The outdoor section Now that we’ve checked our thermostat and air handler, we’re ready to check the outdoor unit.

Slides:



Advertisements
Similar presentations
Wall Mounted J series Troubleshooting.
Advertisements

Operating Functions.
Daikin Altherma™ Troubling Shooting
Thermostats, Pressure Switches, and Other Electric Control Devices
Thermostats. I would recommend that as you proceed through this power point presentation that you refer to your textbook, Unit 14, for some great visuals.
HEAT PUMPS.
Refrigerators.
HEATING AIR © Commonwealth of Australia 2010 | Licensed under AEShareNet Share and Return licence.
Setup/Installation/Operation of an Environmental Control Unit (ECU)
AC-SSC-1 Installation and operation manual
Basic Refrigeration Cycle
Left Side Discharge Pressure Regulator
38GXC(Q)/40GXC(Q) Service Training Sizes 18 and 24K.
Refrigeration Flow Control
HVACR312 - Refrigeration Metering Devices.
C oncerns Ltd ool Energy Efficient Refrigeration Jane Gartshore, Cool Concerns Ltd.
AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS
HVACR416 - Design Humidification. Relative Humidity 1.Air in the home is artificially dried out when it is heated. 2.Because warm air expands, this expansion.
2013 Microwave Service Training All models. Samsung HA Warranty ALL Warranties are subject to change, always verify. 1 Year Parts & Labor Base Warranty,
PHSAUTOMOTIVESALSPHSAUTOMOTIVESALS Charging System tests & Voltage information Checking the charging system with just a volt meter.
Product Introduction.
Oil Pressure Problems What to look for.
Variable Speed Indoor Blower Motor Robert Helt Technical Conference - Panama City Beach, Fl
E2 Motors and Motor Starting
Electrical Electricity Fuses Relays Solenoids Electrical Testing
2-Stage Heat Pump Defrost Options Defrost options: –30, 60, 90, 120 or Auto (Infinity/Evolution only) Defrost initiate temp: 32° F Defrost terminate temp:
Fan Switch and Limit Switch Information. FAN Switch.
Troubleshooting Electric Control Devices
Air-Source Heat Pumps I North Seattle Community College HVAC Program Instructor – Mark T. Weber, M.Ed. Airsource Heat Pump 1.
Learning, our way Examples of bad installation. CONTENT Installation related examples Installation related examples Application related examples Application.
General Troubleshooting Tips.
RESIDENTIAL AIR HANDLERS
HYDRONIC HEATING AQUASTATS
Air Handler Terminology
Air Handler Terminology
Introduction to Defrost
TECHNICAL TRAINING INVERTER-Y
Fan Coils Units Control
Rule #1 Also known as Daryl’s words to live by.
SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43.
STEP 1 Locate the transmission cooler line connection on the vehicle. Identify the correct adapters to be used by referring to the vehicle application.
© 2012 MITSUBISHI HEAVY INDUSTRIES – MAHAJAK AIR CONDITIONERS CO., LTD. All Rights Reserved. Bad case of Installation RAC-B-A07.
We apply 120 VAC to the HM Unit (Remember to check polarity!) Our primary step down T/X provides power to terminal “X” and “COM” on the ignition control.
All Freezer Advance. When the Freezer is first supplied with power or if a power outage occurs, the display will indicate this by flashing the temperature.
AIR CONDITIONING (COOLING)
BASIC ELECTRICITY AND MAGNETISM
Air condition installation
James McIntyre VRF Training Manager V5 Key Components.
shift to the Test Mode (Forced Operation).
TXV Devices.
Two Stage Communicating System
. Level 3 Air Conditioning Inspections for Buildings
Student CD for Commercial Refrigeration for A/C Technicians Chapter 12 Ice Machines.
The Refrigeration Cycle (Air Conditioners)
R3 Controls, Valves, Accessories & Heat Pumps
By: JAGDEEP SANGWAN Refrigeration Basics 101.
Error codes for split systems
Presentation transcript:

The outdoor section Now that we’ve checked our thermostat and air handler, we’re ready to check the outdoor unit.

Setting the outdoor unit on the shipped with ISO pads, will help reduce sound transmission through the ground. The concrete pad should not be touching the structure, for this same reason. The unit should be set to prevent air re- circulation across it’s coil. See the installation instructions for that unit. The outdoor section

HEAT PUMP REVERSING VALUE ILLUSTRATION

. TP-4. TP-3. TP-2. TP-1 SUCTION LINE INDOOR COILOUT DOOR COIL COMPRESSOR DISCHARGE

.... FROM OUTSIDE COIL TO ACCUMULATOR TO INDOOR COIL TP-4 TP-3 TP-2 TP-1 FROM COMPRESSOR DISCHARGE LINE HEATING MODE 5F MAX TEMP. DIFFERENCE

.. TP-4. TP TP-1... TP-3 TO OUTDOOR COIL TO ACCUMULATOR FROM INDOOR COIL FROM COMPRESSOR DISCHARGE LINE COOLING MODE 5F MAX TEMP. DIFFERENCE

COOLING CONDITION INDOOR COIL SAT. SUCT. T. 41F ENT. AIR T. 76F OUTDOOR COIL SAT. COND. T. 120F ENT. AIR T. 90F 4-WAY VALVE SUCT. P. 70 PSIG SUCT. T. 52F SUPERHEAT 11F DISCHARGE PRESSURE 260 PSIG METERING DEVICE SUBCOOLING 10F COMPRESSOR

HEATING CONDITIONS INDOOR COIL OUTDOOR COIL METERING DEVICE SUBCOOLING 10F SAT. COND. T. 95F ENT. AIR T. 70F SAT. SUCT. T. 20F ENT. AIR T. 45F 4-WAY VALVE DISCHARGE PRESSURE 182 PSIG METERING DEVICE SUBCOOLING 10F SUCT. P. 43 PSIG SUCT. T. 35F SUPERHEAT 10F COMPRESSOR

HEAT PUMP TOTAL HEAT REJECTED EQUALS HEAT ABSORBED + HEAT OF COMPRESSOR

HEAT PUMP METERING DEVICES –HEATING CYCLE, REFRIGERANT IS METERED TO THE OUTDOOR COIL –COOLING CYCLE, REFRIGERANT IS METERED TO THE INDOOR COIL

HEAT PUMP METERING DEVICES REFRIGERANT METERED TO COIL WHICH ABSORBS HEAT HEATING CYCLE REFRIGERANT METERED TO OUTDOOR COIL COOLING CYCLE REFRIGERANT METERED TO INDOOR COIL

METERING DEVICES CAPTUBE FIXED ORFICE TXV

METERING DEVICES CHECK VALVE SHUT CHECK VALVE OPEN METERING DEVICE METERING DEVICE FLOW IS METERED FLOW BYPASSES METERING DEVICE

Spine fin coil is used for it’s efficiency. The majority of all heat transfer is done on the leading edge (the tip, where the air and coil first come into contact) of the fin. A spine fin coil is much more efficient than a plate fin coil. So much so that it can do the same job with much less refrigerant. Spine fin coils can easily be repaired. Not in your books The outdoor coil

As mentioned earlier the outdoor coil will produce run off during defrost. This water is normal and has not been known to cause damage in the past! This water must drain freely from the unit. Any sort of drain/collection system would need to have some form of a heater to keep from freezing up and damaging the outdoor coil. Not in your books

The role of the defrost control To extract heat from the outdoor air, the heat pump must lower it’s outdoor coil temperature below that of the outdoor ambient. Depending on the humidity and temperature, frost may form on the outdoor coil. This frost will insulate the coil from the outdoor air, reducing it’s ability to absorb the heat from the outdoor air.

HEAT PUMP DEFROST CONTROLS - CONTROLS THE DEFROST CYCLE IN A HEAT PUMP DURING HEATING OPERATION. -THE DEFROST CONTROL CONTROLS THE FOLLOWING FUNCTIONS: 1 - SWITCH OVER VALVE OR REVERSING VALVE 2 - OUTDOOR FAN MOTOR 3 - ELECTRIC OR GAS AUX. HEAT 4 - INDICATES A FAULT HAS OCCURRED (OPTIONAL) -CONTROL THAT ESTABLISHES THE NEED FOR A DEFROST -BOTH TIMED AND DEMAND CONTROLS ARE USED TODAY -ELECTRO MECHANICAL TIMERS AND PRESSURE SWITCHES USED IN THE PAST

Heat pump defrost controls Several types of defrost controls have been used through the years. We will discuss their function and diagnostics of each type. The newer solid state and Demand Defrost controls will be the main focus of our time today.

SYSTEM IN COOLING MODE- -ENERGIZE REVERSING VALVE –DIRECTS HOT GAS TO OUTDOOR COIL TO MELT THE FROST DEFROST CYCLE

As the frost accumulates on the outdoor coil, the systems capacity is reduced. Ö To remove the frost/ice from the outdoor coil, the system will shift itself into a variation of the cooling mode. Ö During a defrost cycle the outdoor fan will stop, leaving the heat in the coil to remove the frost. Ö The type of defrost control system will dictate how much frost/ice is allowed to accumulate prior to initiating a defrost.

DEFROST CYCLE TEMPERING INDOOR AIR –ELECTRIC HEAT IS TURNED ON TO TEMPER THE AIR DURING DEFROST CYCLE.

DEFROST CONTROLS THE MUCH OLDER EQUIPMENT UTILIZED ELECTRO-MECHANICAL TIME CLOCKS. ELECTRONIC TIMER - TIME & TEMPERATURE DEFROST SOLID STATE - DEMAND DEFROST

DEFROST CYCLE OUTDOOR FAN OFF –ENHANCES DEFROST

Electro-Mechanical systems çAll electro-mechanical systems are a “time/temperature” based control. çA predetermined amount of time must pass before a defrost cycle can be initiated. çAs mentioned earlier, the outdoor conditions have major impact on the amount of defrost needed. çThese systems are temperature activated as well.

Large amounts of frost may accumulate before the “Time” has elapsed. This results in lower seasonal efficiency. The reduced capacity will result with a greater dependence on a secondary heat source.

ELECTRONIC TIME-TEMPERATURE DEFROST CONTROL MINUTE COMPRESSOR RUN TIME SELECTION 10 MINUTE TIME OVERRIDE IN DEFROST CYCLE TWO TEST PINS - ADVANCES ELECTRONIC TIMER AND PUTS SYSTEM INTO DEFROST CYCLE FOR TESTING ON BOARD DEFROST RELAYS FOR OUTDOOR FAN, SOV VALVE AND AUXILIARY HEAT DEFROST TERMINATED ON TIME OR TEMPERATURE COMPRESSOR RUN TIME IS KEPT ONLY WHEN COIL THERMOSTAT IS CLOSED

The defrost thermostat is set to close at 25º. When the DT is closed, supplying 24 VAC to the D terminal, jumpering the test pins will speed up the internal clock. If you are testing the system, and have a jumper from R to D, remove the jumper as soon as the system shifts into defrost to prevent excessive refrigerant pressures.

These controls will default to the 90 minute setting if the selector jumper is not connected. Which is how the equipment is shipped. I recommend one of the shorter time settings, 50 or 70 minutes. The water run off from a unit in defrost is pure water, and has never been reported to caused roof damage to date! Trying to catch the water could damage the outdoor coil (if the collected water froze and backed up under the coil).

TST EDR R R B B X2 Y O O D T DFC CNT1152 OR CNT CNT1152 may be replaced by CNT K2 M1 M2 OD FAN K1 24V AC 24V COMMON INDOOR THERMOSTAT DT MS SC

DT SC TR TR1 EDC OR LPCO MS F G EDR DFC CNT1642 K1 K2 M1 M2 OD FAN TST EDR R R B B X2 Y O O DT T X2 YOTYOT INDOOR THERMOSTAT 24V AC 24V COMMON INDOOR THERMOSTAT COMMON FOR ELECTRIC HEATER ECONOMIZER (OPTIONAL)

TIMER DEFROST CONTROL

TST EDR R R B B X2 Y O O D T

There are several versions of these DFC boards. Many feature the exact same functions, with the only difference being the terminal for the defrost thermostat being labeled “D” or “DT”.

TST EDR R R B B X2 Y O O D T There are several versions of these DFC boards. Many feature the exact same functions, with the only difference being the terminal for the defrost thermostat being labeled “D” or “DT”.

TST EDR R R B B X2 Y O O D T There are several versions of these DFC boards. Many feature the exact same functions, with the only difference being the terminal for the defrost thermostat being labeled “D” or “DT”.

TST EDR R R B B X2 Y O O D T There are several versions of these DFC boards. Many feature the exact same functions, with the only difference being the terminal for the defrost thermostat being labeled “D” or “DT”.

TST EDR R R B B X2 Y O O D T There are several versions of these DFC boards. Many feature the exact same functions, with the only difference being the terminal for the defrost thermostat being labeled “D” or “DT”.

TST EDR R R B B X2 Y O O D T There are several versions of these DFC boards. Many feature the exact same functions, with the only difference being the terminal for the defrost thermostat being labeled “D” or “DT”.

DEMAND DEFROST CONTROLS

DEMAND DEFROST FEATURES –ADAPTABILITY –LEARNING PROCESS –DEFROST ON DEMAND –DIAGNOSTICS –TIME OVERRIDE –SOFT SWITCHOVER

DEMAND DEFROST CONTROLS

HEAT PUMP DEMAND DEFROST CONTROLS - THE DEMAND DEFROST CONTROL WAS DEVELOPED BY TRANE IN 1984 AND IS PATENTED. -HEAT PUMP SYSTEMS WITH DEMAND DEFROST CONTROLS BENEFIT FROM A 6% HEATING SEASONAL PERFORMANCE FACTOR (HSPF) ADVANTAGE. -THERMISTOR SENSORS SENSE THE OUTDOOR AMBIENT TEMPERATURE AND OUTDOOR COIL TEMPERATURE. -THE DIFFERENCE BETWEEN THE OUTDOOR TEMPERATURE AND THE OUTDOOR COIL TEMPERATURE IS CALLED THE DELTA TEMPERATURE OR JUST DELTA-T.

HEAT PUMP DEMAND DEFROST CONTROLS -TRANE DEMAND DEFROST CONTROLS OPERATE IN AN ADAPTIVE PROCESS TO OPTIMIZE THE HEAT PUMP PERFORMANCE. -THE DEMAND DEFROST CONTROL WILL ADAPT TO THE HEAT PUMP IT IS INSTALLED ON AND LEARN ITS OPTIMUM DEFROST CONDITIONS AND STORE THEM IN MEMORY. -THE DEMAND DEFROST CONTROL WILL ADJUST THE TIME BETWEEN DEFROST CYCLES TO MATCH THE WEATHER CONDITIONS.

The Defrost Cycle is Initiated As ice builds on the coil, the delta-t of the system increases until it reaches the initiate value, and the control starts the defrost process. The initiate value is not constant, but instead, is a value that the defrost control has learned will provide a fast, thorough defrost at a given outdoor temperature. Low initiate values waste energy by defrosting too often, while high initiate values fail to defrost the coils thoroughly. The control is continually varying the initiate value slightly to learn the best value. It measures the success of each initiate value by measuring the delta-t of the system during the next heating cycle.

DEFROST IS TERMINATED Once the temperature of the outdoor coil reaches the termination value, the defrost control turns on the outdoor fan. After waiting the soft-switch over time, it changes the switch over valve to the heating mode. This soft-switch over delay time, 12 seconds, gives the outdoor coil time to cool, reducing the refrigerant pressure and reducing the surge that occurs when the switch over valve is switched. If the compressor or “Y” cycles off during defrost, the switchover valve remains energized but the “X2” output will be OFF. If “Y” cycles off during the soft-switchover time, the switchover valve is switched OFF immediately.

Normal operation

Demand Defrost Control Operation Requirements for defrost initialization 1 - The outdoor temperature must be less than 52 F 2 -The coil temperature must be less than 33 F 3 -The Y line must be energized for a least 128 seconds 4 -The delta-T must be greater than the initiate temperature 5 - It must be time for a timed defrost minutes of run time have passed since the unit was first powered up

Demand Defrost Control Operation If the unit is placed into a forced defrost by placing the test jumper in the FRC DFT position and Y is energized, none of the above conditions need to be met.

Requirements for Defrost Termination The coil temperature must exceed the terminate value. If the outdoor temperature is greater than 22 F, the terminate value is 47 F. If the outdoor temperature is less than 10 F, the terminate value is 35 F. If the outdoor temperature is between 10 F to 22 F, the terminate value is 25 F plus the outdoor temperature.OR The defrost control has a 15 minute override time.

The Test Mode The control may be placed into a test mode by placing the RED jumper wire on the TST pin. This will cause the LED to blink rapidly and the operation of the control will be sped up by a factor of 10. The controller will run normally once the jumper is removed from the TST pin.

Fault Indications There are three types of faults the demand defrost control can experience. All three faults can cause the defrost control to change from a demand defrost control to a timed defrost control which defrosts the unit every 30 minutes. When the control goes into a timed defrost mode due to a FAULT A or FAULT C, on units that have the F line feature, it alerts the home owner by energizing the F line once every second which flashes a fault light on the thermostat. If the thermostat is switched to the emergency heat position, the F line will be energized, and the defrost control will be cleared of all faults after a few seconds.

Fault Indications FAULT A is indicated by 2 led flashes per second. FAULT A is caused by one of two conditions: 1 - During heating the system's delta-T is unusually low. (The capacity of the system is lower than it should be.) 2 - After 12 minutes of operation since the defrost termination, delta-T is greater than the initiate value. After running in a FAULT A condition for 30 minutes, the defrost control will indicate it by flashing the LED. After running 2 hours with this fault, the demand defrost control will then change to a timed defrost operation, and the homeowner will be notified via the F line.

Fault Indications FAULT A can be cleared by any one of the following operations: 1 - If the control has two normal defrost cycles (If the fault has been present long enough for the Fault light to start Flashing, it will flash until the first normal defrost.) 2 - If power is removed from the defrost control for more than 30 seconds. 3 - If the F line is energized for a few seconds.

Fault A

Fault Indications FAULT B is indicated by 3 led flashes per second. FAULT B is caused by 10 successive failures of the heat pump to terminate on temperature during the defrost cycle. The unit will stop defrosting after 15 minutes due to the override timer. Once a FAULT B occurs, the control will indicate it by flashing the led. After FAULT B occurs 10 times, the control will act as a timer defrost control.

Fault Indications FAULT B can be cleared by any one of the following operations: 1 - If the control reaches the terminate value during one of the timed defrost cycles. (Since this fault is pretty common in cold climates with high winds, this fault does not alert the home owner via the F line.) 2 - If power is removed from the defrost control for more than 30 seconds. 3 - If the F line is energized for a few seconds.

Fault Indications FAULT C is indicated by 3 led flashes per second. FAULT C is caused by 15 successive faults in which the unit has an unusually high delta-T 15 minutes after a defrost termination. (Poor air flow over outdoor coils - they are probably blocked by ice.)

Fault Indications FAULT C can be cleared by any one of the following operations: 1 - If the unit has a normal delta-T 15 minutes after a defrost. (If the fault has been present long enough for the Fault light to start flashing, it will continue to flash until there is a defrost cycle without a high delta-T fault.) 2 - If power is removed from the defrost control for more than 30 seconds 3 -If the F line is energized for a few seconds

Fault B or C

Combination Fault Indications FAULT A & FAULT B, indicated by 4 led flashes per second, is caused by 60 or more FAULT A's occurring and one or more FAULT B's occurring. FAULT A & FAULT C, indicated by 4 led flashes per second, is caused by 60 or more FAULT A's occurring and one or more FAULT C's occurring. Combination faults will notify the home owner by toggling the F line. Combination faults can be cleared by any one of the following operations: 1 - If the F line is energized for a few seconds 2 - If power is removed from the defrost control for more than 30 seconds

Power-up Initial Defrost After the defrost board is powered up, its first defrost cycle will be a timed cycle. On the newer boards, the unit must run during defrosting conditions for 30 minutes while some older boards must run for 45 minutes. Assuming there are no faults, subsequent defrost cycles will be performed on demand. The delay in each case can be reduced to 1/5 this time by placing the red jumper lead on the TST terminal.

Forcing the Unit to Defrost Placing the red jumper wire on the FRC DFT pin, the defrost board can be forced to initiate a defrost immediately even if outside temperature conditions are not met. The only requirement is that the compressor is running or the “Y” signal is present. The defrost will be terminated normally when the outdoor coil becomes hot enough. If the jumper is still on the FRC DFT lead upon defrost termination, it will initiate the defrost cycle again.

No Fault Found DON’T REPLACE IT! –If LED blinks, –& Sensors ohm out OK, –& Forced defrost works. Look Elsewhere For Cause(s) Package Unit Ambient Sensor Bracket –Added for better ambient sensing

ODS-A Thermistor Failures Cause –Field miss-wire during installation Solution –X2 wire color changed from BR/X2 to BK DO NOT REPLACE CONTROL –Use RES0118 ODS-A kit –Needed ONLY for GE “blue light” thermostat

Temperature Sensors The temperature sensors are temperature dependent resistors encased in a heat-shrunk plastic shroud and sealed from air and moisture by a hot glue adhesive fill. The resistance of the sensor decreases as temperature increases according to a specified curve. See the temperature / resistance curve provided with the service information. It is rare for a temperature sensor to fail, and most that have been replaced in warranty were OK, or they had been damaged by rough handling.

Temperature Sensors A common problem with sensors is damage inflicted by forcing ohmmeter probes into their connectors. This permanently bends the contact causing an intermittent connection. On some package units, the sensor leads have been pinched by the access panel. Checking the sensor resistance to ground will detect this problem.

RESISTANCE DEFROST THERMISTOR RESISTANCE OUTDOOR TEMPERATURE

To avoid damage to the connectors when ohming out insert some short pieces of thermostat wire into the sensor connectors, NOT your meter leads. Thermostat wire slid in to openings for control board pins (18awg. MAX). Take readings here.

Check Out Procedure The following tests are to be performed to check for proper operation after installation of the demand defrost control. Step 1: Apply power to the system and operate in heating mode. The switchover valve should be off (heating mode), and the outdoor fan should be on. Step 2: Check to be sure the led on the defrost board is blinking once every second and the fault light on the thermostat is off. Step3: Force the system to defrost by placing the red jumper wire on the FRC DFT pin.

Check Out Procedure As the unit goes through the defrost process, the switchover valve should be energized, the auxiliary heat should be on and the outdoor fan motor should be off. Step 4: Monitor the system to be sure it stops defrost within 15 minutes. Step 5: At the end of the defrost cycle, the outdoor fan should come on, and after a 12 second delay, the unit will switch back to the heating mode.

Check Out Procedure Step 6: If the board has the fault light feature (G15-G17& G19-G20), test this feature by placing the red jumper wire on the FRC FLT pin for a few seconds then return the red jumper wire to the NORM pin. This should cause the led on the defrost board to blink four times a second, and the indoor fault indicator on the thermostat should be blinking once a second. Step 7: Switch the indoor thermostat to the emergency heating position for at least 30 seconds and then back to the heat pumps position. The indoor fault indicator should stop blinking and the LED should blink once a second indicating that everything is normal.

Helpful Hints in Case of Difficulty Led fails to blink on the defrost board If the led is off, check between R and B to be sure 24 volts is present. Remove power for one minute and re- apply power. Check to see if the LED starts flashing.

Helpful Hints in Case of Difficulty LED flashes, but the unit fails the forced defrost test. 1. Be sure the red jumper wire was returned to the NORM pin. 2. Make sure the thermostat is calling for heating (24 V on Y) 3. Verify that the sensors are connected and mounted in the right places 4. Check the electrical connections to the defrost board (24V on O while defrosting) 5. There is a 1 minute minimum time in defrost under normal operation. If defrost is forced there is no minimum time in defrost.

Helpful Hints in Case of Difficulty 1-The indoor fault indicator goes on and then goes off. During extreme weather conditions, the unit may have difficulty defrosting. This will cause a fault and alert the owner, but when the weather is more temperate, the fault will clear and the indicator will stop blinking. 2 -The outdoor sensor (ODS) is burnt on the defrost board. Check control wiring “T” and “X2”. On the newer units the X2 lead is black and this is not as likely to happen.

On Equipment with ICM-2 indoor fan motors if unit changes indoor fan speed during defrost, check dip switch 7 & 8 settings. If system has supplemental strips installed, X2 is energizing them and the blower is responding to it’s dip switch settings. Helpful Hints in Case of Difficulty

On systems that do not have supplemental heat strips, do not connect thermostat wiring to W1, W2, or W3 connections. On package equipment verify unused control wires are individually isolated. Verify sensors are making proper contact to the pins on the DFC. Helpful Hints in Case of Difficulty

USE SCREWDRIVER HERE AND HERE TO LIFT UP SO IT LOOKS LIKE THIS PRESS DOWN ON TAB TO RELEASE THE SPRING CONNECTOR

Demand Defrost Control Problems Excessive Ice Built-up on OD Coil Low refrigerant charge Defrost Control will not Initiate A. No 24 VAC between R&B at defrost control B.No 24 VAC between B&Y at defrost control with system running C.Verify correct sensor location, mounting & their resistance D.Verify ambient sensor is connected to AMB position on defrost control E.Verify coil sensor is connected to coil position on defrost control

Demand Defrost Control Problems Excessive Ice Built-up on OD Coil SOV Inoperative A.Stuck in heating mode B.Open switchover valve (SOV) coil C.Defective defrost control Defrost control contacts to OD fan fail to open during defrost cycle

Demand Defrost Control Problems Excessive Ice Built-up on OD Coil Defrost control terminates, but does not remove ice A.Windy conditions B.Outdoor unit located under eaves C.Lack of proper drainage D.Night setback operation

Ice Build Up on Lower Part of Outdoor Coil Low refrigerant charge Coil sensor connected to wrong pass of outdoor coil, or poor contact Leaking check valve (outdoor unit) Distributor tube restricted One pass of OD coil restricted Lack of proper drainage

Defrost Initiates, but Terminates Only on a Time Override Low refrigerant charge Outdoor fan on during defrost Windy conditions Night setback operation Unit location Coil sensor in contact with ice Coil sensor circuit open or reading very high resistance.

Defrost Cycle Initiates, but Will Not Terminate Switch-over valve stuck in cooling mode Sensors not making proper contact to DFC pins. Defrost Control

Unit Goes Into Defrost In Cooling Mode Defective Sensors Defective Defrost Control

Control Terminates Defrost Before Frost Is Gone Coil sensor mounted in wrong location or has incorrect resistance reading Refrigerant overcharge

Defrost Initiates About Every 15 Minutes Coil sensor Ambient sensor Defrost control

Defrost Initiates About Every 30 Minutes. Fault Light on Indoor Thermostat Will Be Flashing If Wired Coil sensor Ambient sensor Weather conditions Night setback operation Outdoor fan on during defrost System refrigerant charge SOV operation

Two-Compressor Controllers Tyler Version For V.S. OD Fan Motor –Cooling model 21C150624G02, CNT2275 –Heat pump model 21C150625G02, CNT2276

Two-Compressor Controllers Ft. Smith Version for PSC Fan Motor –Cooling model 21C150624G01, CNT1858 –Heatpump model 21C150625G01, CNT1859

Heat Pump Control