Vadodara institute of engineering,kotambi NAME:NAFISKHANPATHAN(13ELEE181) BARIYA VIPUL(13ELEE182) PATEL AMIT(13ELEE180) BRANCH:EE-2 PPT OF EEE
Miniature circuit breaker(mcb)
Miniature Circuit Breakers (MCB) Multi 9
Protect cables against overloads and short circuits Let the current flow without overheating on cables Open and close a circuit under rated current Protect against insulation faults (see earth leakage protection module) Definition Main functions Miniature circuit = switch + trip unit breaker (MCB) Symbol
A mechanical system to open and close the circuit A bimetal strip to act against overloads A magnetic trip to act against short circuits Definition A Multi 9 circuit breaker has: Miniature circuit = switch + trip unit breaker (MCB)
It has standardized modular dimensions 125A 50 kA 440 V CA Definition Main performances It fits in your pocket...
Definition Multi 9 standard Multi 9 switchgear comes in 9 mm pitch width symmetrical rail external part depth 6010 maxi maxi 44 maxi The modular design meets 2 criteria: mounting on a 35 mm symmetrical rail dimensions - modules in widths of 17.5 mm external part = 45 mm - depth between 55 and 70 mm
The technology Active parts C60N NC100 / NC125 terminal fixed contact moving contact strip braid magnetic trip load side terminal terminal bimetral strip strip braid moving contact magnetic trip load side terminal strip braid bimetal strip
Overload protection bimetal tripping bar bimetal tripping bar screw calibration strip braid NC45 NC100 / NC125 A bimetal strip is used: to protect the cable against overloads symbol: principle of the bimetal: in a Multi 9 circuit breaker
Thermal tripping curve the "thermal" part of the tripping curve must be in accordance with the standard Overload protection Legend: In = rated current Ind = no tripping current Id = tripping current tripping no tripping destruction of bimetal accuracy t (s) I/InInIndId
Overload protection Simultaneous multi-pole tripping Temperature derating our circuit breakers do not have temperature compensation if the calibration temperature is different from the ambient temperature: derating is required
Short-circuit protection Short-circuit current is given as RMS or peak (Isc or Îsc) RMS = Root Mean Square in symmetrical DC (with PF = I) Short-circuit protection must limit thermal stress in the cable in order to prevent cable damage (which may reach vaporization of the copper in some cases) Comments slide 29
Short-circuit protection "By-pass" technique for the protection of sensitive parts of the circuit breaker DC breaking is difficult "By-pass" technique for the protection of sensitive parts of the circuit breaker (magnetic trip) The arc in Multi 9 circuit breakers 2 breaking techniques used by Multi 9 arcing horn arcing horn NC45NC100 / NC125
Short-circuit protection Magnetic tripping curve Our curves are instantaneous tripping curves Legend: Ind = no tripping current Id = tripping current destruction of the solenoid tripping no tripping t (s) I/InIndId
B curve 3 and 5 In protection low short-circuit current generators The magnetic tripping levels with high inrush current: like LV/LV transformers C Curve 5 and 10 In control and protection of circuits with high short-circuit current in industrial and domestic distributions D and K curves tripping betwen tripping: 10 to 14 In; more particulary adopted for installations with high inrush currents like LV/LV transformers Z curve 2.4 to 3.6 In protection against electronic circuits MA curve 12 In; protection only against short-circuit and high inrush currents such as motors, coil G M
Side panel marking: Marking Front panel marking: Circuit breaker marking is governed by strict rules in accordance with the standards and decisions made by the manufacturer
Choosing a circuit breaker In conclusion A Multi 9 circuit breaker is determined by: rating breaking capacity number of poles voltage tripping curve standard frequency type of load
Auxiliaries: C60 SD: alarm switch MX + OF: shunt trip MN: undervoltage release The information is transmitted via a mechanical link C60/NC100 and NC125 auxiliaries are not compatible 54 mm maxi 4 types of auxiliaries for our Multi 9 circuit breakers OF: indication switch MX+OF OF SD C60 44/3 MN 51/3 52/3 54/3 53/3
Auxiliaries: NC100 - NC125 The information is transmitted via a mechanical link C60/NC100 and NC125 auxiliaries are not compatible NC100H MX+OF or Vigi MN or OF SD 33/334/3 35/3 36/3 27/3 SD: alarm switch MX + OF: shunt trip MN: undervoltage release 4 types of auxiliaries for our Multi 9 circuit breakers OF: indication switch