Selective Coordination of Overcurrent Protective Devices

Slides:



Advertisements
Similar presentations
Control Circuit Protection Supplementary Protectors vs
Advertisements

Presented for the IEEE Industry Applications Society Atlanta Chapter
Earthing systems, Harmonics Currents and GFP
Earthing systems, Harmonics Currents and GFP
Fuses vs Circuit Breakers for Low Voltage Applications
MOLDED CASE CIRCUIT BREAKER BASICS
© ABB Ltd - ATLV /26/2015 Insert image here Fuses vs Fuseless Technology.
2014 NEC Code Changes Ted “Smitty” Smith E Light Electric.
GENERATOR PROTECTION.
RT3b – André Smit, Siemens USA
REVIEW OF CODE BREAKFAST QUESTIONS Brought to you by fellow members who attended the Section Meeting.
Mark W. Earley, P.E. Chief Electrical Engineer.  Also known as the NEC ® or ANSI/NFPA 70  There are two electrical codes that govern electrical installation.
Power System Protection
Overcurrent Protection: Fuses and Circuit Breakers
Electrical Power Systems
©2008 The McGraw-Hill Companies, Inc. All rights reserved. Electronics Principles & Applications Seventh Edition Arc Fault Circuit Interrupters Charles.
Breaker Basics Welcome to this general overview of ABB.
© 2011 Ericson Manufacturing, Willoughby, Ohio
Codes and Standards / Power Systems Engineering Selective Coordination for Emergency and Legally-Required Standby Power Distribution Systems Presented.
Chapter 7 SYSTEM PROTECTION
Electrical Safety INSTRUCTOR’S NOTES:
Sistemas Eléctricos Industriales
Electrical Safety INSTRUCTOR’S NOTES:
Electrical Installation 2
Selective Coordination
Arc Fault Circuit Interrupters. Residential fires caused by electricity occur more than 40,000 times each year in the U.S. alone. 40% are due to arcing.
Grounding, bonding, and ground fault currents
Electrical Distribution Training
Objectives Review conductor and conduit selection Learn about protection systems (basic rules) Learn to design Residential Electrical Systems.
November 4, 2013 Topic: Electric Circuit Objectives:
Advanced Coordination Topics – EasyPower w/ Power Protector
Concepts of Engineering and Technology Basic Electricity and Electronics: DC Circuits Copyright © Texas Education Agency, All rights reserved. 1.
Unit 13 Electric Circuits
Utilities & Engineering Department16 Blossom St., Boston Introduction to the Hospital Emergency Power Supply System (EPSS) Jason D'Antona,
Presentation Topic: Circuit Breakers Represented to: Dr. M. Riaz Khan Represented by: M. Mujahid.
Challenges in Applying Higher Voltage Power Distribution in the Data Center Richard Draper, P.E. Data Center Power Distribution Product Manager Thomas.
Section 7.3 Electrical Energy Circuits are pathways for electricity to flow. – Unlike static electricity, which is short-lived and fast, current flowing.
Switches and Over Current Protective Devices Class Instructor ALPHER E. DE VERA, uap.
  The traditional molded-case circuit breaker uses electromechanical (thermal magnetic) trip units that may be fixed or interchangeable.  An MCCB provides.
 The figure below shows a protection system for a transmission line, consisting of a CT, PT, a relay and its associated circuit breaker.
Codes and Standards / Power Systems Engineering Selective Coordination for Emergency and Legally-Required Standby Power Distribution Systems Presented.
Automatic Transfer Switches
Electrical Engineering for Physicists How to get from the 208 VAC 3-phase power in the building to 110- and 220-VAC Code issues All work must be done in.
2011+ NEC Article Arc Energy Reduction. Where the highest continuous current trip setting for which the actual overcurrent device installed.
Mersen’s Fused Coordination Panelboard
Principles & Applications Residential Wiring Concepts
Selective Coordination
ELECTRICAL INSTALLATION AND MAINTENANCE (EIM) 5 INSTALL ELECTRICAL PROTECTIVE DEVICES FOR DISTRIBUTION, POWER, LIGHTING, AUXILIARY, LIGHTNING PROTECTION.
Chapter 7 System Protection
AFCI Protection: AFCI Receptacles and the NEC
Calculations: Transformers and Service Conductor Calculations
Presented to: IEEE-IAS (Atlanta) Presented by: Michael D. Seal, P.E.
Overcurrent Protection— Fuses and Circuit Breakers
Objectives Learn about Electricity Pricing Electric systems.
Objectives Review conductor and conduit selection
UL1077 UL508 UL489 They all look alike? What’s the difference?
Fuses vs Circuit Breakers for Low Voltage Applications
Presentation transcript:

Selective Coordination of Overcurrent Protective Devices “A Change is Gonna Come” Special thanks to NFPA 70 – excerpts from NEC 2014.

What Happened in the NEC 2014? Big Changes, Big Headaches!

NEC 2014 - Article 100 – Definition

What You See, Is What You Get… Article 100 implies full range = 0 What You See, Is What You Get… Article 100 implies full range = 0.01 sec

Change How You Think About Designing… Elevator Circuits Emergency Systems Health Care Facilities Legally Required Systems Critical Operation Data Centers Critical Operation Systems

You Will Have to Change How You Think About… Elevator Circuits - 620.22 Health Care Facilities – 517.26 Emergency Systems – 700.28 Legally Required Systems – 701.28 Critical Operation Data Centers – 645.27 Critical Operation Systems – 708.28

Elevators

Typical Health-Care Facility Electrical System (Informational Note Figure 517.30) Change Must meet Article 700 per 2014 edition Changed to “branch” in 2014 edition Deleted in 2014 edition Must meet Article 700 per 2005-2011 editions

Emergency Systems

Emergency Systems

Legally Required Systems

Critical Operations Power System (COPS)

Critical Operations Power System (COPS)

What Does These NEC Code Articles Have in Common? Theses articles all state, “selective coordination shall be selected by a licensed professional engineer”. You have the power!

Data Centers

How Often Does This Happen? 3 - breakers in series No overlapping of TCC’s. 60F day in August in Atlanta

If It Was Easy Anyone Could Do it…

Circuit Breaker Challenges Higher fault currents makes it more difficult to selectively coordinate breakers down to 0.01 seconds. Most breakers have instantaneous trips Only UL 1066 LVPCB’s come w/o instantaneous trip, i.e. turn off the “I” function in LSI trip. UL 1066 are larger frame sized breakers with solid state trips (800A -6000A). Larger breakers = larger electrical apparatus = less revenue producing space. Not all mfr’s trip units function the same. How do you level the mfr’s technical differences. Molded case switches have lower instantaneous levels & lower interrupting ratings.

Fusible Equipment Challenges Typically larger than circuit breaker equipment. Larger electrical rooms = less revenue producing space Fusible panelboards & Elevator Modules with CLF’s are more expensive than comparable breaker equipment. Stocking and maintenance concerns with fuses. GFP is difficult on standard switches. GFCI – forget about it! Easier to coordinate when using fuses ratio tables.

Current Limiting Fuses Circuit Breakers have tables, too! Current Limiting Fuses Easier to selectively coordinate. Selective Ratio Charts 2:1 ratio of upstream to downstream fuse

Avoid Mixing Fuses & Breakers Avoid using upstream fuses and downstream circuit breakers. Why? The fault current must be less than the current limiting threshold of the fuse. The CL threshold is below the .01 time band on the fuse curve.

Where is the Current Limiting Threshold Point?

Thermal Magnetic Circuit Breaker Thermal (overload) element is fixed. It cannot be adjusted. Instantaneous can either fixed or adjustable. 20/1 CB –“Q” frames are fixed. 150A frame – some adjustability with most mfrs. So, it’s really all about the Instantaneous trip. Do they overlap at 0.01 seconds?

Solid State or Microprocessor Trip Units Trip Unit Adjustments TCC Adjustability

Methods to eliminate the overlapping effect of the instantaneous trip units Reduce the available fault current Set the instantaneous trip above the actual fault current Select a breaker will an instantaneous over ride higher than the fault current.

Thermal Mag Breakers CAN Be Selectively Coordinated If you can reduce the fault current level below the instantaneous level of the downstream breaker, then selective coordination is possible. Add transformer Add impedance Use the 3:1 ratio rule

3:1 Ratio Rule for Breakers The frame size of the up stream breaker should be 3X as large as the downstream breaker. Don’t confuse trip with frame size. A 20A breaker is typically a 60A frame. Example: 40/3 breaker should be fed from a 250A frame breaker. Check with the breaker manufacturer – tighter ratios are possible.

Solid State Trip Unit 100,000 A rms sym fault current Instantaneous curve ends at the max fault current point

Solid State Trip Unit 60,000 A rms sym fault current Instantaneous curve ends at the max fault current point

Solid State Trip Unit 30,000 A rms sym fault current Instantaneous curve ends at the max fault current point

Solid State Trip Unit 25,000 A rms sym fault current Instantaneous curve ends at the max fault current point. What happened? 25kA was less than the instantaneous trip rating of the upstream breaker. Electro-magic!

Solid State Trip Unit 15,000 A rms sym fault current Instantaneous curve ends at the max fault current point

Solid State Trip Unit 10,000 A rms sym fault current Instantaneous curve ends at the max fault current point Now, you can slide those 20/1 breakers in and underneath the curves of the two upstream breakers That’s what I’m talkin’ ‘bout, Willis!

Solid State Trip Unit Adjust the upstream breaker’s instantaneous trip unit above the available fault current. Fault current = 41,638 Instantaneous trip set to 12X

Eliminate main breakers in panelboards. Molded case switches aren’t an improvement. Use the 3:1 ratio rule with downstream thermal magnetic breakers. Impedance is your friend- it helps with selective coordination. Dry type transformers are your friend – it adds impedance & reduces fault current.

Use breakers with adjustable solid state trip units (LSI) – turn off the “I” UL 489 listed breakers (molded case, insulated case) with adjustable solid state trips (LSI) have an “instantaneous over ride” built in. Example: Manufacturer “S”, 1200A frame 50kAIC @ 480V Instantaneous over ride is 24kA. Turn off the “I” Allow for +/- 10% tolerance, use on circuits with available faults below 22kA.

Generator Main Breakers (UL 489) Fault currents are relatively low unless large sets in parallel. Use breakers with adjustable solid state trip units (LSI). Raise short time delay. Inst off. Maximize the “space” below and to the left of the gen breaker curve. In many cases the inst. over ride will be higher than the fault current produced by the genset

Generator Main Breaker – How Do I Fix This?

Use Solid State Breakers on Gensets Adjustable LSI trip units The “Red” diagonal line is the thermal damage curve for the alternator. 1.5 seconds is a critical an inflection point. Ideally we want our breaker trip curve between the green and black lines. But ,we also want our “I” turned off. Set the STD to about 0.15 seconds.

Use Solid State Breakers on Gensets The last thing you ever want to happen is tripping the main breaker on the generator when running in emergency mode. The idea is to create as much space below and to the left of the alternator damage curve. Turn off the “I” Set the STD high Use a solid state breaker with the instantaneous over ride higher than the decrement curve fault current > 4000A. That’s easy!

Generator Main Breaker – How Do I Fix This?

Summary Avoid mixing breakers & fuses. Reduce the available fault current. Add impedance to the circuit. Use breakers with solid state trip units. Set the instantaneous trip above the actual fault current. Select a breaker will an instantaneous override higher than the available fault current. Use the 3:1 Ratio Rule for Breakers Eliminate main breaker panelboards where possible. Check with the breaker manufacturer for hybrid breakers that improve coordination.

Please list the available short circuit currents on the single line diagram.

Thank you!!! Ken Box, P.E. Schneider Electric USA 30000 Mill Creek Avenue, Suite 300 Alpharetta, GA 30022 Phone: 770-792.4839 Ken.Box@schneider-electric.com

References & Specials thanks to National Fire Protection Association – NFPA-70 The National Electrical Code 2014 edition. Robert E. Fuhr, P.E. – Power Systems Engineering, Covington, WA – Meeting the NEC Requirements for Selective Coordination. Square D/Schneider Electric Data Bulletins