UNIVERSITY OF MARYLAND – BALTIMORE HEALTH SCIENCES FACILITY III SENIOR THESIS PRESENTATION KENNETH M. MOORE LIGHTING / ELECTRICAL THESIS ADVISOR │ SHAWN.

Slides:



Advertisements
Similar presentations
WHEELOCK COLLEGE CAMPUS CENTER AND STUDENT RESIDENCE schematic lighting design anne k cheney lighting | electrical option advisor : dr. kevin houser courtesy.
Advertisements

Reading Assignment for next week: HCL Chapter 14 ELECTRIC LIGHTING.
The Franklin Care Center Addition and Renovation Franklin Lakes, New Jersey Jennifer Curley Lighting/Electrical Option Faculty Advisor: Dr. Moeck.
Current Project Update October 25th 2012 Good Evening!!!
Thesis Presentation April 13, 2004 Brian Regan The Virginia Historical Society Building Lighting/Electrical.
Hall Corporate Headquarters Dan Rusnack Tuesday April 13 th, 2004 Lighting/Electrical Emphasis Thesis Presentation Thesis Presentation.
New Jersey Center for Science, Technology, and Mathematics Education John P. Mulhern April 15, 2008 Final Thesis Presentation.
David S. Ingalls Rink 73 Sachem Street, New Haven, CT 06501
Pennsylvania State Employees Credit Union Corporate Headquarters Senior Thesis Presentation | lighting / electrical | Sarah Wujcik | | Dr Houser.
Landon Roberts Lighting/Electrical Option 11/01/07 Medical Education Building Johns Hopkins University School of Medicine Electrical Systems Existing Conditions.
Building Statistics Owner – Dansko, Inc. Owner – Dansko, Inc. Manufacturer of shoes sold in over 3500 stores in the US and Canada Manufacturer of shoes.
West Village Commons Patrick Morgan Lighting/Electrical April 13, 2011.
Ballenger East Building Final Presentation Design Development Architectural Engineering Senior Thesis Presentation 2009 Lighting / Electrical Option Student.
Jason Weaver 12/13/2007 Ann and Richard Barshinger Life Sciences & Philosophy Building Franklin & Marshall College Lancaster, PA.
UNIVERSITY OF MARYLAND – BALTIMORE HEALTH SCIENCES FACILITY III SCHEMATIC DESIGN KENNETH M. MOORE LIGHTING / ELECTRICAL THESIS ADVISOR │ SHAWN GOOD 1.
Fraunhofer | Center for Sustainable Energy Boston, MA Schematic Lighting Design Xiaoyin Wu
NEW COMMUNITY FACILITY Adam Kroll - Lighting / Electrical - Consultant: Dr. Richard Mistrick - Tech 3: Schematic Design.
Senior Thesis Presentation Jason Weaver 5th Year – Architectural Engineering Lighting/ Electrical Option Advisors: Dr. Mistrick & Prof. Dannerth Ann and.
The Edward St. John Student Center Zachary Haupt Faculty Advisor: Dr. William Bahnfleth 11 April 2011.
Schematic Design Proposal Dan Rusnack 11/14/03 Lighting/Electrical option Thesis project The Hall Corporate Headquarters.
2009 AE Senior Thesis Presentation MICHAEL P. GARDNER Mixed-Use Project Eastern United States.
William H. Gates Hall University of Washington School of Law Katie Jenkins The Pennsylvania State University Architectural Engineering Lighting/Electrical.
Boston University ∙ Arena and Recreation Center 2007 Senior Thesis Alexis M. Kreft Advisor: Dr. Mistrick Architectural Engineering Lighting and Electrical.
Schematic Design Proposal Bahen Centre for Information Technology University of Toronto Toronto, Ontario, Canada Rebecca Ho Lighting/Electrical Option.
Background Design Concept Gallery Lecture Hall (acoustics) Meeting Room Conclusions The Bahen Centre for Information Technology Spring 2003 Senior Thesis.
Maryland Transportation Authority Police Training Facility Schematic Design Presentation December 13, 2007 Leah Clark.
Leah Matern Lighting/Electrical Option Faculty Advisors: Dr. Richard Mistrick and Ted Dannerth April 13, 2011 Crystal Lake Elementary School Lake Mary,
Building Plans.
Southeast View of IRMC West View of IRMC. Presentation Outline Introduction Existing Structure Thesis Goals Structural Depth Lighting Breadth Conclusion.
Lutron Thesis ProposalCorron Cultural CenterSara Lappano Sara Lappano, EIT, LC-Intern Lighting/Electrical Option.
Center for the arts university towson university Benjamin Mitten Spring 2005 Benjamin Mitten Lighting/Electrical Spring 2005 center for the arts towson.
Apollo Apollo Scott Brown | Andrew Levy. 350 Mission Introduction | Lighting Design | Lighting Controls | Energy Savings | Conclusions Apollo Apollo.
CNBC GLOBAL HEADQUARTERS
Howard County General Hospital
Dansko Phase III West Grove, PA David Rosenberger Lighting/Electrical Lighting Advisor: Dr. Mistrick Electrical Advisor: Ted Dannerth.
Newseum and Freedom Forum Headquarters Washington, D.C. Ryan Wise Lighting/Electrical Option Consultant: Dr. Mistrick Dec. 14, 2007.
Building Overview Lighting Depth & Electrical Depth – Redesign -Streetscape -Gallery -Flex Use Space -Laboratory Architectural Breadth– Southern façade.
Thesis Lighting Design Proposal Dan Rusnack 12/9/03 Lighting/Electrical option Senior Thesis project Hall Corporate Headquarters.
UNIVERSITY OF MARYLAND – BALTIMORE HEALTH SCIENCES FACILITY III SENIOR THESIS PRESENTATION KENNETH M. MOORE LIGHTING / ELECTRICAL THESIS ADVISOR │ SHAWN.
Schematic Lighting Design Natty Boh Building Baltimore, Maryland Eric Singley Penn State University Architectural Engineering.
The Sunshine Elementary School Redesign Proposal Pennsylvania State University AE Senior Thesis Nicholas Scheib Mechanical Option- IP.
151 First Side William J. Buchko introduction overview proposal structural depth acoustics breadth cm breadth conclusions 151 First Side Pittsburgh, PA.
Howard County General Hospital Schematic Design Proposal Casey Schardt.
Howard County General Hospital
CSE Renovation Project Boston, MA Xiaoyin Wu (Laura) Lighting/Electrical | Architectural Engineering | Penn State University.
Dorrance H. Hamilton Building
The School Of Forest Resources Building University Park, Pennsylvania Chris Hoyman The Pennsylvania State University Architectural Engineering Lighting/Electrical.
The National Research and Training Institute for the Blind Allison Brown Lighting/ Electrical Option April 17 th, 2003.
Naval Network & Space Operations Command (NNSOC) Christopher Ankeny Lighting/Electrical Option Senior Thesis 2007 Advisor: Dr. Richard Mistrick Electrical.
Malory J. Faust ∙ Mechanical Option ∙ Senior Thesis 2007.
North Hills Junior High School Schematic Lighting Design
Twin Rivers Elementary/Intermediate of McKeesport Area School District Tessa Bauman Mechanical Option Technical Consultant: Laura Miller 1600 Cornell St.,
Schematic Lighting Design Natty Boh Building Baltimore, Maryland Eric Singley Penn State University Architectural Engineering.
BUILDING: LOCATION: SIZE: OCCUPANT: ARCHITECT: ENGINEERS: St. Francis Friary Hanceville, Alabama 59,900 square feet, 2 floors above grade Archdiocese.
Schematic Design | December 9, 2009 | Cassandra Watson Franklin Square Hospital Center Patient Tower and Emergency Department Addition.
North Hills Junior High School Pittsburgh, PA Senior Thesis Final Presentation 2005 Chris Rush Lighting / Electrical Faculty Consultant: Dr. Mistrick.
J. david maino the pennsylvania state university architectural engineering lighting/electrical.
Philip Mackey The Pennsylvania State University Architectural Engineering L/E Option HC HOLY CROSS HOSPITAL – NORTH ADDITION FINAL REPORTPhil Mackey Holy.
1 City of Portland Bureau of Development Services Staff Presentation to the Design Commission Land Use Review LU DZ Arthouse.
Von Liebig Center for Science Juniata College Huntingdon Pa Lutron Lighting Presentation Derek Sitosky.
Villanova University: School of Law Jason Greer The Pennsylvania State University Architectural Engineering Lighting/Electrical Option Senior Thesis –
Maryland Transportation Authority Police Training Facility
The AstroPower Headquarters Newark, Delaware
Rosegarden Branch Library San Jose, CA
Grunenwald Science and Technology Building
21st Century School Buildings Plan
SHEPHERD UNIVERSITY WELLNESS CENTER
Concept Features Bus entry, exit and drive are separate from visitor and parent entry and drive Additional area behind building for bus traffic and turn-around;
RiverView Condominiums II Chicago, IL
115-Unit Mixed-Use Project (711 E
Presentation transcript:

UNIVERSITY OF MARYLAND – BALTIMORE HEALTH SCIENCES FACILITY III SENIOR THESIS PRESENTATION KENNETH M. MOORE LIGHTING / ELECTRICAL THESIS ADVISOR │ SHAWN GOOD

BACKGROUND PROJECT OVERVIEW PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

BACKGROUND  HIGHLY ADVANCED RESEARCH FACILITY  HOUSES RESEARCH GROUPS FOR SCHOOLS OF MEDICINE, PHARMACY, AND DENTISTRY  ARCHITECT HELLMUTH, OBATA, KASSABAUM (HOK)  CONSTRUCTION MANAGER BARTON MALOW COMPANY  OWNED BY UMB OFFICE OF FACILITIES MANAGEMENT “ The Health Sciences Facility III further strengthens our footprint in west Baltimore and, as a result, our economic impact on the city and the state. We’re privileged to be able to help revitalize our critically important Baltimore neighborhoods and the state of Maryland as a whole, and at the same time, enable biomedical research and education that has the potential to save lives.” Jay A. Perman, MD President, University of Maryland SOUTH FAÇADE PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

BACKGROUND  PROJECT SIZE 430,000 GSF  CONSTRUCTION TIMELINE JULY 2013 – SEPTEMBER 2017  PROJECT CONSTRUCTION COST $ 216,000,  PROJECT DELIVERY CM AT RISK NORTH FAÇADE SOUTH FAÇADE PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

BACKGROUND  13 STORIES  MECHANICAL MEZZANINE + PENTHOUSE  7 STORY ATRIUM + 3 MAIN TOWERS  WET LAB + DRY LAB  GREEN ROOF WEST ELEVATION EAST ELEVATION PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

BACKGROUND PROJECT LOCATION PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

 CITY OF BALTIMORE  SEVERAL BLOCKS FROM INNER HARBOR  CENTRAL LOCATION IN UNIVERSITY CAMPUS 666 W. BALTIMORE ST. PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

 SCHOOL OF DENTISTRY 666 W. BALTIMORE ST. PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

 SCHOOL OF DENTISTRY  SCHOOL OF MEDICINE 666 W. BALTIMORE ST. PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

 SCHOOL OF DENTISTRY  SCHOOL OF MEDICINE  SCHOOL OF PHARMACY 666 W. BALTIMORE ST. PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

BACKGROUND DESIGN CONCEPT PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

 PRODUCTION AND EMISSION OF LIGHT BY A LIVING ORGANISM  GREEK: BIOS MEANING “LIVING”  LATIN: LUMEN MEANING “LIGHT” BIOLUMINESCENCE PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

BACKGROUND ELEVATOR LOBBY PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

ELEVATOR LOBBYDESIGN CRITERIA  HIGH PEDESTRIAN ACTIVITY  EFFECTIVE CENTER OF PEDESTRIAN ACTIVITY  ACCESSED VIA MAIN ATRIUM  4 PEDESTRIAN ELEVATORS + STAFF ELEVATOR  CENTRAL INFORMATION DESK  CONNECTS TO MEETING ROOM SPACE Circulation, Elevator Lobbies Horizontal (fc) Targets Vertical (fc) Targets Avg:Min Day1034:1 Night524:1 5’ AFF. Reception Lobbies Horizontal (fc) Targets Vertical (fc) Targets Avg:Min Desk Top1554:1 AFF; 5’AFF Common Space TypesLPD (W/ft 2 ) General Lobby Space0.90 PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

DESIGN CONSIDERATIONS PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

DESIGN CONSIDERATIONS  MECHANICAL SUPPLY VENTS PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

LUMINAIRE SUMMARY PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

LUMINAIRE SUMMARY  RECESSED FLUORESCENT GRAZE DOWNLIGHT PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

LUMINAIRE SUMMARY  RECESSED FLUORESCENT GRAZE DOWNLIGHT  RECESSED LED DOWNLIGHT – 13’ 6” MH PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

 RECESSED FLUORESCENT GRAZE DOWNLIGHT  RECESSED LED DOWNLIGHT – 13’ 6” MH  RECESSED LED DOWNLIGHT – 13’ 2” MH LUMINAIRE SUMMARY PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

CALCULATION SUMMARY PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

DESIGN SUMMARY Lighting CriterionRecommended ValueAchieved ValueCriteria Met LPD Area Summary< 0.9 W/ft W/ft 2 Yes Average Target Illuminance≥ 10 fc22.3 fcYes Desk Surface Illuminance15 fc16.8 fcYes PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

DESIGN SUMMARY Lighting CriterionRecommended ValueAchieved ValueCriteria Met LPD Area Summary< 0.9 W/ft W/ft 2 Yes Average Target Illuminance≥ 10 fc22.3 fcYes Desk Surface Illuminance15 fc16.8 fcYes PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

BACKGROUND NANOMEDICINE WORKSTATION PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

NANOMEDICINE WORKSTATION  RESEARCH AND DEVELOPMENT LAB  PRIMARILY CASEWORK, SINKS, SHELVING UNITS  MOVABLE BENCH SECTIONS WITH SHELVING  10 VENTILATION FUME HOODS DESIGN CRITERIA  LAB SPACE Classrooms: Science Labs Horizontal (fc) Targets Vertical (fc) Targets Avg:Min Bench50301:5:1 3’ ; 4’ 6” AFF. Common Space TypesLPD (W/ft 2 ) Workshop1.59 PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

DESIGN CONSIDERATIONS PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

DESIGN CONSIDERATIONS  PROVIDE TARGET ILLUMINANCE RECOMMENDED FOR SCIENCE LABS PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

DESIGN CONSIDERATIONS  PROVIDE TARGET ILLUMINANCE RECOMMENDED FOR SCIENCE LABS  WORKSTATION BENCHES ARE PRIORITY PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

DESIGN CONSIDERATIONS  PROVIDE TARGET ILLUMINANCE RECOMMENDED FOR SCIENCE LABS  WORKSTATION BENCHES ARE PRIORITY  AVOID SHELVING, CASEWORK, AND FUME HOODS PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

LUMINAIRE SUMMARY PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

LUMINAIRE SUMMARY  RECESSED 1 x 4 LINEAR FLUORESCENT DOWNLIGHT PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

LUMINAIRE SUMMARY  RECESSED 1 x 4 LINEAR FLUORESCENT DOWNLIGHT  RECESSED LED DOWNLIGHT PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

CALCULATION SUMMARY PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

DESIGN SUMMARY Lighting CriterionRecommended ValueAchieved ValueCriteria Met LPD Area Summary< 1.59 W/ft W/ft 2 Yes Average Target Illuminance≥ 50 fc62.8 fcYes PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

DESIGN SUMMARY Lighting CriterionRecommended ValueAchieved ValueCriteria Met LPD Area Summary< 1.59 W/ft W/ft 2 Yes Average Target Illuminance≥ 50 fc62.8 fcYes PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

BACKGROUND MEETING ROOM PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

MEETING ROOM PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY Conference: Meeting Horizontal (fc) Targets Vertical (fc) Targets Avg:Min Discourse30101:5:1 2’ 6” ; presentation board height. Common Space TypesLPD (W/ft 2 ) Conference/Meeting1.23 DESIGN CRITERIA  MAIN CONFERENCE ROOM  PRESENTATION AND LECTURE SPACE  ADJUSTABLE FURNITURE TO MEET SPACE REQUIREMENTS

DESIGN CONSIDERATIONS PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

DESIGN CONSIDERATIONS PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY  MECHANICAL SUPPLY VENTS

DESIGN CONSIDERATIONS PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY  MECHANICAL SUPPLY VENTS  PROJECTOR SYSTEMS

LUMINAIRE SUMMARY PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

LUMINAIRE SUMMARY PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY  RECESSED LED SLOT LUMINAIRE

LUMINAIRE SUMMARY PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY  RECESSED LED SLOT LUMINAIRE  RECESSED LED LINEAR DOWNLIGHT

LUMINAIRE SUMMARY PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY  RECESSED LED SLOT LUMINAIRE  RECESSED LED LINEAR DOWNLIGHT  RECESSED LED WALL WASHERS

CALCULATION SUMMARY PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

DESIGN SUMMARY Lighting CriterionRecommended ValueAchieved ValueCriteria Met LPD Area Summary< 1.23 W/ft W/ft 2 Yes Average Target Illuminance≥ 30 fc34.9 fcYes PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

DESIGN SUMMARY Lighting CriterionRecommended ValueAchieved ValueCriteria Met LPD Area Summary< 1.23 W/ft W/ft 2 Yes Average Target Illuminance≥ 30 fc34.9 fcYes PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

BACKGROUND PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY REPORT BREADTHS

BACKGROUND PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY  FAÇADE BREADTH STUDY RAIN SCREEN ADDED TO EXTERIOR  STRUCTURAL BREADTH STUDY RAIN SCREEN LOAD SUMMARY

BACKGROUND PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY ELECTRICAL DEPTH

BACKGROUND PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY  WATTSTOPPER Isolé IDP-3050 Power Strip with Personal Sensor IDP A, DI-110  CONTROLS DESKTOP EQUIPMENT  SAVES ENERGY WITH PERSONAL OCCUPANCY SENSOR  CONSISTS OF 8 OUTLET STRIP (6 CONTROLLED BY OCUPANCY)  EQUIPPED WITH SURGE PROTECTION ENERGY SAVINGS

BACKGROUND PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY  USED PRIMARILY IN OFFICE SPACE  8 FLOORS OFFICE SPACE  TOTAL SUPPLY RATE OF THE BUILDING = C/KWH  INITIAL STUDY SHOWS NEW SUPPLY RATE = C/KWH  SAVING ROUGHLY 10% ENERGY SAVINGS

BACKGROUND PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY REPORT SUMMARY

BACKGROUND  HIGHLY ADVANCED RESEARCH FACILITY  HOUSES RESEARCH GROUPS FOR SCHOOLS OF MEDICINE, PHARMACY, AND DENTISTRY  SHARE NANOMEDICINE CENTER  CENTRAL CAMPUS LOCATION  HEART OF BALTIMORE  EXPECTED COMPLETION DATE – SEPTEMBER 2017 PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY

BACKGROUND Lighting CriterionRecommended ValueAchieved ValueCriteria Met LPD Area Summary< 1.59 W/ft W/ft 2 Yes Average Target Illuminance≥ 50 fc62.8 fcYes Lighting CriterionRecommended ValueAchieved ValueCriteria Met LPD Area Summary< 0.9 W/ft W/ft 2 Yes Average Target Illuminance≥ 10 fc22.3 fcYes Desk Surface Illuminance15 fc16.8 fcYes  ELEVATOR LOBBY  WORKSTATION  MEETING ROOM PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY Lighting CriterionRecommended ValueAchieved ValueCriteria Met LPD Area Summary< 1.23 W/ft W/ft 2 Yes Average Target Illuminance≥ 30 fc34.9 fcYes

BACKGROUND  Dilaura, D. L., Houser, K. W., Mistrick R. G., Steffy G. R. (2011). The Lighting Handbook (10th ed.). New York, NY: Illuminating Engineering Society.  ASHRAE Standard 90.1 – Energy Standard for Buildings Except Low- Rise Residential Buildings th ed. ASHRAE. Print.  maryland-baltimore-health-sciences-facility-iii/  aspx#.VS4_EU3wvGh PROJECT OVERVIEW PROJECT LOCATION DESIGN CONCEPT ELEVATOR LOBBY NANOMEDICINE WORKSTATION MEETING ROOM REPORT BREADTHS ELECTRICAL DEPTH REPORT SUMMARY THANK YOU