13th April 2005R.Bates, QM Measurements of Barrel and EC HEX R. Bates, M. Olcese, B. Gorski, QM for prototype builds.

Slides:



Advertisements
Similar presentations
1 Ann Van Lysebetten CO 2 cooling experience in the LHCb Vertex Locator Vertex 2007 Lake Placid 24/09/2007.
Advertisements

Basic Refrigeration Cycle
April 7, 2010D.R. Lynch 1 PHENIX Shutdown 2010 April 7,2010 Don Lynch.
Tennessee Technology Center Center at Pulaski. Superheat & Sub-cooling A Technician’s Guide to HVACR Diagnostics.
18th March Richard Hawkings Humidity control in the ATLAS ID Richard Hawkings (CERN) JCOV meeting 18/3/04  Overview of humidity and associated gas.
6/3/2015Auke-Pieter Colijn1 C3F8 NIKHEF Design Compare Does it work?
Product Introduction.
Evaporators For Air Conditioning
Cooling Update (May 2011) Tim. Overview From last time – Estimate Power Loads Active components Extraneous heat sources – Develop methodology for exploring.
CO2 cooling pressure drop measurements R. Bates, R. French, G. Viehhauser, S. McMahon.
CO 2 return pressure drop budget and pipes from PP2 to tracker Georg Viehhauser.
Cooling: CEDAR PMT & Electronics Tim Jones Liverpool Group.
1 CO 2 cooling of an endplate with Timepix readout Bart Verlaat, Nikhef LCTPC collaboration meeting DESY, 22 September
JE / RA 29/1/021 RAL Evaporative Cooling UK-V Meeting, RAL Wednesday 30th January Julia Easton Talk given by Richard Apsimon.
23 Jan 2007 LASA Cryogenics Global Group 1 ILC Cryomodule piping L. Tavian for the cryogenics global group.
Calorimeter Analysis Tasks, July 2014 Revision B January 22, 2015.
Evaporative Heater Design, qualification and planning M.Olcese PRR SCT off-detector cooling PRR SCT off-detector cooling March March 2005.
Update on UT cooling specifications and status of activities LHCb CO2 cooling meeting 8/7/2015 Simone Coelli For the Milano UT group INFN milano 1 Istituto.
Cryogenic update before Fermilab meeting (and after the helium tank review) Coordination meeting 6 th May 2015 K. Brodzinski HiLumi-LHC-CC-Cryo-PPT-18_v1.
Cooling R&D at RWTH Aachen Lutz Feld, Michael Wlochal (RWTH Aachen University) CEC Meeting, CERN Lutz Feld, Michael Wlochal (RWTH Aachen University)
LHCb VELO Meeting LHCb VELO Cooling System Bart Verlaat (NIKHEF) 25 February 2003.
CMS FPIX Cooling System Studies Joe Howell, Fermilab for the FPIX Upgrade Mechanical Working Group CMS Upgrade Workshop April 27,
CPPM Pixel Evaporative Cooling Plant Description & Operation with C 3 F 8 or C 4 F 10 G. Hallewell, CPPM, Feb 07, 2005.
Full Scale Thermosyphon Design Parameters and Technical Description Jose Botelho Direito EN/CV/DC 19 November, th Thermosyphon Workshop.
CLAUDIO BORTOLIN SPD Cooling Status INFN – PD / CERN.
LHC CMS Detector Upgrade Project FPIX Cooling Update Stefan Grünendahl, Fermilab For the FPIX Mechanical Group, 29 January 2015 Stefan Grünendahl,
Cooling plant upgrade Jose Botelho Direito, Michele Battistin, Stephane Berry, Sebastien Roussee 2 nd SPD Cooling Workshop 30/11/201112nd SPD.
SEPTEMBER 2002 Pixel Support Tube A. Smith LBNL 1 ATLAS Pixel Detector Heater Panel Testing Alexis Smith September 17, 2002.
1 Monophase Measurements on Prototype Pixel Structures D. Bintinger, M. Gilchriese, J. Taylor and J. Wirth and contributions from D. Cragg, E. Perrin and.
Cooling System Solutions
Phase 1 FPix Cooling Tube Testing Erik Voirin, C.M. Lei, Harry Cheung, Stefan Gruenendahl (FNAL) Kirk Arndt, Qiuguang Liu (Purdue) Phase 1 FPIX cooling.
Status of the ATLAS ID Evaporative cooling system JCOV 25 Nov P. Bonneau TS/CV/Detector Cooling CONTENTS Overall statusOverall status Cooling plant.
Iτiτi AiAi 1(1.2±0.2)×10 6 min0.42±0.11 2(4.1±0.6)×10 4 min0.10±0.01 3(3.7±0.3)×10 3 min0.23± ±25 min0.21± ±5 min0.04±0.03 Donor removal.
EUROPEAN ORGANIZATION FOR NUCLEAR RESEARCH Design of the thermosiphon Test Facilities Thermosiphon Cooling Review A. MORAUX PH Dpt / DT Group CERN SEPTEMBER.
Krzysztof Śliwa 26 August, Krzysztof Śliwa 26 August, 2015  Tests done between 7th to 25th of August 2015  Circulation in by-pass over the manifold.
Aachen Status Report: CO 2 Cooling for the CMS Tracker at SLHC Lutz Feld, Waclaw Karpinski, Jennifer Merz and Michael Wlochal RWTH Aachen University, 1.
Status of the Marco chiller and Marco capacity analyses Bart Verlaat, Lukas Zwalinski, Maciej Osterga, Jan Godlewski MPI Munich,1 March.
GTK GAS COOLING SYSTEM Marco Statera, Vittore Carassiti, Ferruccio Petrucci, Luca Landi, Stefano Chiozzi, Manuel Bolognesi NA62 - GTK working group meeting.
© 2012 MITSUBISHI HEAVY INDUSTRIES – MAHAJAK AIR CONDITIONERS CO., LTD. All Rights Reserved. 5 August 2014.
7 February 2012 Annekathrin Frankenberger (HEPHY Vienna) Open CO 2 Cooling System at the beam test Belle II SVD-PXD Meeting.
MVD COOLING STATUS-PAST AND UPDATES PIXEL COOLING PROJECT: -STUDIES and TEST on MATERIALS (Carbon Foam) -THERMAL FEM ANALYSES and TEST on DISKS and STAVES.
Stave thermal analysis Cooling connections CO2 warm Test
MVD COOLING STATUS MVD COOLING PROJECT: CHOICE of COOLING FLUID,
Fixed Orifice Tube Cycling Clutch System (FOTCC)
2016/12/6 Yasuhiro R&D status of a gas-compressor based 2-phase CO2 cooling system for FPCCD vertex detector 2016/12/6 Yasuhiro Sugimoto.
Feedback on transfer line sizing and flow calculations for UT
Fixed Orifice Tube Cycling Clutch System (FOTCC)
Design of the thermosiphon Test Facilities 2nd Thermosiphon Workshop
ARAC/H/F Air-cooled water chillers, free-cooling chillers and heat pumps Range: kW.
Performance of a CO2 System with Four Parallel Pipes
FPix Cooling Circuit. FPix Cooling Circuit FPix Shared HD - Nominal Flow ΔPtotal = 5bar Δm = 0.5g/s mnominal = 2.6g/s ΔPtotal = 10bar Δm = 0.2g/s mnominal.
Forum on Tracking Detector Mechanics - Bonn, May 2016
Pixel cooling specifications
Tracker cooling loop “check out” draft for discussion
Aachen Status Report: CO2 Cooling for the CMS Tracker
Aachen Status Report: CO2 Cooling for the CMS Tracker at SLHC
Studies in zeotropic C2F6/C3F8 blends for reduced temperature cooling of the ATLAS SCT and pixel detectors + HTC measurements in these blends G. Hallewell.
Ultra-light carbon fiber structures: evaporative tests
Detector Technology Group
Process Equipment Design and Heuristics – Heat Exchangers
Recirculating CO2 System
VELO Thermal Control System
Aachen Status Report: CO2 Cooling for the CMS Tracker
Refrigeration and Air conditioning
By: JAGDEEP SANGWAN Refrigeration Basics 101.
Refrigeration and Air Conditioning
Refrigeration and Air Conditioning
Tests of Endcap capillary & Heat exchangers at CERN
Cryogenics – The Basics
Presentation transcript:

13th April 2005R.Bates, QM Measurements of Barrel and EC HEX R. Bates, M. Olcese, B. Gorski, QM for prototype builds

13th April 2005R.Bates, QM Contents Details of the evaporative cooling system Measurements made:  Barrel HEX  EC HEX CERN Prototype QM-1 HEX  Pressure drops over pipe work

13th April 2005 The evaporative system in 175 General design of system close to final design

13th April 2005R.Bates, QM Details of off-detector section

13th April 2005R.Bates, QM Detail of circuit tested Volume and Danfoss meters for massflow measurements Heat liquid after Danfoss to reach 35°C before HEX inlet  Manual heater control PLC controlled proto- heater ELMBs with PVSS monitoring plus some manometer duplication Keller high pressure transducer before capillary

13th April 2005R.Bates, QM Enthalpy Diagram Sub-cooling Boiling in the cooling circuit Final Heater Compression Condensation Pumping Subcooling increases efficiency, i.e. less flow required Expansion in the capillary Psat= exp(T)

13th April 2005R.Bates, QM Why sub-cooling Cooling power = massflow x Enthalpy Max Enthalpy at -25 °C = 102 J/g No sub-cooling, liquid temp = 35°C  Power = massflow x 36 J/g : Endcap  9.6g/s, Barrel  14g/s No sub-cooling, liquid temp = 20 °C  Power = massflow x 53.7 J/g : Endcap  6.5g/s, Barrel  9.5g/s Sub-cooling to -10 °C  Power = massflow x 86.1 J/g  Massflow reduction up to 2.4 times!  Slightly lower as require Xu = 0.9 to cool inlet liquid in HEX Endcap (35°C) = 5.7g/s, Barrel  7.8g/s Reduce the change in massflow as a function of TlbHEX  No sub-cooling  50% increase in massflow  Sub-cooling  <10% increase (small change in TlbCAP)

13th April 2005R.Bates, QM Pressure specifications Design pressure during normal operation at full power in the evaporative circuit (bara) Outlet of liquid pump Outlet of PR Inlet capillary Outlet capillary Detector structures Inlet of BPR Inlet to the compressor Pressure Max system pressure Driven by 40 °C max inlet T specification Driven by -25 °C design T of on detector loop 350mbar pressure drop budget of on vapour side 1bar pressure regulation

13th April 2005R.Bates, QM HEX & massflow HEX efficiency (and Massflow) must be sufficient to cool system with full power Must cope with  TlbHEX = 20°C to 35°C  Sudden power changes in detector structures Limited increase in Massflow as a function of  TlbHEX  Detector power Vapour pressure drops to be as small as possible (  50mbar)

13th April 2005R.Bates, QM Heat Exchangers Design is different for the three sub-detectors due to different layout and geometrical constraints All countercurrent type Pixel: parallel type external. Al inlet and return tubes glued together over 1.5m. Simple design, possible with small power load EC SCT: inlet tube is coiled in spiral inside the return tube over less than 0.4m. Barrel SCT: parallel type internal. Two inlet tubes are routed inside the return tube over a length of 1.5m and parallel to the return tube axis

13th April 2005R.Bates, QM SCT EC heat exchangers Several prototypes made Final design qualified Pressure drop budget is met QMUL is making a final prototype with final tubes

13th April 2005R.Bates, QM Endcap HEX - designs 1 st failed due to boiling inside capillary HEX1 – HEX3 failed due to low efficiency HEX nameDesign typeInternal pipeVapour return Length (mm) ID (mm) OD (mm) Length (mm) ID (mm) Free ID (mm) HEXCapillary inside HEX HEX1CuNi pipe inside HEX HEX2CuNi pipe inside HEX HEX3Cu pipe inside HEX HEX4Cu pipe inside HEX QM-1Cu pipe inside HEX

13th April 2005R.Bates, QM Results with CERN HEX4 Minimum massflow to remove nominal detector power of 346.5W found for HEX = 5.7g/s Inlet liquid temperature of 35°C maintained through out Massflow measured by volume meter Massflow measurement checked with energy balance  Know inlet liquid and outlet vapour pressure/temperature  Know power into the system  Can calculate massflow

Minimum massflow Baseline massflow = 5.7g/s for TlbHEX = 35°C, 100% power

13th April 2005R.Bates, QM Results summary– CERN HEX4 TlbHEX=35C 100% power TlbHEX=20C 0% power Massflow (g/s) TlaHEX Hex eff Xi Xu Massflow Increase = 0.7%

13th April 2005R.Bates, QM Stability checks Tests were performed to confirm that the system is stable  Ran for more than 2 hours without interference  Rapidly (less than 1 minute) increase detector power from 0 to 100%  Repeated measurements to confirm observations

13th April 2005R.Bates, QM 0 to 100% power min massflow

Different HEX orientations All with TlbHEX = 35°C, 100% power V  min massflow (g/s)  PlbCAP (bara)  TlaHEX (°C)  Efficiency (%)  Xi  Xu deg V L V +45deg L

13th April 2005R.Bates, QM Only 2 capillaries open Tested as some disks only have two circuits  Only 2 EC HEXs has 2 capillaries (disk 1) Tested in +45deg as worse case Efficiency of HEX reduced  Does not work for nominal massflow - now 3.98g/s  Minimum stable massflow = 4.4g/s Same flow if use 2 x large capillaries Could use 1large and 1small cap & increase pressure to test  TlaHEX = -20C, HEX eff = 0.92  DP HEX V = 35mbar, DP on cylinder = 46mbar Change in massflow 100%(T=35°C) to 0%(T=20°C)  0.7% increase

13th April 2005R.Bates, QM QM-1 Inlet liquid pipe length reduced by 8% to 2764mm 100% power TlbHEX=35C CERN HEX, 0deg +45deg-45deg 0%, TlbHEX=20C Massflow (+3%) PlbCAPn/a TlaHEX Hex eff Xi Xu Stable at 98% power and massflow of 5.84g/s (2.5% above baseline 5.7g/s) Max massflow 8% above baseline massflow: (+45deg, 0%(T=20) = 6.06g/s)

13th April 2005R.Bates, QM Barrel HEX Contra-flow Two liquid inlet pipes Length  1.5m Vapour in 45 HEX out of page x z -45deg geometry

13th April 2005R.Bates, QM Results Nominal massflow of 7.8g/s shown to remove nominal detector power of 504 W Inlet liquid temperature of 35°C maintained through out Stability checks performed System measured for both ± 45deg Tested with cooling loop & barrel 6 manifold HEX vapour ΔP too high – but manageable

13th April 2005R.Bates, QM Results 100% power (504W) TlbHEX = 35C +45deg geometry-45deg geometry Massflow (g/s)7.8 TlaHEX ( o C) HEX Efficiency Xi0.34 Xu0.98  P vapour (mbar)  P liquid (mbar) Pressure after Cap

13th April 2005R.Bates, QM Changes in massflow for changes in TlbHEX and power Power (%) TlbHEX ( o C) Massflow (g/s) % change in massflow  P vapour (mbar)  P liquid (mbar) TlaHEX ( o C) HEX eff N/A * * Funny seen in the system. The operating conditions for a power cycle 100% to 0% power (TlbHEX = 35°C) resulted in a lower efficiency for the HEX and therefore lower massflows when compared to starting the system up. From start up the massflow for TlbHEX=35°C was 8.8 g/s. Not observed for -45deg geometry. +45deg

13th April 2005R.Bates, QM Efficiency increases with lower TlbHEX XiXu 20C C

13th April 2005R.Bates, QM Highest efficiency up to 75% power – 378W TlbHEX=35C 75% power Massflow = 8.6g/s

13th April 2005R.Bates, QM Stability 0 – 100% power TlaHEX = 9.5C TlbHEX = 35C TvbHEX = -25C TvaHEX = 14C

13th April 2005R.Bates, QM 2hour run

13th April 2005R.Bates, QM System only slightly affected at 75% power Vq=0.75 Vq=0.98

13th April 2005R.Bates, QM Barrel HEX with cooling loop

13th April 2005R.Bates, QM Barrel HEX with cooling loop

13th April 2005R.Bates, QM Barrel HEX/Cooling loop test Tested HEX with real cooling loop  HEX performance the same with cooling loop as with dummy load  Cools first and final module  Pressure drop over cooling loop considerable – results in evaporation temperature changes  ΔP less for lower detector power and lower inlet liquid temperature

13th April 2005R.Bates, QM Cooling loop Press & Temps Coolant Temperature, ( o C) Calculated saturation pressure, bara Measured pressure, bara Start of loop End of loop Start of loop End of loop In exhaust pipe few cm after manifold

13th April 2005R.Bates, QM  P in loop & manifold 100% power  Pman = 280mbar  Ploop = 540mbar  Ptotal = 820mbar

13th April 2005R.Bates, QM Smooth increase in  P as function of outlet vapour quality

13th April 2005R.Bates, QM  P for TlbHEX = 20ºC For m=7.8g/s Vapour quality reduced Pressure drop reduced  Still very high Tevap reduced   T < 3ºC NOTE  If reduce massflow then VQ increase,  P and Tevap rise TlbHEX 35C20C VQ inlet VQ outlet  P TOTAL (mbar)  P loop  P manifold T start of loop T end of loop  T (ºC)

13th April 2005R.Bates, QM Summary of HEX performances Need more liquid at the outlet (higher efficiency) for stability Min flow cooling 100% of power with stable load transients 0%-100%-0% 50% more capacity

13th April 2005R.Bates, QM Pressure drop measurements Pressure drops measured for:  Inlet pipe work ID = 4 mm, Length = 10.8 m  Outlet pipe work ID = 8 mm, Length = 6 m  Final design of Endcap On-cylinder pipe work  Prototype EC and Barrel Heaters  HEX of each design: Liquid inlet & Vapour return  Barrel cooling loop  Barrel HEX to manifold pipe work Final pipe work sizes predicted for  heater exhaust to PPF1/PPF2  PPF2 to PPF3 (PR on racks)

EC Pressure drops - summary FromToLength (mm)ID (mm)Pressure drop (mbar) Inlet PP3PP PP2PPF PPF1Inlet of HEX HEX (1200) Total inlet side (1325.2) Exhaust PPF0Inlet of HEX24636&890 (130) HEX Outlet of HEXInlet of Heater Heater Heater exhaustPPF PPF1PP PP2PP Total return side314.5 (354.5)

Barrel Pressure drops - summary FromToLength (mm)ID (mm)Pressure drop (mbar) Inlet PP3PP PP2PPF PPF1Inlet of HEX HEX Total inlet side623.5 Exhaust Stave ExhaustInlet of HEX HEX170013/ Outlet of HEXInlet of Heater Heater Heater exhaustPP PP2PP Total return side353.4

13th April 2005R.Bates, QM Extra slides

13th April 2005R.Bates, QM Photos The main cooling rig BPR

13th April 2005R.Bates, QM Condenser, volume meter, PLC

13th April 2005R.Bates, QM Power supplies for cooling loop heaters

13th April 2005R.Bates, QM Barrel cooling loop pictures Final cooling loop Barrel 6 manifold Barrel 3 pipe run manifold to HEX 36 ceramic heaters

13th April 2005R.Bates, QM Pictures Capillary into loop Pressure measurements just after capillary Press sense 5cm after manifold on exhaust Temperature sensors on pipe and on heaters Insulations around temp sensors

13th April 2005R.Bates, QM Barrel HEX & cooling loop HEX at -45deg Loop horizontal

13th April 2005R.Bates, QM EC QM HEX prototype First QM EC HEX at CERN

13th April 2005R.Bates, QM Pressure specifications High input P : MinP inlet > P sat (T=40°C) = 12.8bara  MinP inlet = 13bara  P sat (T=35°C) = 11.3bara  MinP inlet = 11.5bara Low evaporating pressure : P(T=-25°C) = 1.67bara Pressure drops  Liquid side Capillary to PR = 1bara PR to cooling rack = 1bara PR range (for flow regulation) = 1bara Pressure from liquid pump = 16bara  Vapour side P min at inlet of BPR = 1.3bara Pressure drop from detector structures to BPR = 350mbara Pressure drop includes drop along Heater, (budget = 50mbar), HEX, on- cylinder pipe work, and rest of pipe work to BPR. Higher massflow implies higher pressure drops in system  BIGGER pipes, bigger Heater etc  And more powerful Heater

13th April 2005R.Bates, QM Number of circuits and capacity Table 1: basic parameters and cooling capacity of the SCT evaporative circuits Numbers of capillaries per circuit Number of circuits Nominal power load Subtotal nominal power load [W][kW] SCT Barrel SCT EC (3 sectors disk) SCT EC (2 sectors disk) TOTAL

13th April 2005R.Bates, QM Barrel +45deg, change in operating conditions of HEX as TlbHEX and power changes