Steam Condenser II Prof. Osama El Masry

Slides:



Advertisements
Similar presentations
HEAT EXCHANGER GUIDED BY: PREPARED BY:
Advertisements

Heat Exchanger Design Thermal / Fluid System Design Final Project Department of Mechanical Engineering Fall 2005 December 13, 2005 Team Members: Andrew.
Quiz – An organic liquid enters a in. ID horizontal steel tube, 3.5 ft long, at a rate of 5000 lb/hr. You are given that the specific.
Application of Steady-State Heat Transfer
ERT 216 HEAT & MASS TRANSFER Sem 2/
First Law of Thermodynamics - Open Systems
Lecture# 9 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES
So Far: Conservation of Mass and Energy Pressure Drop in Pipes Flow Measurement Instruments Flow Control (Valves) Types of Pumps and Pump Sizing This Week:
Chapter 4.2: Flow Across a Tube Bundle Heat Exchanger (Tube Bank)
Heat Exchange Design and Optimization Project Presented: May 6 th, 2010 Professor: Mr. Toksoy Group Members: Nathan Dart Andrew Kinney Paul Thompson Joe.
Chapter 3.2: Heat Exchanger Analysis Using -NTU method
Chapter 2: Overall Heat Transfer Coefficient
Experiment : 5/03/2012 Presentation : 12/03/2012 Group B1/B Vartak Shankul Shisheer 10D Abhishek Mathur 10D Kunal Bhoyar 10D
 A 'heat exchanger' may be defined as an equipment which transfers the energy from a hot fluid to a cold fluid. Here, the process of heating or cooling.
Analysis of Simple Cases in Heat Transfer P M V Subbarao Professor Mechanical Engineering Department I I T Delhi Gaining Experience !!!
One-Dimensional Steady-State Conduction
Mass and Energy Analysis of Control Volumes. 2 Conservation of Energy for Control volumes The conservation of mass and the conservation of energy principles.
Thermal Development of Internal Flows P M V Subbarao Associate Professor Mechanical Engineering Department IIT Delhi Concept for Precise Design ……
Heat Convection : Cylinder in Cross Flow P M V Subbarao Associate Professor Mechanical Engineering Department IIT Delhi A Common Industrial Application.
Heat Exchangers with Cross Flow past Cylinders P M V Subbarao Professor Mechanical Engineering Department I I T Delhi Another Common Industrial Application!!!
LINEAR SECOND ORDER ORDINARY DIFFERENTIAL EQUATIONS
Kern Method of SHELL-AND-TUBE HEAT EXCHANGER Analysis
HEAT EXCHANGERS Day 2.
Heat exchangers. Device that facilitate the exchange of heat between fluids that are at different temperatures while keeping them from mixing with each.
Chapter 3.1: Heat Exchanger Analysis Using LMTD method
بنام خدا.
Temperature Driving Force Concentric Pipe Heat Exchangers
SURVIVAL MODE Quiz 3 –
Fouling Factor: After a period of operation the heat transfer surfaces for a heat exchanger become coated with various deposits present in flow systems,
Capture and Utilization of Carbon Dioxide Ethanol Production Presented By: Dana Al-Maiyas. Supervised By: Prof.Mohamad A.Fahim. Eng.Yousif Ismael.
PM3125: Lectures 10 to 12 Content of Lectures 10 to 12: Heat transfer:
ISAT Module III: Building Energy Efficiency
Heat Transfer Equations For “thin walled” tubes, A i = A o.
So Far: Conservation of Mass and Energy Pressure Drop in Pipes Flow Measurement Instruments Flow Control (Valves) Types of Pumps and Pump Sizing This Week:
ERT 216 HEAT & MASS TRANSFER Sem 2/
One-Dimensional Steady-State Conduction
Convection: Internal Flow ( )
Equipment Design Designed by Eman A. Khajah. Outline Design of Heater. Design of Stripper.
Heat Transfer/Heat Exchanger How is the heat transfer? Mechanism of Convection Applications. Mean fluid Velocity and Boundary and their effect on the rate.
Heat Transfer Equations. Fouling Layers of dirt, particles, biological growth, etc. effect resistance to heat transfer We cannot predict fouling factors.
Table of content 1- Heat exchanger design (cooler ) 2- Distillation column design. 3- Valve.
Heat Transfer Equations For “thin walled” tubes, A i = A o.
FOOD ENGINEERING DESIGN AND ECONOMICS
Heat Exchanger Design Cooler E-100 Heater E-108.
Heat Transfer Su Yongkang School of Mechanical Engineering # 1 HEAT TRANSFER CHAPTER 11 Heat Exchangers.
Done by: Zainab Al-fadhli Supervised by: Prof: M.Fahim Eng : Yusuf Ismail Kuwait university Engineering and Petroleum college Chemical Engineering Department.
Exercises for Q1. Insulated copper tube A thin walled 10 mm copper tube is used to transport a low-temperature refrigerant with a temperature that is.
Heat Transfer by Convection
Heat Transfer Su Yongkang School of Mechanical Engineering # 1 HEAT TRANSFER CHAPTER 8 Internal flow.
Mechanical Engineering Department GOVERNMENT ENGINEERING COLLEGE, DAHOD. A PPT On Derivation of LMTD for Parallel flow Heat Exchanger Prepared By:
Heat Transfer Su Yongkang School of Mechanical Engineering # 1 HEAT TRANSFER CHAPTER 8 Internal flow.
1 Chapter 5 Mass and Energy Analysis of Control Volumes.
Internal Flow: General Considerations. Entrance Conditions Must distinguish between entrance and fully developed regions. Hydrodynamic Effects: Assume.
First Law of Thermodynamics applied to Flow processes
Chapter 8: Internal Flow
One Dimensional Steady State Heat Conduction
Conservation of Mass and Energy
Influence on the performance of cryogenic counter-flow heat exchangers due to longitudinal conduction, heat in-leak and property variations Qingfeng Jiang.
Extended Surface Heat Transfer
Chapter 5 The First Law of Thermodynamics for Opened Systems
Concentric Tube (double-pipe) Heat Exchangers
Condensers.
Heat-transfer Equipment
Heat Exchangers Heat Exchangers.
Heat Exchangers Heat Exchangers.
Heat Transfer In Channels Flow
Internal Flow: General Considerations
Heat Exchangers Heat Exchangers.
Steam traps Applications and Recommendations
12. Heat Exchangers Chemical engineering 170.
Presentation transcript:

Steam Condenser II Prof. Osama El Masry Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry Steam Condenser II Prof. Osama El Masry

Steam Condenser Design Assumption while design heat exchanger The heat exchanger operates under steady-state conditions [i.e., constant flow rates and fluid temperatures (at the inlet and within the exchanger) independent of time]. Heat losses to or from the surroundings are negligible (i.e. the heat exchanger outside walls are adiabatic). There are no thermal energy sources or sinks in the exchanger walls or fluids, such as electric heating, chemical reaction, or nuclear processes. The temperature of each fluid is uniform over every cross section in counter flow and parallel flow exchangers. For a multipass exchanger, the foregoing statements apply to each pass depending on the basic flow arrangement of the passes; the fluid is considered mixed or unmixed between passes as specified.

5. Wall thermal resistance is distributed uniformly in the entire exchanger. 6.The phase change occurs at a constant temperature as for a single-component fluid at constant pressure; the effective specific heat cpeff for the phase-changing fluid is infinity in this case, and hence Cmax = m cpeff 00, where m is the fluid mass flow rate. 7. Longitudinal heat conduction in the fluids and in the wall is negligible. 8. The individual and overall heat transfer coefficients are constant (independent of temperature, time, and position) throughout the exchanger, including the case of phase changing fluids in assumption 6. 9. The specific heat of each fluid is constant throughout the exchanger, so that heat capacity rate on each side is treated as constant.

10. . The heat transfer surface area A is distributed uniformly on each fluid side in a single-pass or multipass exchanger. In a multipass unit, the heat transfer surface area is distributed uniformly in each pass, although different passes can have different surface areas. 11. The velocity and temperature at the entrance of the heat exchanger on each fluids side are uniform over the flow cross section. There is no gross flow misdistribution at the inlet. 12. The fluid flow rate is uniformly distributed through the exchanger on each fluid side in each pass i.e., no passage-to-passage or viscosity-induced misdistribution occurs in the exchanger core. Also, no flow stratification, flow bypassing, or flow leakages occur in any stream. The flow condition is characterized by the bulk (or mean) velocity at any cross section

Condenser Design H.T. Calculation Temperature Profile

Heat Transfer Dimensionless numbers and properties: Prandalt number Reynolds number Heat transfer co-efficients Inside boundary of tube Outside boundary of tube assume that outside heat transfer co-efficient is 1.5 times the inside heat transfer co-efficient Overall heat transfer co-efficient:

Heat Transfer ∆Tm= U= C1C2C3C4 √v Q = UA ∆Tm The overall H.T. coefficient U can also be expressed by the emperical Equation: C1, C2 , C3 and C4 are obtained from the tables: U= C1C2C3C4 √v

Heat Transfer Constants in Equation Tube outer diameter, in 3/4 7/8 1.0 C1 [v m/s,U W/(m2 . k)] 2777 2705 2582 Water Temp. oC 4 8 12 16 20 24 28 32 36 40 C2 0.58 0.64 0.72 0.79 0.86 0.93 1.0 1.04 1.08 1.12 Tube material 304 stainless steal Admiralty, Arsenic-copper Aluminum- Brass, Muntz metal Bronze, 90-10 Cu-Ni 70-30 Cu-Ni C3 18 gauge 0.58 1.0 0.96 0.9 0.83 17gauge 0.56 0.98 0.94 0.87 0.80 16 gauge 0.54 0.91 0.84 0.76 C4 0.58 for clean tubes, less for algae or sludged tube

A=Q/ U ∆Tm A= (πd) x l x n mw= Q/cp (T2 – T1) T2 – T1=∆Ti -∆To Surface area required A=Q/ U ∆Tm A= (πd) x l x n Water calculation mw= Q/cp (T2 – T1) T2 – T1=∆Ti -∆To cpwater=4.18 kJ/kg oK

Pressure drop in condenser water box, m (A)one-pass, (B)two-pass

Pressure drop in condenser tubes m/m length of tube

Single-pass and Two-pass condensers Mass flowrate 2 m˙ m˙ Power P 4 P Temp. difference ΔT 2 ΔT Condenser press. Pc > Pc

Example Design a condenser that would handle 1000 ton/h of 90% quality steam at 6 kPa and 120 ton/h of 45oC drain water from FWH and 0.6 ton/h of 210 oC drains from the steam jet ejector. Fresh cooling water is available at 20 oC. Solution H.T. calculation: Select: A two-pass condenser Type 304 stainless steel tubing Tubes 16 m in length, 7/8 OD, 18 BWG TTD = 4 oC Inlet water velocity 2m/s

Heat load Q = 1000 x 103 x (xhfg)+120 x 103(h45oC -hf) + 0 Heat load Q = 1000 x 103 x (xhfg)+120 x 103(h45oC -hf) + 0.6 x 103(h210oC -hf) =1000 x 103 x (2174.4)+120 x 103(36.9) + 0.6 x 103(746.2) =103x (2174400+4428+447.7)=2.175 x 109 kJ/h=604.16 x106 W ∆Ti= tsat-20=36.2-20=16.2 oC ∆To= 4 oC ∆Tm=(16.2-4)/ ln(16.2/4)=12.2/1.399=8.72 oC Q = UA ∆Tm (1) U= C1C2C3C4 √v (2) From tables From tables U= 2705x 0.86x 0.58x0.58 √2=1106.7 W/m2. oC Total surface area=62,604 m2 For 7/8-in tubes surface area/m is 0.0698 m2 and cross-section area=3.879cm2 A /π d = ltotal Total length of tubes= 896,905 m

ltotal = l x n Number of tubes=56,056 tubes 28,028 tubes/pass Water calculation: T2 – T1=∆Ti -∆To= 12.2 oC For cpwater=4.18 kJ/kg oK mw= Q/cp (T2 – T1)= 604.16 x103/4.18x12.2 =11.8x103kg/s=42,650 Ton/h check using Continuaty Equation Mass flow rate= ρ x v x A x n/2=10.87 x103kg/s=39,132 Ton/h

Pressure drop Pressure drop in water box= 0.833 m=0.0817 bar Pressure drop in tubes=0.3 m/m length=0.0294 bar Allow for 0.05 m thick tube sheet Each pass will have a length of 16.1 m Total pressure drop= 0.0294 x 2 x 16.1=0.945 bar Total pressure drop in the condenser= 0.945+0.0817=1.029 bar Power= m ∆P/ ρ=1214.63 kW