Artificial Lighting Design Task lighting for general purpose rooms involves the installation of light sources that will provide the optimum amount of.

Slides:



Advertisements
Similar presentations
Sustainable Lighting Strategies
Advertisements

EGEE 102 – Energy Conservation And Environmental Protection Energy Efficient Lighting.
BASICS OF LAMP TECHNOLOGY Created by the U.S. Department of Energy Rebuild America Business Partners and Philips Lighting Company.
LAMPS (Chapter 3) Lamp efficacy, life, and color Incandescent
Lighting System Design
Kitchen & Bath Lighting. A good lighting design should: Look good – both people and design space Provide the proper amount of light in every room Be.
1 Lighting A quick overview The Physics The Practical.
Professor Mark A. Comeau, AIA © Interior Environment Week 9 Lighting: High efficiency Day-lighting Occupancy & daylight sensing, programmable operations.
2010 Energy OutWest Reno, Nevada 12-Mar-10 Baseload Electricity quantify, address, manage 2a) Lighting baseload: effective & efficient use to shape & affect.
Technology in Architecture Lecture 4 Lighting Design Example Lecture 4 Lighting Design Example.
16469 Low Energy Building Design Lighting Cameron Johnstone Department of Mechanical Engineering
Energy Efficiency 4/29/2015 Lighting Akrem Awad 1.
Management and Organisation of Electricity Use Energy Efficient Lighting Techniques Belgrade November 2003.
400 Watts Metal Halide (455 Watts with ballasts) Pendant mount 22’ from the floor Six 4’, T8 lamps per fixture: 224 Watts (with ballasts) Mounted on the.
The LOWEST COST LIGHTING SOLUTION Comparison Presentation.
Lighting. Artificial Light Units of Measurement Input Power – Watts Light Output – Lumens Efficacy* (of light source) – Lumens per watt Efficiency (of.
The Concept of Daylighting Lighting buildings prior to the late 1800s relied chiefly on daylight from windows. Lighting buildings prior to the late 1800s.
16469 Lighting and Daylighting Design. Energy Efficient Lighting Lighting accounts for a significant portion of energy use in commercial buildings We.
 General Lighting - provides an area with overall illumination. Also known as ambient lighting, general lighting radiates a comfortable level of brightness,
Lighting Calculations
Why BoldPlay? Brilliant Design. Intuitive Engineering Innovation + Design = Performance Serious Energy Savings Ideal direct/indirect distribution maximum.
1) This classroom has _______. A)Too much lighting B)Not enough lighting C)About the right amount of lighting.
K. F. Chan (Mr.)ELEC LUMEN METHOD Utilization factor -- Ratio of flux received by reference plane to total rated lamp flux in the installation. Utilization.
Light Quantity Lighting Metrics Luminous Flux Illuminance
Lighting Interior Design II. Natural Light Provided by the sun Makes color sharper and brighter Generates a feeling of well being.
HOUSING DECISIONS p How are these mounted? Which way do they direct light? Valance lighting Bracket lighting Recessed down lights Surface mounted.
Lighting calculations
Electrical Lighting & Cable Selection D.K.Pathirana.
Kitchen & Bath Lighting. A good lighting design should: Look good – both people and design space Provide the proper amount of light in every room Be.
Photometric Data Photometry is the science of measurement of light.
FLUORESCENT LUMINAIRES Fluorescent Luminaires U.S. Department of Energy Rebuild America Business Partners And Lithonia Lighting.
ENME808W Advanced Topics in Mechanical Engineering: Energy Efficiency/Energy Audit and Conservation Week Eleven Lecture I: Dr. Michael Ohadi Class: Mon.
Landscape for Deemed Lighting Workpapers Building Code and Voluntary Program Relationship Building Code Changes Driven by Big Vision Voluntary Program.
Lighting System A lighting system consists of : 1.Light sources 2.Luminaires (or fixtures) 3.Ballasts.
Facilities Management and Design
1 Lighting Learning outcome from this topic, the student is able to – recognize the definitions and meanings for terms used in lighting – calculate lighting.
Day 10 Environmental Systems I Daylight as a primary lighting source Artificial lighting as a secondary source Room 102 Architecture Building.
Chapter 18. Natural Light – Artificial Light – Incandescent Light – Fluorescent Light – Direct Lighting–
1 ISE Ch. 20: Vision and Illumination Performance on visual tasks depends on …  human vision  environment  task Human Vision acuity color vision.
Department of Technical Education
Lighting Systems: Electrical Sources Chapter 3 Part 2 © 2006 Fairchild Publications, Inc.
Chapter 8 Quantity of Lighting © 2006 Fairchild Publications, Inc.
Luminaire Types.
Phil Munsey, Facilities Energy Engineer Plant 17 Lighting Energy Reduction Project.
Objectives Learn about lighting design.
Lighting facts.  Lighting can be a big energy consumer in offices and production areas and experience shows that energy savings may be achieved - often.
LIGHTING SYSTEMS. Introduction  Electricity used to operate lighting systems represents a significant percentage of electricity consumed in most countries.
Lighting. TYPES OF LIGHTING Natural and Artificial.
Lighting systems in labs & offices1 Subject: By:a.Yousefvand.
JP Bedell SDA Lighting
LEVEL 4 ENERGY ASSESSOR TRAINING 8. Level 3 re-cap lighting and Power Factor Correction.
Illumination Devices Measurement Unit.
Combination Artificial & Daylighting
Lighting 4.05.
Module 5 Lighting Calculations
Lighting Design: Energy Efficient Lighting Design:
Incandescent Light Bulb LUMEN DESIGN METHOD Where: N = E A F UF LLF N = number of lamps E = level of illuminance A = Area at working plane.
ART 2640, Building Systems of Interior Environments Fall Semester 2016 Tuesdays & Thursdays 9:00-10:20 Grover Center E218 Matthew Ziff, Associate Professor.
LIGHT FIXTURES INTRODUCTION LIGHT DISTRIBUTION CONTROL OF BRIGHTNESS
METHODS OF ILLUMINANCE CALCULATION
OBJECTIVE 1.04: Select interior lighting fixtures.
ILLUMINATION.
Point-by-Point Factors
Definitions Luminance:The amount of light reflected from or transmitted through a material. Measured in candelas/ft (candelas/m ). Perceived as brightness.
Technology in Architecture
Objectives Learn about lighting design.
Announcement Filed trip is on Monday, May 6th from 8 to 9 AM
Announcement Next class: 15 minutes quiz
What Is Area ? Area is the amount of space inside a shape: Area Area
Objectives Finish Lighting system design Daylighting.
Presentation transcript:

Artificial Lighting Design Task lighting for general purpose rooms involves the installation of light sources that will provide the optimum amount of light, and distributed as evenly as possible in the work areas. General purpose such as classrooms that will be used for relatively short duration, that do not require a variety of quantity nor quality, differ from commercial work places that may require a serious consideration of the four aspects of quantity and quality.

Two important elements of lighting design include units of measurement: FOOTCANDLE LEVEL of light on a work plane – the designer must choose the amount of general illumination light desired for the particular task. Recommendations of light quantity in footcandles are given in the text and other publications that deal with lighting design. LUMEN OUTPUT from a lighting source. Lighting fixtures contain units of illumination. A standard 100 watt incandescent bulb produces 1700 lumens. A 48” 40 watt T12 fluorescent tube produces approximately 2800 lumens. Other output data is included in the text.

The Illumination Engineering Society has established standards for general purpose lighting for classrooms and offices. Several factors govern: –Size and shape of the room; room cavity ratio –Light reflectance values of floors, walls, & ceilings –Maintenance of the system (LLF) –Characteristics of the light source Lumen output Coefficient of Utilization –Control of artificial lighting devices –Desired lighting level in footcandles –Height of light source above work plane

The IES formula for determining the number of lighting fixtures required for certain conditions is: Number required = FC level x room area lumens x C.U. x L.L.F lumens x C.U. x L.L.Fwhere: FC = lighting level desired in footcandles FC = lighting level desired in footcandles room area is in square feet lumens is total amount per fixture C.U. = coefficient of utilization of fixture L.L.F. = light loss factor in maintenance

Procedure for using the formula 1 The designer first determines the level of light desired. 2Calculate the area of the room in square feet. 3Select a suitable lighting fixture, and determine the total amount of lumens the fixture will produce. 4Determine the light loss factor. A discussion of this process follows. 5From the manufacturer’s data for the lighting fixture selected, a coefficient of utilization will be determined. In order to do this, the reflectance values of the room ceiling and walls must be known. Floor reflectance is usually assumed at 20%. The room cavity ratio must then be determined, which involves the length and width of the room, and the height the lighting fixtures will be mounted above the work plane.

Room Cavity Ratio is determined by the formula: l = length of the room l = length of the room w = width of room w = width of room and 5 is a constant, RCR will be a number between 0 and 10, to be used in conjunction with the illumination data of the lighting source chosen. Where: h = height of light above work plane RCR = 5h x (l + w) / (l x w)

As an example problem, choose Room 102 in the Architecture Building The room is 32’ x 31’ Ceiling height = 12’ And h = 9.5 feet (desktops are 30” (desktops are 30” high) high) RCR = 5 x 9.5 x (32 +31) / (32 x 32) = (32 x 32) = 3.016

IES recommends from 58 to 78 footcandles of illumination for a school classroom. Choose then, a design level of 70 footcandles. Fluorescent lighting is desirable for this task since the lumen output and color of light is more acceptable for general illumination. An acceptable fluorescent lighting unit would be a “Williams” 440CW, which contains four tubes, each with a lumen output of 2800, for a total of 4 x 2800 = 11,200 lumens - per fixture. Each tube is 40 watts, for a total of 200 watts per fixture, including allowance for the ballast. 4 x 2800 = 11,200 lumens - per fixture. Each tube is 40 watts, for a total of 200 watts per fixture, including allowance for the ballast.

Two Points of Clarification in the formula: The text refers to calculating the “number of luminaires” with the formula. The meaning here is the number of units that produce light. But consider that a unit may have one or more light sources, such as a chandelier with many light bulbs, or a fluorescent fixture that may have from 2 to 6 light tubes. Replace the word “luminaire” with “light fixture”, which would contain the number of light sources for which it is designed, and the number of lumens equals the lumen output “per light source” times the number of light sources. Consider also that you require either candlepower or lux as the quantity of light desired. If lux is what you calculate, the room area must be in square meters. If you calculate for candlepower, the room area is in square feet.

Reflectance Values of the Room Since Room 102 has windows, we will for the time being ignore the free daylight and assume the calculation will be suitable for night time classroom use. The reflectance values for the room are: –Ceiling= 80 % –Floor= 20 % –Walls= 50%

Calculate the room cavity ratio for the room: RCR = 5h x ( l + w / l x w ) = 5 x 9.5 ( / 31x32) = 47.5 ( 63 / 992 ) = 47.5 x.0635 = 3.016

Determine the Coefficient of Utilization (CU), using the fixture manufacturer’s data:

From the CU chart: In the column for ceiling reflectance, choose 80. Then under the wall reflectance of 50, read the column of numbers directly below. Find the number nearest the RCR calculated (3.016), and see the Coefficient of Utilization Value of 0.62 At this point, from the IES formula, we have: FC = 70 Room Area = 32x31= 992 Lumens per fixture = 11,200 C.U. = 0.62

Next, find the Light Loss Factor, which is a measure of the level of maintenance you will assume will be done. Light loss factor is a percentage number, or how efficient each item will be, using a scale of zero to one, where one is perfect, and zero is no maintenance at all. All the numbers are allowances you will make, based on expected performance. Refer to the chart:

The Light loss factor is then, 1 x 1 x 1 x.9 x 1 x.9 x.9 x.9 =.6561 In other words, the allowance for cleaning the room and fixtures, and changing burnouts, is only 65% efficient.

To complete the calculation, insert all the numbers into the formula, and Number of fixtures required = (70 x 992) / (11,200 x.62 x.6561) (70 x 992) / (11,200 x.62 x.6561) = fixtures = say sixteen = fixtures = say sixteen Then arrangement of the fixtures in a symmetrical manner to distribute light evenly must be considered. One could consider 4 rows of 4 fixtures each, which certainly would be an even distribution in a nearly square room. Total watts for the fixtures = 16 x 200 = 3200 watts

Consider an Incandescent Source

Now consider a comparison of a different type of light source: Say use incandescent down-lights in a recessed housing flush with the ceiling. A “Lightolier” RC150 fixture would contain one recessed flood light, of 150 watts and 3500 lumen output. Assume that LLF is the same as before, and compare the two types. Consider the chart for the Coefficient of Utilization:

In the column of numbers for 80% ceiling and 50% walls, note the C.U. number closest to the RCR of 3.16 =.78

Now insert the new figures into the formula and find: Number of fixtures required = ( 70 x 992 ) / ( 3500 x.78 x.6561) = ( 70 x 992 ) / ( 3500 x.78 x.6561) = fixtures = say 36, or arranged in a square room 6 rows of 6 lights each. or arranged in a square room 6 rows of 6 lights each.

Consider a High Intensity Discharge Source

Now consider a high intensity discharge lamp such as a Metal Halide that could be used inside. Considering a comparison with the incandescent, with a C.U. of.78 and a LLF of.6516: The smallest Metal Halide is 175 watts with a lumen output of 14,000. Plugged into the formula, the number of light units would be ( 70 x 992 ) / ( 14,000 x.78 x.6516 ) = 9.76 fixtures For comparison say 5 fixtures in two rows. 10 fixtures x 200 watts (including ballast) = 2,000 watts

All fixtures give approximately the same amount of light, but consider a comparison of power use: Fluorescent: 16 x 200 = 3,200 watts Incandescent: 36 x 150 = 5,400 watts Metal Halide: 10 x 200 = 2,000 watts Metal halide units would be by far the most efficient solution in terms of power, but an even distribution of light in the room would probably suffer, unless an acceptable arrangement and diffusion system could be utilized. H.I.D lamps cannot be operated with dimmers.

PRACTICE PROBLEM

A room is 40’ x 34’ with a ceiling height of 10 feet. The work plane is 30” above the floor. The ceiling and wall reflectance are 80 and 30 percent. The light loss factor is Total lumens per fluorescent fixture = 11,200. Desired illumination at the work plane is 75 footcandles. Find: Room area: Room cavity ratio: The coefficient of utilization: Number of fixtures required for 75 footcandles

Room area = 40 x 34 = 1360 s.f. Room cavity ratio: 5h= 5x 7.5 = 37.5; l+w = 74; RCR = 37.5 x 74 / 1360 = 2.04 The coefficient of utilization: from chart, 80, 30 % = 0.65 Number of fixtures required for 75 footcandles = (75 x 1360) / (11,200 x.65 x.62) = 102,000 / 4,513.6 = = 23, and for distribution, probably equals 24 fixtures.