American Electric Power Service Corporation Jan 26, Coordinating Controls across CREZ What dials are available to the operators? What are the hand-offs between the ISO and TO? What does it take to implement controls in the field?
American Electric Power Service Corporation Jan 26, What dials are available to the operators? Reactive Resources Static vs Dynamic Inductive vs Capacitive Power Flow control Line switching Phase Shift Transformers Series Capacitors
American Electric Power Service Corporation Jan 26, Syncro-Phasor Voltage (high wind production) DFW Angle Magnitude Houston Valley Mid/Ods Generation Power Flow
American Electric Power Service Corporation Jan 26, What are the hand-offs between the ISO and TO? Traditional Automatic Voltage Regulator with target kV Power Flow Controller with target MW Alternative Approach Reactive Reserve targets Real Power limits
American Electric Power Service Corporation Jan 26, What does it take to the implement controls? Reserves Local real and reactive systems must have head room to respond to disturbances Anticipation State Estimator predicts post-contingency conditions Preemptive scheduling of set points, so that local control can regulate back into secure positions
American Electric Power Service Corporation Jan 26, Definitions for Reactive Reserve Controller DRCS Dynamic Reactive Compensation System —Automation to control static and variable reactive power devices as an integral system SSD Static Shunt Device —Fixed capacitor or reactor bank
American Electric Power Service Corporation Jan 26, DRCS Block Diagram – SVC/STATCOM
American Electric Power Service Corporation Jan 26, SSD Controller Terms V DRCS Voltage on bus regulated by dynamic device V SSD Voltage on bus with SSDs Q DRCS Reactive power output (± MVAR) of dynamic device Increment Increase reactive power to grid (e.g. close cap or trip reactor) Decrement Decrease reactive power to grid (e.g. trip cap or close reactor)
American Electric Power Service Corporation Jan 26, SSD Controller Terms (continued) Scheduled Voltage Regulation setting for dynamic reactive device Midpoint Setting by operator for voltage or reactive power operation band Bandwidth Setting in the DRCS defining the high and low points of the band set
American Electric Power Service Corporation Jan 26, What Determines SSD Switching? Dynamic reactive output (Q DRCS ) outside of operating band for a set time (typically minutes) Q DRCS Increment set
American Electric Power Service Corporation Jan 26, SSD Switching Pattern in McCamey area Three DRCSs at Crane, Rio Pecos and Friend Ranch operate locally to switch capacitors and reactors, compensating for reactive power consumption caused by intermittent power from wind
American Electric Power Service Corporation Jan 26, Implementation of Real Power Controllers Phase Shift Transformers Bandwidth control around a set point Series Capacitors Bypass controller based on target range of power flow