Enea Detectors Range
Introducing new devices ENEAis a range of analog addressable detectors and ancillaries for hi end applications ED100 – SMOKE DETECTOR ED200 – HEAT DETECTOR ED300 – COMBINED SMOKE AND HEAT DETECTOR
Introducing new devices Designed and manufactured at Inim electronics, it is a 100% italian product
Introducing new devices Each device of the new ranges has been approved by LPCB which is one of the most prestigious notification body in fire detection EN54-5 : Heat Detectors EN54-7 : Smoke Detectors EN54-17 : Short Circuit Isolator EN54-18 : Input/Output devices
KEY FEATURES Optical Smoke detectors are based on th eprinciple of the light scattering, to avoid false alarm it is important to avoid contaminations in the analysis chamber
Introducing new devices Top side completely sealed to avoid dust or water condensation to reach the chamber One of the most common false alarm or fault reason is the dust coming from the pipes or condensating water dropping from the top side
Introducing new devices Metal mash agains insect wit less than 500um holes diameter One of the biggest problems of optical smoke detectors is dust or insect entering in the chamber
Introducing new devices Electronic circuit completely WAX coated to avoid any contamination Moisture or environmental pollution may affect the behaviour of hi sensitive electronics circuits in the detector
Introducing new devices Sensitive part of the circuit completely shielded by a metal cage Electromagnetic noise may affect the measurement of the hi gain amplifier generating false alarms
Introducing new devices Last generation CPU inside each detector whith hi false alarm rejection algorithm The measurement of the smoke chamber and thermal probe are evaluated by the internal CPU and by means of the algorithm designed from the Inim R&D department an hi rejection to false alarm is achieved
Introducing new devices Smoke chamber easy to open for clean up operations In case of detector’s chamber contamination detector can be easily opened and cleaned with some air or a soft brush
Introducing new devices Each Detector is Full tested with automatic test equipment which measure each single component and verify each electrical connection
Introducing new devices Each Detector is Calibrated with a two stage process : one in free air and another one in a smoke tunnel to ensure the same response from each sample
Introducing new devices Each Detector is subjected to a «Burn IN test» of 24 hours: the 80% of electronic components failure occur during the first 24 hours of theyr life, detectors live theyr first 24 hours in our burn in test!
Introducing new devices Universal mounting base for every detector model Clip for line continuity restore in case of detector removal
Introducing new devices Relay base available direct driving of any type of external device
Each device is identifyed by a serial number Introducing new devices Each device is identifyed by a serial number The serial number is reported on the back label and on two small detachable labels : this allow to stick a serial number to map and a serial number to mounting base
Introducing new devices Thanks to LOOPMAP technology, which is the ultimate technology in loop addressing and fault finding, no any address operation is required
Introducing new devices After the loop has been wired up, by using the panel and its configuration software or using the EDRV1000 driver with the included FireGenius software…
Introducing new devices The loop wiring is automatically detected and a graphic report (including any T junction etc) is available:
Diagnostic features using Smartleague configuration software: Introducing new devices Diagnostic features using Smartleague configuration software:
Contamination analysis using Smartleague configuration software: Introducing new devices Contamination analysis using Smartleague configuration software:
If some divice is not responding Introducing new devices The interactive graph show where there is a short circuit (each device include a short circuit isolator) Right button mouse click If some divice is not responding Allow to Manually activate the 3 colour leds, the outputs etc. in order to test the loop
Introducing new devices For each detector Smoke and heat sensitivity can be adjusted and are available early warning threshold for Smoke and heat level
THANK YOU