BEYOND THE GREEN WIRE
Is grounding science, art or black magic? Science – having the data and knowledge to competently design a system Art – always possible to manipulate a design for a more elegant solution based on factors such as budget or the environment Black magic – the perception created with gaps in knowledge / understanding
We must choose a perspective BYNUMS 5 LAWS OF ENGINEERS An engineer is empirically oriented An engineer is data driven An engineer in one way or another sells his/her time and expertise Liability concerns Due diligence issues
Grounding, bonding, surge, lightning Cannot be treated discretely Each is an element of a coherent whole All may not be necessary but none can be manipulated separately
Why grounding / earthing? References a structure to the environment – potentials rise and fall together Set points for circuit breakers Fuse selection Defines and identifies ground reference for ground fault and arc flash relays Coordination of the system
Where to start? Whether in design, forensics or rehab take a line from medical ethics First do no harm
Using the first two points of Bynums Law Engineers are compelled by training and discipline to design TO something Anything else may be an educated guess, informed guess or lucky guess… but still a guess With grounding we design between what we want or need and what the environment allows
Point #2 of Bynums Law When the required data is not available the tendency becomes using a formerly successful boilerplate design or to overdesign effectively becoming a guess
Standards IEEE Std. 80 (1986) IEEE Std (Green Book for Commercial / Industrial Facilities) IEEE Std (Emerald Book for Electronics)
The perfect world The engineer will have a certified start point in the form of results from a soil resistivity test Fairly reliable predictor of grounding electrode performance
Soil Resistivity Tests 4 Point Wenner Method Test developed in 1915 by Dr. Frank Wenner of NIST for U.S. Bureau of Land Management Most accurate test Used by civil engineers to locate water table but CE test protocol may be problematic for the electrical engineer
Soil Resistivity Tests Schlumberger Array developed by Conrad Schlumberger of France in the 2 nd decade of the 20 th century These are typically green field tests
Factors affecting resistivity Moisture Temperature (Sandy loam with a 15.2% moisture 32 deg. F [ice] has almost 3 times the resistivity of the same 32 deg. F [water]) Soil type – it has been reported the Metroplex has over 250 separately identifiable soil types
Factors affecting resistivity Depth – varies with soil type, moisture content and freeze line NOTE! There is a very real correspondence between resistivity and corrosion issues Electrolytes in the soil (active, pH issues) Pollution issues
Rules of thumb Most useful when talking about thumbs Designs generally specify 18 deep and outside of slab (drip line) At 18 the conductor merely connects the electrodes 30 and below (due to moisture content and freeze line) the conductor begins to act as an electrode in and of itself
Design Considerations Types of Grounding Systems Facility Layout Conductor & Electrode Materials Special Considerations
Types of Grounding Systems Solidly Grounded Low Resistance Grounding High Resistance Grounding Ungrounded
System Layout Grid Counterpoise Instrumentation – Dedicated System
Conductor Materials Copper or Tinned Copper Aluminum Braided Concentric Insulated Bare
Electrode Materials Galvanized Steel Copperclad Steel Zinc or Magnesium Solid Shapes Graphite Chemically Enhanced Ground Rod Ufer
Special Considerations Risk of Copper Theft Soil Reactivity Raw and Finished Products of Facility Depth of Conductors Cathodic Protection Systems Other Utilities
Acceptance & Maintenance Grounding is not an Install & Forget Acceptance Testing & Documentation Scheduled Testing & Maintenance
Why establishing a baseline is important.
We have a problem.
Summary Grounding is a fundamental Infrastructure system Yes, it can be expensive to get right. It is more expensive to correct problems after construction. It is most expensive when a ground system failure causes injury, equipment damage or loss of product.