Temperature Control Loop

Slides:



Advertisements
Similar presentations
Objectives Control Terminology Types of controllers –Differences Controls in the real world –Problems –Response time vs. stability.
Advertisements

Basic Refrigeration Cycle
STEAM TRAPS.
©2008 Armstrong International, Inc. Basic Steam Trap Operation.
Control Valves: Specifications, Sizing & Technologies
Chilled Water Piping Systems (VPF Focus)
Control System Instrumentation
Pneumatic Control Valves
COMMERCIAL REFRIGERATION
Process Control Instrumentation II
HVACR312 - Refrigeration Metering Devices.
Section 5: Commercial Refrigeration
Booster System Basics: Constant Speed Systems
Hydraulics.
Cheer up. It is not as difficult as you thought!
Control System Instrumentation
Lecture 3 Control valves.
© Belimo University 2011, All Rights Reserved
CHE 185 – PROCESS CONTROL AND DYNAMICS OPTIMIZATION AND PRIMARY LOOP ELEMENTS.
Refrigeration and Heat Pump Systems Refrigeration systems: To cool a refrigerated space or to maintain the temperature of a space below that of the surroundings.
Chemical Engineering 3P04 Process Control Tutorial # 2 Learning goals 1.The feedback cause-effect principle 2. Key element in the loop: The control valve.
Module 3 Eng. Asma Abu Baker. Introduction One of the most important uses of instruments or measuring devices is in the field of process control. If you.
Air Operated Valve Calibration NMV21
Sean Kalman – Hays Fluid Controls
CONTROL VALVE - THEORY & SIZING
STEAM HEATING.
Hydronic Mechanical Controls
Specifying and Sizing Control Valves A design equation used for sizing control valves relates valve lift to the actual flow rate q by means of the valve.
Static Pressure Control Loop The purpose of the static pressure control loop is to maintain an optimal static pressure in the ductwork. The control loop.
Valves In Industry (Part 3).
Water piping design.
Industrial Process Control: CONTROL OF HEAT EXCHANGER
HVAC523 Basic Subsystems.
Important variables Water: Air: Conversion:
Topic 7 Control Valves. What We Will Cover Topic 1 Introduction To Process Control Topic 2 Introduction To Process Dynamics Topic 3 Plant Testing And.
CHAPTER 9 Control System Instrumentation
CONTROL VALVES By M.Freethan M
PUMPS, VALVES, & FANS …Moving fluids Objectives Comprehend the basic construction and application of valves used Comprehend the basic construction and.
Control System Instrumentation
MECHANICAL ENGINEERING FOR SYSTEM BALANCE ASHRAE MEETING 2/15/2007 NORTHERN NEVADA CHAPTER 126 MATT BRENNAN, TBE.
VAV Box Control Loop The purpose of the VAV Box control loop is to adjust airflow through the box to maintain a space temperature. The difference between.
Valves In Industry (Part 3)
 Switches are commonly employed as input devices to indicate the presence or absence of a particular condition in a system or process that is being monitored.
Sizing Variable Flow Piping – An Opportunity for Reducing Energy
Control Theory Control System Objectives  Establish a final condition  Provide safe operation  Eliminate the human element  Assure economical operation.
HYDRAULICS & PNEUMATICS
Variable Speed Applied to Pumps. Life Cycle Costs - Courtesy of Hydraulic Institute and Europump Initial cost is not the only cost associated with a pump.
Objectives Finish DOAS Control Terminology Types of controllers
Introduction to Energy Management. Week/Lesson 11 Control Systems for Occupant Comfort.
Introduction to Energy Management. Week/Lesson 13 Control Strategies for Occupant Comfort.
Control Loops Tune a Fish. Control Loops Tuning of a control loop involves selecting loop parameters to ensure stable control under all operating conditions.
CHAPTER 9 Control System Instrumentation
ME444 ENGINEERING PIPING SYSTEM DESIGN CHAPTER 10 : CONTROL VALVES IN CLOSED LOOP SYSTEMS.
Session 6 - Agenda BREAK Activity Est. Time 1. Agenda
James McIntyre VRF Training Manager V5 Key Components.
Introduction to Final Control Elements
Actuator Edi Leksono Department of Engineering Physics
Author: Nurul Azyyati Sabri
EEN-E1040 Measurement and Control of Energy Systems Control II: Controlled devices, control in energy technology, complex systems Nov 7th 2016.
Sensors and Detectors - 1
Control System Instrumentation
Course PEF3006 Process Control Fall 2017 Actuators By Finn Haugen
Control System Instrumentation
Control System Instrumentation
Control System Instrumentation
By: JAGDEEP SANGWAN Refrigeration Basics 101.
UNIVERSITÁ DEGLI STUDI DI SALERNO
Hydraulic Flow Control • Metering Fluid Flow
Presentation transcript:

Temperature Control Loop The purpose of the temperature control loop is to maintain a constant off-coil temperature. The control loop senses the actual off-coil temperature and compares it to a setpoint. The controller sends an output signal to a valve actuator which adjusts the valve stem position which affects the waterflow through the valve and the coil which impacts the off-coil air temperature.

Temperature Control Loop Off-Coil Temperature DDC Control Calculations Signal to Valve Actuator Position of Valve Stem Water flow through valve / coil

Temperature Control Loop Cooling Coil Air Flow Off-coil Air Temperature Sensor Valve Actuator CHWS CHWR Setpoint and other Tuning Parameters DDC Controller

Temperature Control Loop Control Loop Setpoint

Temperature Control Loop Control Loop Setpoint Setpoint of control loop is fixed by building engineer. Choosing too high of a setpoint will result in: lower chiller energy higher fan energy reduced system capacity higher RH in space

Temperature Control Loop Control Loop Setpoint Too low a setpoint may cause the loop to saturate meaning no control. Common practice is to fix off-coil temperature setpoint between 10°C and 14°C.

Temperature Control Loop Chilled Water Valves

Temperature Control Loop Chilled Water Valves The chilled water valve should be mounted in the chilled water supply pipe. If the chilled water valve is in the return valve, then when the valve is closed the coil is full of cold water and condensation will result increasing maintenance problems.

Temperature Control Loop Normally Open Cage Trim Globe Valve Body Packing nut Packing guide Packings Bonnet (Centerpiece) Stem Disk (Integral w/Plug) Plug Cage (Integral Seat) Body

Temperature Control Loop Normally Open Flanged Globe Valve Body Stem Packing nut Packing guide Packings Packing box Centerpiece Disk holder Disk Plug Seat (screwed in) Plug guide Body

Temperature Control Loop Resilient Seat Butterfly Valve Body Stem Bushing, Stem Seal Stem Retaining Ring Valve System Neck Body Valve Seat Disc

Temperature Control Loop Valve Plug Design % Flow 100 Quick Opening 75 Linear 50 25 Equal Percentage 25 50 75 100 Quick Opening % Valve Stem Lift Linear Equal Percentage

Temperature Control Loop Use quick opening plug for two position applications. Linear plug is typically used for industrial applications. Equal percentage plug typically used for HVAC applications. Why?

Temperature Control Loop Valve Characteristic + Coil Characteristic = % Flow % Design Capacity 100 100 75 75 50 50 25 25 25 50 75 100 25 50 75 100 % Valve Stem Lift % Design Flowrate

Temperature Control Loop A roughly linear system characteristic 100 % Design Capacity % Valve Stem Lift 25 50 75

Temperature Control Loop All valves experience uncontrollable flow when almost closed. Uncontrollable flow

Temperature Control Loop Rangeability A high rangeability means good control under low load conditions. There are different standards to define “Minimum Controllable Flow”

Temperature Control Loop Cavitation As water goes through the restricted area between the plug and the seat, the velocity increases and static pressure decreases. If the static pressure drops below the vapour pressure, air bubbles form. After passing the restriction, velocity decreases and static pressure increases. As the static pressure rises, the bubbles implode causing shock waves which result in pitting on the inside of the valve.

Temperature Control Loop Cavitation Plug to Seat Clearance * * * Flow Implosions Velocity Liquid Vapour Pressure Pressure Pressure Velocity

Temperature Control Loop Valve Authority Cooling Coil Pv Pt

Temperature Control Loop Valve Sizing Undersized valves cannot deliver sufficient flow for maximum load conditions. Oversized valves must operate at the end of their stroke making tuning more difficult.

Temperature Control Loop Valve Sizing For 2 position valves, select the valve according to line size. For modulating valves, use the design pressure drop and flow rate to calculate the flow coefficient.

Temperature Control Loop Valve Sizing Flow Coefficient (Cv) is the USGPM of 60°F water that will flow through a fully open valve with a 1 psi drop across it.

Temperature Control Loop Valve Sizing Cv = Valve flow coefficient Q = Flow in USGPM Pv = Pressure difference between inlet and outlet in psi

Temperature Control Loop Valve Sizing Example Q = 90 USGPM Pv = 5 psi (typical) Cv = 90/2.24 = 40

Temperature Control Loop Valve Sizing Valves are only manufactured with specific flow coefficients. After calculating the desired flow coefficient, select the valve with the next lowest coefficient. Most systems are oversized so slightly undersizing the valve will not compromize system performance, but it does improve system controllability.

Temperature Control Loop Three Way Mixing Valve Body Normally Closed Common Normally Open

Temperature Control Loop Three Way Valves Pump Cooling Coil C S Three way valve in mixing application piped N.C. to coil N.C. N.O. R N.C. Cooling Coil R Three way valve in bypass application piped N.C. to coil C N.O. S

Temperature Control Loop Three Way Valves Three way valves are used for constant flow systems. Constant flow systems are not popular because they waste pump energy. Constant Flow to Building Variable Flow to Building

Temperature Control Loop Valve Actuator There are two critical issues when selecting the valve actuator: Close off pressure Spring return End switch

Temperature Control Loop Valve Actuator For a two way valve, the close off pressure must be sufficient to overcome the pump head. For a three way valve, the close off pressure is twice the pressure drop across the valve plus the pressure drop across the coil. If spring return in provided, the valve will return to a known position if the control signal is removed or during a power failure.

Temperature Control Loop Temperature Sensors

Temperature Control Loop Temperature Sensors An averaging temperature sensor is mounted in ductwork in front of cooling coil to measure off-coil temperature.

Temperature Control Loop Temperature Sensors Resistance Temperature Detectors (RTD) measure temperature using the resistance property of metals such as nickel or platinum. The resistance of a thin wire varies linearly over a limited temperature range. Low current is used to avoid self-heating.

Temperature Control Loop Temperature Sensors Different metals have different sensitivity to heat. Thermal sensitivity is measured in ohms/ohm/Deg C. For example, a sensor with a sensitivity of 0.003 ohms/ohm/Deg C and a base resistance of 22°C will change from 1003to 1006as the temperature varies from 23°C to 24°C.

Temperature Control Loop Temperature Sensors Two common metals used for RTD are Nickel and Platinum. Both type of sensors are available with a base resistance of 1000Platinum sensors are also available with a base resistance of 100 Base resistance is not as important as sensitivity and linearity.

Temperature Control Loop Temperature Sensors Nickel sensors have a high sensitivity (.00343 C). Nickel sensors have a slight non-linearity at extreme temperatures and software correction may be required under these conditions. Nickel sensors are low cost and can be used for point or averaging elements.

Temperature Control Loop Temperature Sensors Platinum sensors have a low sensitivity (.00214 C). Platinum sensors are very linear for the range of temperatures found in HVAC applications. Platinum sensors are higher cost and are not available as averaging elements.

Temperature Control Loop Temperature Sensors Point Element : Appropriate for Return Air Temperature or Room Temperature (well mixed air) Averaging Element : Used for Off-Coil Temperature or Supply Air Temperature (turbulent/stratified air)

Temperature Control Loop Temperature Sensors Calibrate a temperate sensor by: Disconnect RTD element. Replace RTD element with a precision 1000 resistor. Adjust offset in DDC Controller to read base temperature (this compensates for resistance of wiring). Replace RTD element.