Power by Innovation… Innovation Through Partnerships Demonstration of the long-term reliability of XLPE insulation used in MV cables in South Africa by.

Slides:



Advertisements
Similar presentations
CONDITIONS FOR SUCCESSFUL INTERRUPTION:
Advertisements

Technical System Options
Moisture effect on the dielectric response and space charge behavior of mineral oil impregnated paper insulation Jian Hao1, 2, George Chen2, Ruijin.
Jicable11, June Versailles - France MODERN METHODS OF INSTALLATION AND DIAGNOSTIC TESTING OF DISTRIBUTION POWER CABLES Edward GULSKI, onsite.hv.solutions,
UNDERGROUND CABLES.
Measurement of mobility of positive charge carriers in polyethylene J Zhao, G Chen and P L Lewin University of Southampton, Southampton, UK Positive charge.
Partial discharge analysis of defective three-phase cables An overview of an ongoing project involving the generation and analysis of PD within distribution.
Capacitors for RF Applications Michael P. Busse Vice President Dielectric Laboratories, Inc 2777 Rte. 20 East Cazenovia, NY
Breakdown in Solid Dielectrics
Mr. Harethe El Ouadhane IEC member for IEC MT14. |Infrastructure Business | Germany | Test Engineer & Expert (Internal Arc, Making, Breaking.
ESTIMATION AND HYPOTHESIS TESTING
LIQUIDS AS INSULATORS Liquid dielectrics are used mainly as impregnants in high voltage cables and capacitors, and for filling up of transformers, circuit.
1 Seventh Lecture Error Analysis Instrumentation and Product Testing.
Regional Sales Manager
TESTING OF MATERIALS Name of the Subject : Material Science N. R. Dagade Electrical Engineering Department NBNSSOE, Ambegaon, Pune.
Economic Impact of Poor Power Quality on Industry Nepal Adopted from The Internet for Educational Purpose Sudaryatno Sudirham October 2003.
Transmission Lines …….. Conductor Material
Ernst Schutte African Cables 30 July CBI-electric: african cables  An empowered company  Powerhouse Utilities (Pty) Ltd  25,1% shareholding 
Codex Guidelines for the Application of HACCP
Test of the high voltage strength of Pelletron’s gas insulation (18-Dec-2008) Recycler Meeting January 21, 2009 A. Shemyakin.
Review of progress and future work SQSS Sub Group 2 August 2006 DTI / OFGEM OFFSHORE TRANSMISSION EXPERTS GROUP.
Quality Control McGraw-Hill/Irwin Copyright © 2012 by The McGraw-Hill Companies, Inc. All rights reserved.
[1] POWER CAPACITOR AND REACTIVE POWER MANAGEMENT.
Subtransmission Reliability Criteria
INSULATION RESISTANCE PROFILE (IRP) AND ITS USE FOR ASSESSING INSULATION SYSTEMS David L. McKinnon, member IEEE PdMA Corporation Tampa, FL United States.
 For AC ramp breakdown testing a Phenix AC Dielectric Test Set, Type 600C was used with a custom built test cell.  The test cell used mushroom electrodes.
Lecture 14 Sections 7.1 – 7.2 Objectives:
Chapter 7. Statistical Intervals Based on a Single Sample Weiqi Luo ( 骆伟祺 ) School of Software Sun Yat-Sen University : Office.
Frankfurt (Germany), 6-9 June 2011 Hans-Erik Olovsson – Sweden – Session 1 Network Components – Paper 0453 Innovative Compact 145/12 kV Indoor Air Insulated.
Aleksandra RAKOWSKA Jozef LORENC Witold HOPPEL Poznań University of Technology Institute of Electrical Power Engineering DISTURBANCES IN POLISH 15 KV NETWORK.
Jicable’11, June Versailles - France EXPERIENCE WITH JOINT FAILURES IN NEW SMART- GRID MV CABLE CIRCUITS Frank DE VRIES, Liandon BV, (The.
Wireless Local Loop Unit -6.
The strategy for improved electricity distribution maintenance 9 June 2008.
SINTEF Energy Research 1 Fault statistics in distribution network Regulation of quality of supply Gerd Kjølle, Norway, RT3.
5 장 Dielectrics and Insulators. Preface ‘ Ceramic dielectrics and insulators ’ is a wide-ranging and complex topic embracing many types of ceramic, physical.
Provisions, Contingent Liabilities and Contingent Assets
AC Breakdown characteristics of LDPE in the presence of crosslinking byproducts. N. Hussin and G. Chen University of Southampton, Southampton, UK Weibull.
8. Intrinsic and Related Forms of Breakdown in Solids
Standards ATAMER DIŞ TİC. A.Ş
Frankfurt (Germany), 6-9 June 2011 CELLI – IT – Main Session 2 – Paper 700 Extending Switching Reclosing Time to Reduce Interruptions in Distribution Networks.
The Effect of Nanofiller on Polyethylene System K. Y. Lau 1, 2, *, A. S. Vaughan 1, G. Chen 1 and I. L. Hosier 1 1 University of Southampton, Southampton,
Data Retention in MLC NAND FLASH Memory: Characterization, Optimization, and Recovery. 서동화
Декабрь GM52 ETOM25 Yestayev Yersultan Reliability of power cable lines.
Diagnostics of photovoltaic power plants operation Vitezslav Benda, CTU Prague, Faculty of Electrical Engineering.
1 Pacini IT Barcelona May 2003 Improvement in the Distribution Assets Management by the Exploitation of the Innovative Component Technology.
A confocal Raman microprobe analysis of partial discharge activity in gaseous voids N A Freebody 1*, A SVaughan 1, G C Montanari 2 and L Wang 2 1 University.
Chapter 4 Statistical Inference  Estimation -Confidence interval estimation for mean and proportion -Determining sample size  Hypothesis Testing -Test.
Material Processing of Polystyrene Boron Nitride Nanocomposites Raed Ayoob Supervisor(s): Thomas Andritsch and Alun Vaughan 16 September 2015 Early Career.
Rick Walker Evaluation of Out-of-Tolerance Risk 1 Evaluation of Out-of-Tolerance Risk in Measuring and Test Equipment Rick Walker Fluke - Hart Scientific.
Acknowledgements: This Research was sponsored by ONR Funds: N Study on the Electrical Performance and Aging of Polymer Insulation S. Grzybowski.
Ben Dyson Earth Supply Ltd Alternative feedstock for sustainable growing media: Compost.
Failure Modes, Effects and Criticality Analysis
TRANSMISSION AND DISTRIBUTION
Ageing Phenomena in Cables Insulation Materials Condition Monitoring of Electrical Equipment Spring 2016 Edit by Ilaria Mele.
Influence of humidity on the IV characteristics A.Chilingarov Lancaster University ATLAS SCT Week CERN,
© 2016 Minitab, Inc. Reliability for Your Company's Survival Bonnie Stone, Minitab October 19,
Comparison of AIS and GIS Grid Station Muhammad Ali Ashraf Management Associate (Electrical) CPP Project.
Hipot Testing 101.
Ms. Tahoora Qureshi, Asst. Professor
Introduction Purpose To explain the characteristics and features of the RTAN Series Precision Tantalum Nitride Thin Film Resistors Objectives To provide.
Chapter 5 Hypothesis Testing
Capacitors for RF Applications Michael P. Busse Vice President
Oil-tight MV fuse CEF-OT with TPC bushings
Sequential Analysis Team: The Authors 11/22/2018 Case 16 Example.
Overhead Conductors.
Inter-Laboratory Comparison Exercise CPC CALIBRATION
Transformer Loading Considerations
1. TURBOGENERATOR ROTOR WINDINGS
Biosco: MV/LV prefabricated substations IEC Presentation of the standard Safety is a choice.
Presentation transcript:

Power by Innovation… Innovation Through Partnerships Demonstration of the long-term reliability of XLPE insulation used in MV cables in South Africa by Pravesh Haripersad Design Engineer

 What is meant by MV cables?  What is the current reliability of such cables?  What are water trees?  How does a cable manufacturer demonstrate long- term reliability of their cables?  Discussion of the 50Hz and 500Hz ageing tests conducted!  What service-life can one expect?  What is the benefit of conducting both ageing tests?  Conclusions Presentation will address the following questions or concerns:

What is meant by MV cables?

Introduction to MV cables  MV cables range from 3.3kV to 33kV  Two primary insulations: Paper Insulated Lead Covered (PILC) Cross-linked Polyethylene (XLPE) SANS 97SANS 1339 Compulsory Specifications!

What is the current reliability of such cables?

 PILC cables known to have high reliability – some in service well over 50 years!  Similar reliability not reported for the first XLPE cables installed in the 1970’s and 1980’s: -Premature failures occurred mainly due to the presence of impurities and contaminants within the XLPE insulation  XLPE insulation cleanliness and production/process technologies have evolved considerably (depending on Manufacturer, ofcourse!!)  The quality of manufactured XLPE cables is so high that it is becoming the preferred insulation even at 500kV!! -Lower dielectric losses; higher operating temperatures thus higher ampacities; lower environmental impact Long-term reliability of MV XLPE cables Long-term reliability of MV XLPE cables

 Service-life expectancy of a good quality, defect free XLPE cable operating under normal conditions is estimated to be in excess of 30 years !!  The following factors reduce this long-term reliability: - presence of impurities and contaminants - increase in operating voltage (electric stress) - increase in operating frequency - increase in operating temperature - the presence of water trees  A 10 o C increase in operating temperature reduces cable life expectancy by up to 50%!!!  Presence of water trees in XLPE insulation reduces cable life expectancy by up to 43%!!!

What are water trees?

Water trees in XLPE cables Water trees in XLPE cables  Water has an adverse effect on XLPE insulation as it develops water trees !!

Water trees in XLPE cables Water trees in XLPE cables  Generally, MV XLPE cables are not water blocked  No definite mechanism whereby water trees arise, but one possibility is by diffusion: Water enters by diffusion Add impurities, voltage, temperature and frequency Bow-tie tree Vented tree

Water trees in XLPE cables Water trees in XLPE cables  Water trees are microscopic and are usually invisible to the naked eye  Insulation is stained and examined using a microscope A Vented tree A Bow-tie tree

Water trees in XLPE cables Water trees in XLPE cables  Water tree development and growth dependant on: - presence of water - presence of impurities or contaminants - alternating electrical stress - frequency - temperature  Water trees develop into conductive electrical trees which ‘bridge’ the insulation causing failure  Growth of an electrical tree from a needle point inserted into XLPE insulation: Play

How does a cable manufacturer demonstrate long-term reliability of their cables? (50Hz and 500Hz ageing tests)

Demonstration of long-term Demonstration of long-term reliability (50Hz or 500Hz ageing)  To demonstrate good quality and long-term reliability, cable manufacturers are compelled to conduct either a: - 2 year, 50Hz ageing test, or a - 4 month, 500Hz ageing test  The main ageing mechanisms that will be applied to the cable are: - increased electrical stress (3 x Uo) - frequency (50Hz or 500Hz) - growth of water trees

Demonstration of long-term Demonstration of long-term reliability (50Hz or 500Hz ageing)  500Hz ageing test is attractive due to shorter duration, 4 months vs 2 years!!  Only two local companies are known to have 500Hz ageing test facilities in the country CBi electric: african cables 500Hz ageing test lab

Demonstration of long-term Demonstration of long-term reliability (50Hz or 500Hz ageing) CBi electric: african cables 50Hz ageing test area Setup as per SANS

Demonstration of long-term Demonstration of long-term reliability (50Hz or 500Hz ageing)  At end of ageing, 12 samples, each 10m long are subjected to stepped breakdown test at 1Uo for 5 minutes  Passing criteria is based on breakdown strength, not on water tree count!  Test requirements according to SANS 1339: Minimum withstand stressNumber of samples that must achieve this 14 kV/mm12 18 kV/mm9 22 kV/mm5

50Hz and 500Hz ageing tests conducted by CBi electric:african cables and a discussion of the results!

 African Cables have conducted both ageing tests in strict accordance to SANS 1339: Test results, comparisons Test results, comparisons and discussions 50Hz ageing test 500Hz ageing test Started Mar 2003April 2003 CompletedJuly 2005Dec 2003 Size95mm² x 1 Al240mm² x 1 Cu Cable voltage6.35/11kV XLPE thickness3.5mm Length120m Applied test voltage19kV (3Uo)

Test results, comparisons Test results, comparisons and discussions 50Hz aged sample about to be broken down in 1Uo, 5 minute steps

Test results, comparisons Test results, comparisons and discussions Test technician configuring and programming the test set

Test results, comparisons Test results, comparisons and discussions The 11kV, 2 year aged sample withstood 80.7kV (13Uo or 30kV/mm) !!!

Test results, comparisons Test results, comparisons and discussions Sample cut at breakdown site!!

and discussions Test results, comparisons Test results, comparisons 50Hz ageing test 500Hz ageing test Withstand  14kV/mm 12 Withstand  18kV/mm 1211 Withstand  22kV/mm 1211 Type test resultSUCCESSFULLY COMPLIED!!  Breakdown assessment of aged samples:

Test results, comparisons Test results, comparisons and discussions  Breakdown data analysed using Weibull Distribution: 63% characteristic breakdown strength 50Hz500Hz 37.5 kV/mm 32.5 kV/mm Unaged cable has a typical breakdown strength of 50 kV/mm!!!

Test results, comparisons Test results, comparisons and discussions  Water tree analysis:

Test results, comparisons Test results, comparisons and discussions  Water tree analysis: 50Hz ageing test 500Hz ageing test Number of vented trees near inner semicon 13 (  600µm) 0 Number of vented trees near outer semicon00 Number of bow-tie trees0 2 (  100µm)

Test results, comparisons Test results, comparisons and discussions The bow-tie tree observed in the 500Hz aged sample

What service-life can one expect?

Cable life-expectancy n = 9 30 years

What is the benefit of conducting both ageing tests?

Effectiveness of the two ageing tests  Both tests met all breakdown strength criteria of SANS 1339  Some differences in results, but not significant differences: - 63% characteristic breakdown strength of 500Hz is 5kV/mm lower than 50Hz - slope of 50Hz Weibull plot is steeper than 500Hz plot - 50Hz produced more water trees than 500Hz  Above indicates that there are numerous ageing mechanisms taking place  Passing both 50Hz and 500Hz test gives greater confidence of good quality and long-term reliability of the cables

Conclusions

Conclusions  Paper highlights two different approaches taken by African Cables to demonstrate long-term reliability of their MV XLPE cables  Results of ageing show that even after 30 years, cables will have breakdown strengths in excess of 10Uo  Water tree ageing mechanism produced little water trees, confirming high quality and defect free XLPE insulation  Such results enable a customer to easily satisfy himself of the level of quality and long-term reliability of the cable  CBi electric: african cables have demonstrated that they offer only high quality MV XLPE cables with a long-term reliability

Power by Innovation… Innovation Through Partnerships Thank you and visit us at: