAVING TRANSFORMERS (EST) TRANSFORMER RECTIFIER UNITS 3 rd HARMONIC REJECTION TRANSFORMERS (HRT) ULTRA HIGH ISOLATION TRANSFORMERS.
Dry type transformers Zaragoza Drives application
Unit 29 Three-Phase Transformers. Objectives: Discuss the construction of three-phase transformers. Discuss the formation of a three-phase transformer.
PowerGUARD Energy Saving for inductive loads Saving 8%-15% Protection Power Quality.
ISA Northern California Section, South Bay October 14, 2003 Craig Chidester
Introduction In recent years, harmonics are considered as one of the most essential problems in the industrial power distribution networks. The problem.
1 Green River Utah Area Transmission and Distribution System – January 16, 2009.
LECTURE 28 AC Voltage Controllers Dr. Rostamkolai
Power Distribution Harmonics Case Study of 285-3F Chiller Plant Michael W. Harmon Principle Engineer Savannah River Nuclear Solutions, LLC Savannah River.
POWER FACTOR CORRECTION
Transient Overvoltages
PQSynergy TM 2011 Harmonic Assessment of PEA North1, Chiangmai’s Customers in North Industrial Estate Chotepong Pongsriwat. M.Eng(EE) Chief of Power.
Section 3 TRANSMISSION & DISTRIBUTION US Bulk Power Transmission System Transmission & Distribution (T&D) Components New T& D Technologies This product.
2. Terms and definitions1 # Terms and Definitions # Voltage Sags and Interruptions.
Industrial Electrical Engineering and Automation Structures of the Energy flow system Mechatronics 2007.
Applied Harmonics Control of Harmonics
1 Chapter 3 Harmonic Modeling of Networks Contributors: T. Ortmyer, C. Hatziadoniu, and P. Ribeiro Organized by Task Force on Harmonics Modeling & Simulation.
POWER QUALITY.
Chapter 3 Power System Harmonic Mitigation. INTRODUCTION Power system harmonic issues have existed since the early 1900 ’ s. The earliest discovered issues.
LECTURE 25 Controlled Rectifiers Dr. Rostamkolai
Circuit Master Circuit Master™ uses three PROVEN technologies* – Capacitor (reduces DEMAND) – Harmonic Filter (harmful frequencies) – Surge Protection.
Voltimum Expert Topic – Power Harmonics. What are Harmonics? They are waveforms with frequencies that are multiples of the fundamental frequency (Typically.
IEEE PES General Meeting, Tampa FL June 24-28, Chapter 3 Harmonic Modeling of Networks Contributors: T. Ortmyer, C. Hatziadoniu, and P. Ribeiro.
Three Phase Motors Maths
7/08/2002PP.AFD.07 Harmonic Quality1 of 49 Yaskawa Electric America Harmonic Currents, Voltages and Your Building Power System.
الاسبوع الحادي والعشرون تطبيقات المبدلات Inverter Application تطبيقات المبدلات Inverter Application.
Presented by. What is Power Factor? Power Factor is the percentage of current delivered from the utility that is needed to perform the actual work. For.
controlled rectifiers (Ac-dc converters)
TECHNICAL PAPER ON SIMULTANEOUS AC-DC POWER TRANSMISSION
7/15/2002PP.AFD.081 of 28 Power Quality Considerations When Applying Adjustable Frequency Drives Explanations and Various Countermeasures.
Asea Brown Boveri Jumet S.A. FD 1/30 ASEA BROWN BOVERI Harmonic Problem ? Are Tuned Filters THE Solution ?
6. Unregulated Power Supply Design
(SWTCHED - MODE POWER SUPPLY)
Power Quality Issues Power Electronics Group.
Power Quality at Solar Distributed Generation Facilities
Effects of Harmonics on Capacitors Electrical System
CHAPTER 6 SPECIAL TRANSFORMERS Electrical Machines.
Presented By Deepak Kumar Bari Regd. No
MEDIUM VOLTAGE APPLICATIONS.
Yaskawa Electric America on Variable Torque Loads
Power System Harmonics
Distribution Feeder Voltage Regulation and Control
Klystron Power Supplies for ILC
ELL100: INTRODUCTION TO ELECTRICAL ENGG.
Power Electronic Systems Power electronics refers to control and conversion of electrical power by power semiconductor devices wherein these devices operate.
Presentation transcript:

Harmonics Problems in Distribution Systems Case Study AEP Texas Central Company Scott Lee, Reliability Engineer

SYMPTOMS OF A PROBLEM  Residential customer calls complaining of problems with electronics: TV, thermostat – AC, motors making strange noises  Serviceman and Operations Tech troubleshoot and have transformer replaced because of unusual humming and arcing sounds from coil  New transformer makes the same sound, customer still has problems – call the engineer  Tech goes to new pipe plant down the road and finds 2000kVA pad transformer making same noise

 Houston based company built a pipe coating and storage plant in George West to better serve the Eagle Ford Shale area  Two 1000kW induction furnaces to heat and coat 2 inch to 24 inch diameter casing with fusion bonded epoxy  Two solid state 6-pulse rectifiers and step up transformers provide variable frequency 4kV power to induction coils For more info... see texisle.com and ajaxtocco.com THE SOURCE

INSTALLATION  Previously during the plant planning stages, AEP provided system, line, and transformer impedances to drive manufacturer for design. Distance and PQ were discussed.  3 miles of distribution feeder was upgraded with 477MCM aluminum, with a total length of 6.4 miles  Drive manufacturer wanted two 1500kVA or one 3000kVA transformer, we supplied one 2000kVA. They were also very insistent on our transformer meeting their specs. Actual peak is 1380kW.  A 1000kVA pad was installed for other plant power that peaks at 600kW  AEP standard for three phase padmounts is wye-wye  IEEE-519 requirements were not discussed, customer did not tell us the inverter was a 6-pulse drive

George West Sub 138/12kV 9.4 MVA Plant  * Residence  Feeder upgraded to 477, 6.4 circuits miles from sub to customer

 1000kW  500 Hz  Variable Frequency  6-pulse rectifier  No filtering  Water cooled

 PMI recorders installed at plant transformer and at residential customer. Set to record harmonics and capture waveforms.  Voltage THD at pipe plant on secodary, 14%  Voltage THD at residential secondary, 5.1% PMI stands for Power Monitors Incorporated, see iVs-3 and Eagle 440www.powermonitors.com MEASUREMENTS

3rd 12.4% THD-Voltage 7th 11 th 13th 5th 23.4% THD-Amps 2000 kVA Padmount 6-Pulse Drive 5th 7th 11th Unfiltered, running at 1550kVA

12.4% THD-V 23.4% THD-A Unfiltered, 2000kVA Padmount, 6-Pulse Drive

THE FIX  Met with pipe company and drive manufacturer to request they install filtering and comply with IEEE-519 (5% THD limit on voltage)  Move other distribution customers in area to another feeder  Drive manufacturers said they would install passive filters (reactors and capacitors) but parts would have a 14 week lead time plus engineering and installation time  I countered to pipe company that this was unacceptable, and offered three filter manufacturers with on the shelf parts that offered active filtering and engineering support.  Recomended MTE Matrix Pure Sine active filters, Schaffner EMC ECOsine active filters, and TCI H5 active filters.

 There was a debate over passive versus active, but after some research, I pressed the customer to go with active filters because of the varying load and the possibility of hitting resonance with a passive unit, also recommend a 5% line reactor which is standard for 6 pulse drives  The customer chose a vendor, and we had several phone conferences about what to install, and what would be acceptable with AEP  The vendor chosen was Schaffner EMC and the ECOsine FN3420 filter with additional 5% reactors For more info... List location or contact for specification (or other related documents) THE FIX cont.

 Schaffner EMC ECOsine filter injects up to 300 amps of current  Compensates for harmonic currents  Compensates for reactive current  Can choose percentage of overall current dedicated to each harmonic  Two installed with 5% reactor ahead of each drive

 Before at 1850 amps of load:  Voltage THD 12.6% Current THD 23%  After at 2150 amps of load:  Voltage THD 5.5% Current THD 8.8%  After at 1320 amps of load:  Voltage THD 7% Current THD 5%  Adjacent Transformer Voltage THD 3.5%

Total Load 1800 amps HarmonicAmpsAmps with Filter 5 th th th th 6059 THD-V from 12.2% to 8.1%

2300A rms 5.9% THD-V 9.6% THD-A 8.4% THD-V 24.2% THD-A Neutral volts and amps Testing, filter on and off  Filter off

Waveforms showing commutation notching 6.9% THD-voltage 5% THD-current 1300 amps

UG Residence, one mile from pipe plant, plant running at 7% THD-V 3.5% THD-V 3 rd, 7 th, and 5th V I

 Not below 5% THD on voltage at meter  Filtering has done all it can do  Work with drive manufacturer to control commutation notching using saturating reactors on SCRs to speed gate closing

 Should have required drive manufacturer to meet IEEE 519 standard  Get a written proposal from drive manufacturer on how they will meet the standard  Use delta primary transformer to trap Triplen harmonics, this is 2.7% of total  Recommend active filtering  Recommend 12 pulse drives or technology to reduce commutation notching IN RETROSPECT