Electrical Distribution Training

Slides:



Advertisements
Similar presentations
Introduction to Switchgear
Advertisements

Understanding electrical networks to enhance their protection ? Situate the protection relay Ask the customer the right questions Duration: 43:35 min Expert:
MIFII DIGITAL FEEDER PROTECTION A Cost Effective Protection Solution for Overcurrent Protection at Any Voltage Level GE Multilin
HYDRAULICS & PNEUMATICS
Protections from the technical point of view “What you always wanted to know about protections and were afraid to ask…” Petra Píclová Online training
FP5000 Refer to for the latest information on this constantly evolving productwww.eatonelectrical.com.
RT3b – André Smit, Siemens USA
Elec467 Power Machines & Transformers
Slide 1 / 35 P&T - GPS - Training PhB - 01_TECH_TeSys_U_controller_ en 06/2004 Presentation of the range Composition of the controller  Control base 
INTRODUCTION TO SWITCHGEARS
1 PCA2 On-load Protection Condition Analyser. 2 PCA2 online testing concept Concept introduction: PCA2 is a new system test approach intended to save.
Submitted By Ravi Raj Rajeev Kumar Vipul Batra. FUNCTIONS PERFORMED BY THE RELAY MADE 1.OVER VOLTAGE PROTECTION 2.OVERCURRENT PROTECTION.
Chapter 7 SYSTEM PROTECTION
Prof. David R. Jackson ECE Dept. Fall 2014 Notes 5 ECE 2317 Applied Electricity and Magnetism Notes prepared by the EM Group University of Houston 1.
SISTEMA Example Two. Schneider Electric – Areva D Acquisition – June Example 2: Safe stopping of a PLC-driven drive with emergency stop – Category.
Discrimination of protection devices on installations
Electro-Pneumatics Module 1
Industrial Machine Control
Electrical Installation 2
Understand the concept to improve parameter setting
SFT 2841 IN CONNECTED MODE Prepare setting files.
POWER SYSTEM PROTECTION. Power system Generators Transformers Transmission lines »Underground cables »Overhead lines Distribution systems.
Electrical Distribution Training
Selective Coordination of Overcurrent Protective Devices
New proposed BU circuit and control logic design University of Washington.
Current operation (black keys) Descriptions Parameter / protection setting (blue keys) Main points to remember A B C D ? SEPAM UMIs SEPAM UMI OPERATION.
Manjula Dewadasa Arindam Ghosh Gerard Ledwich
A. Lisowiec 1, A. Nowakowski 1, Z. Kołodziejczyk 1, B. Miedziński 2 1 Centre For Tele-Information Systems and Hardware Applications, Tele and Radio Research.
Universal Relay Family B30 Presentation Q&As. Power Management The Universal Relay Contents... Application Algorithm Biased Characteristic Dynamic Bus.
Need for protection Power system must be kept in operation continuously without major breakdowns This can be achieved in two ways: 1.Implement a system.
Electrical Distribution Training Logic Equation Editor.
MV Network Operation and Control Barcelona May 2003 Eugenio Di Marino Italy Session 3 Alpha 1 Block 1.
Queensland University of Technology CRICOS No J Protection of distributed generation connected networks with coordination of overcurrent relays.
Protection & Switchgear
Consumer’s Main Switchroom & Main L.V. Switchboard
Introduction To Protective Relays This training is applicable to protective relaying and System Monitoring tasks associated with NERC Standards PRC-001.
SmartMQn Motor Horner APG, LLC September 9, 2008.
November 4, 2013 Topic: Electric Circuit Objectives:
Motor. What Does it Do? Monitors three phase motors for a number of current, temperature, estimated power and timing parameters. Provides motor protection.
Introduction To Protective Relays
1 Distributed Generation and Power Quality-Continued.
SISTEMA Example Four.
A PRESENTATION OF PRACTICAL TRAINING ON “400KV GSS “ \
Prepared by:Ronnel P. Agulto, CpE Objectives Different types of topologies; Their advantages & disadvantages How to choose an appropriate topologies in.
ΜΕΣΑ ΔΙΑΚΟΠΗΣ, ΠΡΟΣΤΑΣΙΑΣ ΚΑΙ ΕΛΕΓΧΟΥ ΚΥΚΛΩΜΑΤΩΝ ΟΙΚΙΑΚΩΝ ΗΛΕΚΤΡΙΚΩΝ ΕΓΚΑΤΑΣΤΑΣΕΩΝ ΣΤΟΧΟΣ: Ο μαθητής να: αναγνωρίζει και να επιλέγει τα κατάλληλα Μέσα.
ABOC/ATC days Electrical Network: Selectivity and Protection Plan José Carlos GASCON TS–EL Group 22 January 2007.
PRESENTATION ON THE TOPIC By: Rahul agarwal. INTRODUCTION  Overload protection circuit are required in inverters and uninterrupted power supplies to.
Student Name USN NO Guide Name H.O.D Name Name Of The College & Dept.
Main contacts closed – RED Colour with ON
SmartMQn Motor Protective Functions Ken Jannotta Jr. Horner APG, LLC.
ECE 498HZ: Power Distribution System Analysis
Survey of Smart Grid concepts and demonstrations Smart substation Ari Nikander.
This project on Primary sub station of Visakhapatnam port trust at Visakhapatnam. It is 132kv/11kv substation with incoming feeder from APTransco and 11.
Protection of Power Systems
 The figure below shows a protection system for a transmission line, consisting of a CT, PT, a relay and its associated circuit breaker.
Protection and Relay Schemes
Protection of Power Systems
the CERN Electrical network protection system
GROUND-FAULT GROUND-CHECK MONITOR
Chapter 7 System Protection
Agenda Introduction of Protective Relays
POWER SYSTEM COMMISSIONING AND MAINTENANCE PRACTICE
Presentation transcript:

Electrical Distribution Training Training for Sepam Series 20/40/80 Control and monitoring functions

Presentation Sepam series 20/4080 perform the basic control and monitoring functions required for electrical network operation and also reduces the need for auxiliary relays. Each Sepam includes the appropriate control and monitoring functions for the chosen application. In order for functions to be used, exclusive parameter setting and special wiring of the inputs and outputs are required. For easier commissioning, the functions have default settings that may be used for the most frequent applications.

Switchgear control This logic function handles all the circuit breaker closing and tripping conditions based on: breaking device status data remote control orders protection functions specific control logic scheme for each application (e.g. recloser, load shedding) In order for this function to operate, the Sepam series 80 must have the necessary logic inputs (an MES 120 module is required).

Switchgear control

Switchgear control detail of ANSI 25 control

Switchgear control Circuit breaker or contactor with tripping coil (parameter: circuit breaker)

Switchgear control Simple contactor (parameter: contactor)

Latching / acknowledgment The functions that inititate tripping may be latched individually when they are set up and may be reset according to different modes.

TC / switchgear position discrepancy This function detects discrepancies between the last remote control order received and the actual position of the circuit breaker or contactor.

Disturbance recording trigger

Switching of groups of settings There are two groups of settings, group A / group B, for the phase overcurrent, earth fault, directional phase overcurrent and directional earth fault protection functions. By switching from one group of settings to another, the protection characteristics may be adapted to suit the electrical environment of the application (change of earthing system, changeover to local power generation …).

Logic discrimination This function considerably reduces the tripping time of the circuit breakers closest to the source and may be used in closed ring networks. It applies to the the phase overcurrent 50/51, directional phase overcurrent 67, earth fault 50N/51N and directional earth fault 67N protection functions (definite time and IDMT). Blocking order Time-based discrimination Logic discrimination

Logic discrimination Blocking signals are sent during the time required to clear the fault. If the Sepam gives a tripping order, the blocking signals are interrupted after a time delay that takes into account the breaking device operating time and the protection relay reset time. This system guarantees safety in downgraded operating situations (faulty wiring or switchgear). Pilot wire test The pilot wires may be tested using the output relay test function in the SFT2841 software.

Logic discrimination Threshold assignment Threshold assignment for S80, S81 and T81 applications 1 reception and 1 send (radial network) Threshold assignment for M81, M87 and M88 applications No reception because last link in chain. Threshold assignment for S82, T82, T87, G82, G87, G88 applications 2 receptions and 2 sends (ring network, 2 parallel incomers, etc.)

Logic discrimination / 1 reception and 1 send

Logic discrimination / radial network + -- 1A 1kA inst 1A 1kA 0.2s 1B 1kA 0.5s Downstream Sepam Upstream Sepam 1 No fault / initial phase

Logic discrimination / radial network + -- 1A 1kA inst 1A 1kA 0.2s 1B 1kA 0.5s Downstream Sepam Upstream Sepam 1 Appearance of fault Blocking signal Case 1

Logic discrimination / radial network Blocking signal during opening + -- 1A 1kA inst 1A 1kA 0.2s 1B 1kA 0.5s Downstream Sepam Upstream Sepam 1 Tripping order TRIP Case 1

Logic discrimination / radial network + -- 1A 1kA inst 1A 1kA 0.2s 1B 1kA 0.5s Downstream Sepam Upstream Sepam 1 Appearance of fault Blocking signal Case 2

Logic discrimination / radial network Blocking signal during opening + -- 1A 1kA inst 1A 1kA 0.2s 1B 1kA 0.5s Downstream Sepam Upstream Sepam 1 Tripping order but problem during opening TRIP Case 2

Logic discrimination / radial network + -- 1A 1kA inst 1A 1kA 0.2s 1B 1kA 0.5s Downstream Sepam Upstream Sepam 1 Blocking signal inhibition and upstream opening Case 2 TRIP

Logic discrimination / radial network + -- 1A 1kA inst 1A 1kA 0.2s 1B 1kA 0.5s Downstream Sepam Upstream Sepam 1 Appearance of fault Blocking signal Case 3

Logic discrimination / radial network Blocking signal during opening + -- 1A 1kA inst 1A 1kA 0.2s 1B 1kA 0.5s Downstream Sepam Upstream Sepam 1 Tripping order but problem during opening TRIP Case 3

Logic discrimination / radial network + -- 1A 1kA inst 1A 1kA 0.2s 1B 1kA 0.5s Downstream Sepam Upstream Sepam 1 Inhibition problem Case 3 TRIP

Logic discrimination / radial network + -- 1A 1kA inst 1A 1kA 0.2s 1B 1kA 0.5s Downstream Sepam Upstream Sepam 1 Backup threshold order Case 3 TRIP

Logic discrimination / closed ring networks Closed ring networks may be protected by Sepam S82 or T82, which include the following functions: directional phase (67) and earth fault (67N) protection, with 2 units of each: one unit to detect faults in the "line" direction one unit to detect faults in the "busbar" direction use of 2 discrimination types: receipt of 2 blocking signals, to block the direction protection functions according to the detection direction Sending of 2 blocking signals, according to the detected fault direction

Logic discrimination / closed ring networks With the combination of directional protection functions and logic discrimination, the faulty section may be isolated with a minimal delay by tripping of the circuit breakers on either side of the fault. Blocking signals are initiated by both protection functions 67 and 67N. Priority is given to 67: when 67 and 67N detect faults in opposite directions at the same time, the blocking signal sent is determined by the direction of the fault detected by protection 67. The instantaneous output of protection function 67, activated at 80% of the Is threshold, is used to send blocking signals. This avoids uncertainty when the fault current is close to the Is threshold.