Out-Of-Compliance Grocery UES Measure Recommendations Regional Technical Forum March 18, 2014.

Slides:



Advertisements
Similar presentations
Pole-Mounted Lights (Barn Lights) Proven UES Measure Proposal Regional Technical Forum January 22, 2014.
Advertisements

Residential Refrigerators and Freezers UES Measure Update Regional Technical Forum October 14, 2014.
Residential New Construction (NC): Slab Insulation UES Measure Update Regional Technical Forum March 18, 2014.
Residential Single Family Clothes Washer UES Measure Update Christian Douglass Regional Technical Forum February 18, 2015.
Commercial Clothes Washer UES Measure Update Regional Technical Forum February 19, 2014.
Residential LED UES Measure Update Regional Technical Forum August 20, 2013.
Oregon Energy Star Homes Measure Update New Measure Proposal April 22nd,
Evaluation of Energy Savings for Strip Curtains Presented To RTF Scott Moore PECI Sr. Engineer June 2, 2009.
Out-Of-Compliance Grocery UES Measure Recommendations Regional Technical Forum June 17, 2014.
Variable Frequency Drives (VFDs) for Potato/Onion Shed Fans UES Measure Update Regional Technical Forum April 23, 2014.
Commercial Tank Water Heaters Out-of-Compliance (OOC) UES Measure Recommendation Regional Technical Forum November 19, 2013.
Heat Pump Water Heaters Provisional UES Proposal Regional Technical Forum October 4 th, 2011.
Grocery Measure: LEDs for Reach-In Display Cases Regional Technical Forum July 21 st, 2015 Mohit Singh-Chhabra.
LED Case Lighting With and Without Motion Sensors Michele Friedrich – Sr. Engineer PECI 1/5/2010.
Regional Technical Forum July 1st, 2008 Presented by Ryan Fedie and Jamie Anthony Portland Energy Conservation, Inc.
Today’s “Game Plan” Two Trial-Runs of a new deemed measure review process – Deemed measure analysis and review Developed by … – (consultant, RTF member/staff,
Commercial Showerhead UES Measure Update Regional Technical Forum Staff Update June 18, 2013.
Night Covers on Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30,
Advanced Power Strips (APS) Planning UES Measure Proposal Regional Technical Forum August 20, 2013.
Retrofit Doors to Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30,
Heat Pump Water Heaters: Tier 2 – Ducted Interior Installations Provisional UES Proposal Regional Technical Forum February 14 th, 2012.
Plans to bring Out-of-Compliance UES Measures back into Compliance: 1. Agricultural Irrigation Hardware UES 2. Agricultural Motors UES Regional Technical.
RTF Research and Evaluation Subcommittee Meeting Regional Technical Forum April 15, 2013.
Thermostatic Shower Restriction Valve –Measure Screening Results New Measure Proposal February 19th, 2014.
Non-Residential Network Computer Power Management UES Measure Update Regional Technical Forum July 16, 2013.
Pre-Rinse Spray Valve Small Saver UES Measures Regional Technical Forum September 17, 2013.
LED Case Lighting in Vertical and Semi-Vertical Open Refrigerated Cases Eric Mullendore – Energy Analyst PECI 6/29/2010.
EnergySmart Grocer Program Evaluation Findings Summary PWP, Inc.
Commercial Showerhead UES Measure Update Regional Technical Forum Staff Update June 18, 2013.
Grocery Measure: EC Motors for Display Cases Regional Technical Forum July 21 st, 2015 Mohit Singh-Chhabra.
Regional Technical Forum October 9, ECMs for Compressor Head Cooling Fans  Measure –Retrofit of compressor head cooling fans on low temperature.
Grocery Measure: EC Motors for Display Cases Regional Technical Forum June 16 th, 2015 Mohit Singh-Chhabra.
Standard Information Workbook (SIW) Update Proposal Regional Technical Forum May 13, 2014.
Residential Single Family and Manufactured Home Heat Pump Water Heaters Christian Douglass Regional Technical Forum 4/14/2015.
Anti-Sweat Heater Control Small Saver UES Measure Regional Technical Forum September 17, 2013.
Deemed Savings Update: ECMs in Display Cases Ben Cartwright PECI January 5, 2009.
Update: Grocery Refrigeration Provisional Standard Protocol for Site Specific Savings RTF Meeting June 28,
RTF Delivery Verification Guidance Batch 1 Jennifer Anziano Regional Technical Forum May 12, 2015.
EER Analysis Results Regional Technical Forum March 18, 2014.
Commercial Showerhead UES Measure Update Regional Technical Forum April 16, 2013.
2011 RTF Projects RTF Input on SOW Outlines: - Deemed Measure Reviews - Measure Life Guidelines -Measure Cost Guidelines Regional Technical Forum April.
Out-Of-Compliance UES Measure Recommendations Part 1 – November Measures Regional Technical Forum November 19, 2013.
Measurement and Verification of Refrigeration Measures in 4 Grocery Stores in Pacific County Presented to the Regional Technical Forum August 8 th, 2006.
Integration Issues for RTF Guidelines: Savings, Lifetimes and Cost/Benefit October 24, 2012 Regional Technical Forum Presented by: Michael Baker, SBW.
Implementer’s Group July 2015 RTF Meeting Debrief and Upcoming Meeting Prep July 29, 2015.
High Efficiency Evaporator Coils for Medium Temperature Cases Dustin Bailey, Engineer PECI Jan 5, 2010.
RTF Management Update Jennifer Anziano Regional Technical Forum February 18, 2015.
Residential New SF Energy Star Homes UES Measure Update December 17th, 2013.
Grocery Store Issues RTF April 10, Need Recommendations PECI: Energy Smart Grocer Program Savings method for interactive measures Savings method.
PTCS Commissioning, Controls & Sizing Update of UES Measure Category and/or Status Regional Technical Forum July 15, 2014.
Out-Of-Compliance Grocery UES Measure Recommendations Regional Technical Forum July 15, 2014.
Ductless Heat Pumps (DHP) in Single Family Homes with Zonal Electric Heat Proven UES Measure Proposal Regional Technical Forum October 16, 2013.
GrocerSmart TM Energy Modeling Software -Revision Status Report- & -Request For Input- July 13, 2010.
Display Case Motion Sensors Small Saver Measure Update July 16th, 2013.
Commercial Clothes Washer UES Measure Update Regional Technical Forum April 16, 2013.
UES Measure: Commercial – Traffic Signal LED’s Commercial – Traffic Signal LED’s Proposal to Change Status from “Under Review” to “Active” Regional Technical.
Residential Refrigerator UES Measure Update Regional Technical Forum April 16, 2013.
ENERGY STAR Commercial Refrigerators and Freezers Regional Technical Forum January 21 st, 2016 Mohit Singh-Chhabra.
Research and Evaluation Subcommitee – 2014 Plans Regional Technical Forum January 22, 2014.
December 11, 2012 Grocery UES Updates Reach-in LED and Case ECM.
Non-Residential Network Computer Power Management Christian Douglass Regional Technical Forum January 21, 2016.
Agriculture Irrigation Hardware UES Measure Update Regional Technical Forum April 16, 2013.
Residential Single Family Clothes Washer UES Measure Update Regional Technical Forum September 16, 2014.
Exterior LED Area Lights
Commercial Efficient Tank Water Heater UES Measure Update Regional Technical Forum December 17, 2013.
New Refrigeration Measures -Status Report- & -Request for Input- September 13, 2010.
ANTONIO CORRADINI & M M VALMIKI, AESC MAY 26, 2016 High Efficiency PMSM Fan Assemblies for Refrigerated Case Evaporators - Abstract.
UES MEASURE REVIEW PROJECT Final Report March 14, 2012 Regional Technical Forum Presented by: Jeff Romberger.
Ductless Heat Pumps (DHP) in Single Family Homes with Zonal Electric Heat UES Measure Update Regional Technical Forum June 17, 2014.
RTF Delivery Verification Guidance Batch 3 Jennifer Light Regional Technical Forum November 10, 2015.
Presentation transcript:

Out-Of-Compliance Grocery UES Measure Recommendations Regional Technical Forum March 18, 2014

Presentation Outline Background Measure Overview Staff Highlighted Areas UES Workbook – Measure Descriptions – Measure Analysis and Input Details – Savings, Cost, and Cost Effectiveness RTF Staff Recommendation Proposed Decision 2

Background Multiple Grocery measures found Out-of-Compliance – Subsequent analysis determined remaining potential small – Extended sunset date at November 2013 meeting – Staff to develop plan to bring back into compliance Grocery measures in question: 1.ECMs for Walk-ins 2.Walk-in Evaporator Fan ECMotor Controllers 3.Compressor Head Fan Motor Retrofit to ECM 4.Floating Head Pressure Controls for Single Compressor Systems 5.Autoclosers 6.Door Gasket Replacement 7.Display Case LEDs (Open Cases) 8.Strip Curtains 3

Measure Overview Plan to go through each measure individually Seeking decision on methodology of 3 measures presented – Need to be updated with finalized EER results If 15% lower EER value, then ~5% increase in savings Staff working with PECI to obtain updates to other five grocery measures Will request sunset extension on measures not presented today 4

ECMs for Walk-ins 5

Measure Overview What does it do? – Replaces existing Shaded Pole motor with a more efficient Electrically Commutated Motor (ECM) – Savings occur from: Direct motor wattage reduction Waste heat reduction to refrigeration system 6

Recommendation Memo Items Recommendation Memo ItemStatusStaff Response The Average EER parameter is based on proprietary DOE 2.2-R simulations of Northwest grocery environments. This parameter needs to be derived transparently from publically available data. DoneLimited remaining potential and classification as a Small Saver alleviates the need to collect data. Used PECI modeling analysis to derive value. The sources for the Fan Input Power parameter are not published. Provide a summary of the analyses performed on the raw data to obtain the referenced values. DoneOnline check of motor sources confirms wattages used are sufficient. Further documentation is needed for Annual Fan Runtime Hours. If documentation is not available, use the suggested value of 8,322 sourced from Pacific Gas and Electric (PGE) and Southern California Edison (SCE) work papers. DoneUsed recommended source of SCE 2012 workpaper for defrost cycle time of 72 minutes per day. The sources noted for the Mix of Rated Fan Power and Mix of Low and Medium Temperature Walk-ins parameters should be more thoroughly documented. DonePECI has provided weightings based on site audit data. Weightings match ECM for Reach-in case measure. 7

Staff Highlighted Areas Weighting of motors into one category have large variation for smaller sized motors Measure is retrofit, therefore a pre-conditions baseline – Unsure of current market practice for motor replacement 8

Motor Weighting PECI provided motor weights for 3 motor classes: 1/20HP, 1/15HP, and Watt Difference in weighted average for small motors 9 Wtd. Average

Motor Weighting Ok to leave as 1 measure based on PECI weighting of expected program conditions? Split into two measures? – One for 1/15 & 1/20 – One for Watt Staff Recommendation: Split into two measures to account for savings variation 10

Pre-conditions RUL needs to be estimated for pre-conditions – DEER provides estimate of 5 years What is current practice at end of RUL? – If shaded pole motors only, then RUL=EUL – If combination of shaded pole and ECM, then: Full savings and cost assigned during RUL period Reduced savings and cost assigned for remaining EUL period Do we want to do this for small savers? Staff Recommendation: Assume current practice is 100% Shaded Pole and assign savings accordingly 11

Measure Descriptions Go to the following sections in the Summary tab in the proposed measure workbook: – Measure Properties – Measure Identifiers 12

Measure Analysis and Inputs Details Go to the following sections in the Summary tab in the proposed measure workbook: – Constant Parameters – Energy Savings Estimation Method, Parameters and Data Sources – Measure Incremental Costs and Benefits – Measure Lifetime 13

Savings, Cost, & Cost Effectiveness Go to the following sections in the Presentation tab in the proposed measure workbook: – Measure savings – Measure costs – Measure TRC B/C ratios 14

RTF Staff Recommendation Approve the ‘ECMs for Walk-ins’ UES measure as a “Small Saver” – Update EER values with finalized numbers once analysis is complete (~4% increase in savings) Split measure into two identifiers Assume current practice = all Shaded Pole Set the measure status to “Active” Set the sunset date to March,

Proposed Decision “I _______________ move that the RTF: Pick one of each: [Split into two measures / weight into one measure]; and Assume current practice is [all Shaded Pole / x.x % is ECM]; and Approve the ‘ECM for Walk-ins’ measure as a “Small Saver” UES; Set the measure status to ‘Active;’ and Set the sunset date to March, 2019.” 16

ECMotor Controller for Evaporator Fans on Walk-ins 17

Measure Overview What does it do? – Installs a motor controller on Evap. systems already equipped with ECMs – Provides 2-speed operation of fans High when cooling; low when not – Savings occur from: Direct motor wattage reduction due to full speed runtime hours reduction Waste heat reduction to refrigeration system 18

Recommendation Memo Items Recommendation Memo ItemStatusStaff Response Recommend collecting primary meter data or use a sufficiently reliable secondary data source to establish the Full Speed Fan Motor Input Power for the 16 to 23 watt motor size category. DoneUsed fan motor power from ECM replacement analysis. Derived from manufacturer data. Recommend collecting primary meter data or use a sufficiently reliable secondary data source to establish the Low Speed Fan Motor Input Power. DoneUsed fan laws to ratio high/low power consumption based off full speed input power. Exponent set at 2.5 (Professional Judgment). The Average EER parameter is based on proprietary DOE 2.2-R simulations of Northwest grocery environments. This parameter needs to be derived transparently from publically available data. DoneLimited remaining potential and classification as a Small Saver alleviates the need to collect data. Used PECI modeling analysis to derive value. Further documentation is needed for Annual Fan Runtime Hours. DoneRelied on NRM metering study for this parameter and provided documentation on study when possible. 19

Staff Highlighted Areas None 20

Measure Descriptions Go to the following sections in the Summary tab in the proposed measure workbook: – Measure Properties – Measure Identifiers 21

Measure Analysis and Inputs Details Go to the following sections in the Summary tab in the proposed measure workbook: – Constant Parameters – Energy Savings Estimation Method, Parameters and Data Sources – Measure Incremental Costs and Benefits – Measure Lifetime 22

Savings, Cost, & Cost Effectiveness Go to the following sections in the Presentation tab in the proposed measure workbook: – Measure savings – Measure costs – Measure TRC B/C ratios 23

RTF Staff Recommendation Approve the ‘ECMotor Controller for Evaporator Fans on Walk-ins’ UES measure as a “Small Saver” – Update EER values with finalized numbers once analysis is complete (~6% increase in savings) Set the measure status to “Active” Set the sunset date to March,

Proposed Decision “I _______________ move that the RTF: Approve the ‘ ECMotor Controller for Evaporator Fans ’ measure as a “Small Saver” UES; Set the measure status to ‘Active;’ and Set the sunset date to March, 2019.” 25

Compressor Head Fan Motor Retrofit to ECM 26

Measure Overview What does it do? – Replaces existing Shaded Pole motor with a more efficient Electrically Commutated Motor (ECM) on a compressor head fan – Savings occur from: Direct motor wattage reduction 27

Recommendation Memo Items Recommendation Memo ItemStatusStaff Response Provide data sources with metered data to justify baseline and efficient Input Motor Wattage assumptions. DoneOnline check of motor sources confirms wattages used are sufficient. Revise annual run time to apply Duty Cycle of 70% instead of 75%, based on revised values reported in Navigant Consulting’s “Energy Savings Potential and R&D Opportunities for Commercial Refrigeration Equipment.” DoneUpdated assumption with more recent data as per recommendation memo. Additional data should be collected for the Fan Motor Size Population Weighting which was supplied by one grocery chain based on a review of its own refrigeration equipment. DoneNo additional data available. Uptake has been minimal, and Kroger is primary target of measure. Propose to keep weighting as-is using grocery store values. 28

Staff Highlighted Areas None 29

Measure Descriptions Go to the following sections in the Summary tab in the proposed measure workbook: – Measure Properties – Measure Identifiers 30

Measure Analysis and Inputs Details Go to the following sections in the Summary tab in the proposed measure workbook: – Constant Parameters – Energy Savings Estimation Method, Parameters and Data Sources – Measure Incremental Costs and Benefits – Measure Lifetime 31

Savings, Cost, & Cost Effectiveness Go to the following sections in the Presentation tab in the proposed measure workbook: – Measure savings – Measure costs – Measure TRC B/C ratios 32

RTF Staff Recommendation Approve the ‘Compressor Head Fan Motor Retrofit to ECM’ UES measure as a “Small Saver” Set the measure status to “Active” Set the sunset date to March,

Proposed Decision “I _______________ move that the RTF: Approve the ‘ Compressor Head Fan Motor Retrofit to ECM ’ measure as a “Small Saver” UES; Set the measure status to ‘Active;’ and Set the sunset date to March, 2019.” 34

OTHER OOC GROCERY MEASURES 35

RTF Staff Recommendation Staff needs more time to incorporate changes and data from PECI Request 3 month sunset extension for the following measures: 36 MeasureStatusSunset Date Grocery - Floating Head Pressure Controls for Single Compressor SystemsOut-of-Comp.June, 2014 Grocery - AutoclosersOut-of-Comp.June, 2014 Grocery - Door Gasket ReplacementOut-of-Comp.June, 2014 Grocery - Display Case LEDs (Open Cases)Out of Comp.June, 2014 Grocery - Strip CurtainsOut-of-Comp.June, 2014

Proposed Decision 37 “I _________ move that the RTF extend the sunset dates for the following measures shown below.” MeasureStatusSunset Date Grocery - Floating Head Pressure Controls for Single Compressor SystemsOut-of-Comp.June, 2014 Grocery - AutoclosersOut-of-Comp.June, 2014 Grocery - Door Gasket ReplacementOut-of-Comp.June, 2014 Grocery - Display Case LEDs (Open Cases)Out of Comp.June, 2014 Grocery - Strip CurtainsOut-of-Comp.June, 2014