Zoran Gajić ABB AB Vasteras, Sweden

Slides:



Advertisements
Similar presentations
Introductory Circuit Analysis Robert L. Boylestad
Advertisements

New Energy Horizons Opportunities and Challenges Fault Current Contributions from Wind Plants Dean Miller PacifiCorp July 25,
Accurate Fault Location is Critical
Advanced Power Protection Lecture No.2
Chapter 19 Methods of AC Analysis. 2 Dependent Sources Voltages and currents of independent sources –Not dependent upon any voltage or current elsewhere.
Research & production enterprise «EKRA», Ltd,
Contingency Ranking by Time Domain Simulations ECE 422/522 Russell Patterson Micah Till Terry Jones.
CIGRE 7-10 September 2009, Moscow
ECE 3336 Introduction to Circuits & Electronics
Fundamentals of Electric Circuits Chapter 19 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
Electromagnetics (ENGR 367)
AC Power: average power
AC Review Discussion D12.2. Passive Circuit Elements i i i + -
R,L, and C Elements and the Impedance Concept
Network Theorems SUPERPOSITION THEOREM THÉVENIN’S THEOREM
Lesson 24 AC Power and Power Triangle
Lesson 20 Series AC Circuits. Learning Objectives Compute the total impedance for a series AC circuit. Apply Ohm’s Law, Kirchhoff’s Voltage Law and the.
Generator Protection. Amount of Protection Rated power of the generator Ratio of its capacity to the total capacity of the system Configuration of the.
Chapter 4 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
Current Contribution from Wind Plant for a System Fault Working Group C17 May 2010 Meeting.
Copyright © 2010 Pearson Education, Inc. Lecture Outline Chapter 24 Physics, 4 th Edition James S. Walker.
1 ENE 429 Antenna and Transmission lines Theory Lecture 4 Transmission lines.
CIGRE Study Committee B5 Colloquium, Calgary September 2005 AREVA T&D Automation Protection & Control of Series Compensated Networks Z Q Bo PART.
1.6 Real Single-Phase Transformer.
1 1. Power and RMS Values. 2 Instantaneous power p(t) flowing into the box Circuit in a box, two wires +−+− Circuit in a box, three wires +−+− +−+− Any.
Review Part 3 of Course. Passive Circuit Elements i i i + -
1 © ABB AB, Application of Unit Protection Schemes for Auto-Transformers Zoran Gajić ABB AB Vasteras, Sweden Authors: Z. Gajić, ABB Sweden.
Chapter 24 Alternating-Current Circuits. Units of Chapter 24 Alternating Voltages and Currents Capacitors in AC Circuits RC Circuits Inductors in AC Circuits.
ELE130 Electrical Engineering 1 Week 5 Module 3 AC (Alternating Current) Circuits.
Connections of a CT and a PT to supply, load and relay.
1 © Unitec New Zealand DE4401 AC PHASORS BASICS. AC Resistors 2 © Unitec New Zealand.
EMLAB 1 Chapter 5. Additional analysis techniques.
New proposed BU circuit and control logic design University of Washington.
SMART SENSORS FOR A SMARTER GRID BY KAILASH.K AND LAKSHMI NARAYAN.N.
Chapter 15 – Series & Parallel ac Circuits Lecture 19 by Moeen Ghiyas 11/10/
POLYPHASE CIRCUITS LEARNING GOALS Three Phase Circuits Advantages of polyphase circuits Three Phase Connections Basic configurations for three phase circuits.
GOOSSENS (BE) Session 2 – Block 3 Barcelona May Improved Assessment of Voltage Dips with Common Monitoring Devices M. Bollen, A. Robert &
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
Alternating Current (AC) R, L, C in AC circuits
AC Series-Parallel Circuits Chapter 18. AC Circuits 2 Rules and laws developed for dc circuits apply equally well for ac circuits Analysis of ac circuits.
ELECTRICAL CIRCUIT CONCEPTS
1 Department of Electrical & Communication Engineering CHAPTER 1 Per Unit Calculations 1.Power System Representation Power Component SymbolPower ComponentSymbol.
1 ELECTRICAL TECHNOLOGY EET 103/4  Define and explain sine wave, frequency, amplitude, phase angle, complex number  Define, analyze and calculate impedance,
Protection of Microgrids Using Differential Relays
Copyright © SEL 2010 Advancements in Transmission Line Protection and Fault Location Brian Smyth Lead Product Engineer.
ECEN 679 Project 1 Topic 22: Fault Location Using Synchronized Phasors Po-Chen Chen Instructor: Dr. M. Kezunovic Mar. 3, 2014.
1  Explain and calculate average power, apparent power, reactive power  Calculate the total P, Q and S and sketch the power triangle. ELECTRICAL TECHNOLOGY.
Instructor :Kashif Mehmood
UNIT-VII Static Series Compensators
POLYPHASE CIRCUITS LEARNING GOALS Three Phase Circuits
CHAPTER 2: DC Circuit Analysis and AC Circuit Analysis Motivation Sinusoids’ features Phasors Phasor relationships for circuit elements Impedance and admittance.
A sinusoidal current source (independent or dependent) produces a current That varies sinusoidally with time.
Protection of Power Systems
Halliday/Resnick/Walker Fundamentals of Physics 8th edition
FUNDAMENTAL OF ELECTRICAL POWER SYSTEMS (EE 270)
CHAPTER 5 DC AND AC BRIDGES.
Reactance and Resonance. Some Review of Important Concepts AC waves have constantly changing voltage and currents. We need to use RMS voltage and RMS.
البحث السابع بحث منفرد منشور فى مؤتمر دولى متخصص (منشورة التحكيم علي البحث الكامل) Adel A. Elbaset 13th International Middle East Power System Conference,
1 AC Circuit Theory. 2 Sinusoidal AC Voltage Waveform: The path traced by a quantity, such as voltage, plotted as a function of some variable such as.
Protection of Power Systems
Power System Protective Relaying-Part Two
Quality and Security Assessment of Protection Systems
CHAPTER 6 SPECIAL TRANSFORMERS Electrical Machines.
Transient Analysis of Shunt Reactor Switching on 500kV System
POWER SYSTEM ANALYSIS INTRODUCTION.
Protective Relaying Conference
Peter van Oirsouw (Phase to Phase)
ELL100: INTRODUCTION TO ELECTRICAL ENGG.
Exercise Session 11 Power systems.
Exercise 9 Power systems.
Presentation transcript:

Zoran Gajić ABB AB Vasteras, Sweden Multi-terminal Line Differential Protection Installed on Series Compensated, 400kV Line with Five-Ends Zoran Gajić ABB AB Vasteras, Sweden Authors: Z. Gajić, ABB Sweden I. Brnčić, ABB Sweden F. Rios, Svenska Kraftnät

Application Description The following data are valid for this application: Positive sequence line impedance Zero sequence line impedance Total series capacitor reactance this corresponds to the impedance of 400kV line with length of 265km

Application Description The following data are valid for this application: Line three-phase reactive power generation 657.5 kVAr/km at 400kV (circa 350A per phase of charging current at 400kV over the whole length of the protected line). This corresponds to phase to ground fault with resistance of 650 Ohms primary. Main CT involved in this scheme have ratio: 2000/2 in Station #1, 3000/1 in Station #2 2400/2 in Station #3.

Communication Setup For this installation master-master differential protection principle is used (i.e. every differential relay had all five currents available and is able to perform the differential protection algorithm). Distance protection is included in each differential relay in order to provide reserve protection for the line. The line differential protection scheme uses a telecommunication SDH/PDH network with unspecified route switching. Therefore differential relays utilize the GPS for the time synchronization. In the substations there are 16 x G.703 64 kbit/s channels. The following SDH/PDH configuration is used: SDH multiplexing (STM-1 or STM-4)à 8 x 2 Mbit/s (E1) à PDH multiplexing à 16 x 64 kbit/s (E0).

Overall System Setup

Differential Operating Characteristic Differential current (Operate current) is the vectorial sum of measured currents at all line ends and it is calculated separately for each phase Bias current (Restrain current) is considered as the greatest phase current in any line end and it is common for all three phases Dual slope characteristic is used Unrestraint differential level is available IdMinHigh used during initial line energizing

External/Internal Fault Discriminator Based on theory of symmetrical components It utilize the negative sequence current component from all ends of the protected line Directional comparison principle is applied Negative sequence current component from the local end is compared with the sum of the negative sequence current components from all remote ends When these two phasors are in phase fault is internal When these two phasors are in contra-phase fault is external

Problem of Charging Current for Long Lines Capacitance of the protected line causes false differential current to be measured by IED Π – equivalent circuit can be used to estimate the charging current if voltage measurement on both end of the line is available Charging currents are symmetrical (i.e. they exist mostly as positive sequence current component)

Problem of Charging Current for Long Lines By using voltage derivative charging current can be estimated It is only APROXIMATE method because the Π – equivalent circuit is too simplified and do not represent properly the line especially during transient conditions Problem for more complex line configurations: Series compensation Multi-terminal lines HV cables

Why Charging Current is Required? To make line differential protection sensitive for high resistance faults Is there any more general method which will work for independently from the primary system set-up?

Assumption for New Charging Current Algorithm During high resistance faults voltage drop will be quite small therefore the charging current just before and after the fault inception will be approximately the same For heavy external or internal faults influence of charging current will be practically negligible

New Charging Current Algorithm Differential function learns the false symmetrical differential current over a period of time (i.e. it consider all three phases simultaneously) Once this value is learned it is simply subtracted from the presently measured RMS currents in every phase Any change in measured currents freezes charging current estimation Algorithm is adaptive and does not need to know anything about primary system setup, however it needs some short time before it becomes effective Voltage measurement is not required Only end user setting is to enable or disable it (i.e. On/Off)

Charging Current Compensation Principle Note that only RMS differential current are compensated, not the instantaneous differential current values Both of them are available from IED as service value and to the built-in disturbance recorder

Recorded Internal Faults Two captured recordings in this installation are presented in the paper. Both recordings were captured by line differential protection IED installed in Station #3. The first recording is an internal L2-L3-Gnd fault which was caused by lightning. The fault location was estimated to be 99km from Station #1 and estimated fault resistance was around 24 Ohms primary. The second recording is an internal L2-Gnd fault. The fault location was estimated to be 7km from Station #1 and the fault resistance was estimated to be around 8 Ohms primary. The cause of this fault is unknown. Differential protection has operated properly for both internal faults.

Internal Fault No 1; Recorded Diff Currents Instantaneous Diff Currents Present before the fault Diff RMS Quantities Zero before the fault

Internal Fault No 2; Recorded Diff Currents Instantaneous Diff Currents Present before the fault Diff RMS Quantities Zero before the fault

Internal Fault No 3 Summer 09; Recorded Diff Currents Instantaneous Diff Currents Present before the fault Diff RMS Quantities Zero before the fault

Conclusion The proposed charging current compensation method, independent from voltage measurements, seems to work very well for such long, series-compensated overhead line configurations. It has been shown that the multi-terminal line differential protection is a good solution for protection of long, series-compensated, high-voltage lines with more than two ends. Combination of multi-terminal line differential protection and distance protection provides good protection solution for such lines. Differential protection is in service for almost two years with correct behavior

СПАСИБО ЗА ВНИМАНИЕ! THANK YOU!