Copyright 2005 Ted "Smitty" Smith Practice Code Look Up Two Minute Drill #6.

Slides:



Advertisements
Similar presentations
FIRE PUMP ELECTRICAL CONFIGURATIONS UNDER 600 VOLTS.
Advertisements

Master Examination Practice Drill # O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded.
Master Examination Practice Drill # Ted “Smitty” Smith.
EET Survey of Electronics
E Light Electric Services, Inc © 2001 Ted “Smitty” Smith.
AGENDA INTRODUCTION CELLS AND COMPONENTS PV PERFORMANCE PV APPLICATIONS CODES AND STANDARDS EMERGENCY RESPONSE.
2014 CHANGES TWO MINUTE DRILL COPYRIGHT TED “SMITTY” SMITH ©2014.
©Ted “Smitty” Smith This speed drill focuses on calculations that will be required for the journeyman and masters examination. The question slide.
Copyright 2005 Ted "Smitty" Smith Two Minute Drill Number Three Improving your skill in code Look Up Increasing Speed Drill.
Two Minute Drill Number 32- Journeyman Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Copyright 2008 Ted "Smitty" Smith Two Minute Drill Number 25- Residential Improving your skill in code Look Up Increasing Speed Drill.
©Ted “Smitty” Smith  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead.
Two Minute Drill #8 Copyright 2005 Ted "Smitty" Smith Practice Code Look Up.
Two Minute Drill Number 26- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.
Equipment Use In Occupancies  A receptacle shall not be grouped or ganged in enclosures with other receptacles unless they are so arranged so that voltage.
Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith.
Two Minute Drill Number 27- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Calculation Speed Drill # NEC
Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1.
Copyright 2008 Ted "Smitty" Smith.  Left click on the presentation ICON located at the bottom of the slide directory to the left of the this slide. 
©Ted “Smitty” Smith This speed drill focuses on subjects that will be required for the journeyman and masters examination arranged by chapter of.
Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Two Minute Drill Number 31- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Two Minute Drill Number 22- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith Two Minute Drill Number 24- Residential.
2008 Code Drills (C) Copyright 2008 Ted "Smitty" Smith 1 Smitty’s Speed Drills.
Ag. Mechanics for Beginning Teachers
Copyright 2008 Ted "Smitty" Smith Two Minute Drill Number 21- Residential Improving your skill in code Look Up Increasing Speed Drill.
2014 NEC C ODE C HANGES C LASS P ART III C ALCULATIONS Ted “Smitty” Smith 8/15/2014 E Light Electric Services, Inc.
2014 NEC C ODE C HANGES C LASS P ART II Ted “Smitty” Smith 8/15/2014 E Light Electric Services, Inc.
HOUSE WIRING Final Review. Electricity Electricity = flow of electrons Conductor= electricity passes thru easily - Metal, water, person Insulator = restricts.
P RACTICE C ODE L OOK U P Two Minute Drill #7 Copyright 2005 Ted "Smitty" Smith.
Smitty’s Two Minute Drill Grounding
Smitty’s Two Minute Drill Grounding
Advanced Calculations Drill 1 for the 2011 NEC
License Examination Practice Drill
2011 Changes Two Minute Drill
Smitty’s Two Minute Drills
Smitty’s Two Minute Drill Overcurrent Protection
Smitty’s Two Minute Drill Mixed Content -05
Theory and Calculations
Smitty’s Two Minute Drill #9: Special Occupancies
Practice Code Look Up Two Minute Drill #7
Conductors and Cables 2017 NEC
Ampacity Calculations and Overcurrent Protection 1
Calculation Speed Drill #1
AGENDA INTRODUCTION CELLS AND COMPONENTS PV PERFORMANCE
Calculations: Transformers and Service Conductor Calculations
Smitty’s Two Minute Drill #1: Feeders and Branch Circuits
Two Minute Drill: Raceways and Boxes 2017
Smitty’s Two Minute Drill Photovoltaic Systems
2014 Changes Two Minute Drill
EET 323 – Electrical System Design Lecture 9: Grounding
Two Minute Drill Number 29- Conductors and Raceways
AGENDA INTRODUCTION CELLS AND COMPONENTS PV PERFORMANCE
Smitty’s Two Minute Drill Grounding and Bonding
Transformer Calculations: Word Problems
2008 Code Drills Health Care Facilities
Smitty’s Two Minute Drill Services, Feeders, and Branch Circuits 1
Two Minute Drill – Residential 3
Smitty’s Two Minute Drill Varied Number 7
FIRE ALARM DRILL 26 © Ted Smith 2017.
Smitty’s Two Minute Drill The BIG 5 Drill 1
Two Minute Drill – Residential 2
Calculations Review Drill
Calculation Speed Drill Varied-1
Varied Calculations Drill 2
Presentation transcript:

Copyright 2005 Ted "Smitty" Smith Practice Code Look Up Two Minute Drill #6

Copyright 2005 Ted "Smitty" Smith Directions Left click on the presentation ICON located at the bottom of the slide directory to the left of the this slide. Each slide will transition to the correct answer automatically in 2:00 minutes. The correct answer will transition in 5 seconds. Do not worry about writing down the correct answer for now. You will have the opportunity to do that at the end of the two minute drill Good luck

Further More You have seen all of these questions before. This time the slides will transition at different rates of speed. Remember do not worry about writing down the right answer for now. When you reach the end all of the slides will be repeated without the timer so you can take your time to find the ones you missed and write down the correct answers then. Copyright 2005 Ted "Smitty" Smith

Raceways LFMC shall be securely fastened in place by an approved means with in _______ inches of each box, cabinet, conduit body, or other conduit termination.

Copyright 2005 Ted "Smitty" Smith Raceways 12” (A)

Copyright 2005 Ted "Smitty" Smith Equipment Any wiring behind heating or heating panel sets located in interior walls or partitions shall be considered as operating at an ambient temperature of _______________ degrees Celsius and the ampacity shall be calculated on the basis of the correction factors given Article 310.

Copyright 2005 Ted "Smitty" Smith Equipment 40 degrees (B)

Copyright 2005 Ted "Smitty" Smith Overcurrent Protection According to Article ___________________ of the 2005 NEC, nonstandard fuses are permitted.

Copyright 2005 Ted "Smitty" Smith Overcurrent Protection True 240.6(A)

Copyright 2005 Ted "Smitty" Smith Services A cable tray may serve to carry service- entrance conductors along with other conductors as long as there is a ________.

Copyright 2005 Ted "Smitty" Smith Services Barrier Ex

Copyright 2005 Ted "Smitty" Smith Services True of False, the disconnect for a TVSS is not counted as one of the six disconnects allowed for a service.

Copyright 2005 Ted "Smitty" Smith Services True (A)

Copyright 2005 Ted "Smitty" Smith Services The service head for entrance-conductors should be located above the point of attachment but may be located elsewhere as long as the attachment is within __________ feet.

Copyright 2005 Ted "Smitty" Smith Services 2 feet (C) Ex

Copyright 2005 Ted "Smitty" Smith Grounding For multiple separately derived systems the common grounding electrode conductor shall not be smaller than __________________.

Copyright 2005 Ted "Smitty" Smith Grounding 3/0 CU or 250Kcm AL (A)(4)(a)

Copyright 2005 Ted "Smitty" Smith Raceways The minimum burial depth for a nonmetallic raceway with no vehicular traffic shall be __________________ inches.

Copyright 2005 Ted "Smitty" Smith Raceways 4" Table Col. 3

Copyright 2005 Ted "Smitty" Smith Calculations A conductor passing through a junction box with a loop length of ______________ shall be counted twice for box fill calculations.

Copyright 2005 Ted "Smitty" Smith Calculations Twice the minimum length required by Article (B)(1)

Copyright 2005 Ted "Smitty" Smith Grounding When bonding equipment, __________shall not be used for this connection and the termination shall not depend solely on__________________.

Copyright 2005 Ted "Smitty" Smith Grounding Sheet metal screws, solder 250.8

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits The size of a feeder, grounded conductor shall not be smaller than required by_________, except that _________ shall not apply where grounded conductors are run in parallel.

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits , (F) 215.2(A)

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits Where the premises wiring system has branch circuits supplied from more than one nominal voltage system, each ungrounded conductor of a branch circuit, where accessible, shall be identified by __________.

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits System 210.5(C)

Copyright 2005 Ted "Smitty" Smith Equipment Use The size of the industrial control panel supply conductor shall have an ampacity not less than ________ percent of the full load current of all resistance heating loads plus 125% of the full load current rating of the highest rated motor plus the sum of the full load current ratings of all connected motors and apparatus based on their duty cycle that may be in operation at the same time.

Copyright 2005 Ted "Smitty" Smith Equipment Use 125%

Copyright 2005 Ted "Smitty" Smith Equipment Use A ballast in a fluorescent luminaire that is used for egress lighting and energized only during a failure of the normal supply shall not have ________________.

Copyright 2005 Ted "Smitty" Smith Equipment Use Thermal Protection (E)(4)

Copyright 2005 Ted "Smitty" Smith Grounding The earth shall not be considered as an effective ground fault current path. True or False

Copyright 2005 Ted "Smitty" Smith Grounding True 250.4(A)(5)

Copyright 2005 Ted "Smitty" Smith Overcurrent Protection Can the next standard sized overcurrent protective device be used to protect tap conductors for transformer secondary conductors?

Copyright 2005 Ted "Smitty" Smith Overcurrent Protection NO (C)

Copyright 2005 Ted "Smitty" Smith Grounding All grounding electrodes as described in (A)(1) through (A)(6) that are ____________ at each building or structure served shall be bonded together to form the grounding electrode system.

Copyright 2005 Ted "Smitty" Smith Grounding Present

Copyright 2005 Ted "Smitty" Smith Equipment Use Handhold enclosure covers shall have an _____________________ that prominently identifies the function of the enclosure.

Copyright 2005 Ted "Smitty" Smith Equipment Use identifying mark or logo (D)

Copyright 2005 Ted "Smitty" Smith Conductors and Cable Assemblies Type MC cable does not have to be supported if it is not more than 2 feet long and it is being used to provide flexibility to a termination. True or False

Copyright 2005 Ted "Smitty" Smith Conductors and Cable Assemblies True (D)

Copyright 2005 Ted "Smitty" Smith Equipment Use Wiring installed in aircraft hangars in unclassified locations that are adjacent to areas in which flammable liquids or vapors are not likely to be released, such as stock rooms or electrical control rooms, which are adequately ventilated and are effectively cut off from the hangar itself by walls or partitions, shall be permitted to be of any suitable type wiring method recognized by chapter 3 of the NEC. True or False

Copyright 2005 Ted "Smitty" Smith Equipment Use True Exception to 513.7

Copyright 2005 Ted "Smitty" Smith Equipment Use A 1/2" knockout will be made in a fluorescent light fixture that will be mounted over a junction box. The light fixture will be mounted with toggle bolts. A 1/2" chase nipple will be installed so that the conductors from the box can be brought into the fixture for make up. Is this is legal installation according to the NEC?

Copyright 2005 Ted "Smitty" Smith Equipment Use No (A)

Copyright 2005 Ted "Smitty" Smith Equipment Use Is thermal protection required for the ballast of a fluorescent exit light?

Copyright 2005 Ted "Smitty" Smith Equipment Use No (E)(3)

Copyright 2005 Ted "Smitty" Smith Equipment Use The 480 volt auxiliary equipment of an electric discharge lamp is permanently installed in a luminaire and the luminaire is mounted on a pole for the illumination of a highway. What is the minimum height above the ground the auxiliary equipment must be mounted?

Copyright 2005 Ted "Smitty" Smith Equipment Use 22 ft 210.6(D)(1)(a)

Copyright 2005 Ted "Smitty" Smith Equipment Use Is the terminal of an electric discharge lamp rated in excess of 1000V considered to be a live part according to the NEC?

Copyright 2005 Ted "Smitty" Smith Equipment Use Yes (C)

Copyright 2005 Ted "Smitty" Smith Grounding Is an equipment grounding conductor required to be installed in listed metal flexible conduit that is 2 feet in length and is used only to provide flexible connection to a motor?

Copyright 2005 Ted "Smitty" Smith Grounding Yes (5)(d)

Copyright 2005 Ted "Smitty" Smith Grounding Exposed, non-current carrying, metal parts of motion picture projection equipment that is fastened in place shall be grounded regardless of voltage. True or False

Copyright 2005 Ted "Smitty" Smith Grounding True (H

Copyright 2005 Ted "Smitty" Smith Grounding Exposed, non-current carrying, metal parts of equipment that is connected by cord and plug, regardless of voltage, that is installed in non-hazardous locations shall be grounded. True or False

Copyright 2005 Ted "Smitty" Smith Grounding False (1) and (2)

Copyright 2005 Ted "Smitty" Smith Grounding The connection of a grounding electrode conductor or bonding jumper to fire-proofed structural steel shall not be required to be accessible if it is made with an irreversible compression connection. True or False

Copyright 2005 Ted "Smitty" Smith Grounding True (A) Exep. 2

Copyright 2005 Ted "Smitty" Smith Grounding A ground rod of 8 feet in length must be installed so that the connection point of the grounding electrode conductor remains accessible and above the ground. True or False

Copyright 2005 Ted "Smitty" Smith Grounding False (G) and (A) Exp. 1

Copyright 2005 Ted "Smitty" Smith Equipment Use Handhold enclosure covers shall have an _____________________ that prominently identifies the function of the enclosure.

Copyright 2005 Ted "Smitty" Smith Equipment Use identifying mark or logo (D)

Copyright 2005 Ted "Smitty" Smith Grounding The ground fault current path of the equipment grounding system is intended to return fault current back to the earth. True or False

Copyright 2005 Ted "Smitty" Smith Grounding False Back to the source

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits Where calculations result in a fraction of an ampere that is less than __________, such fractions shall be permitted to be dropped.

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits (B)

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits Outlets for heavy duty lamp holders shall be calculated at a minimum of _______ volt- amperes.

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits (E)

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits A load not less than ___________ volt amperes shall be included for each 2-wire laundry branch circuit installed as required by (C)(2).

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits (B)

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits An alternate load calculation for determine if the existing service or feeder is of sufficient capacity to serve additional loads in an existing dwelling unit is found in __________________.

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits The rules for calculating the load on fixed multi-outlet assemblies are found in _______________.

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits (H)

Copyright 2005 Ted "Smitty" Smith The End Each of the slides will now be repeated. They are not timed in this segment. To change a slide, click on the side with your left mouse button. Be sure to physically look up the answers in your code book to improve your look up speed and skill.

Copyright 2005 Ted "Smitty" Smith Raceways LFMC shall be securely fastened in place by an approved means with in _______ inches of each box, cabinet, conduit body, or other conduit termination.

Copyright 2005 Ted "Smitty" Smith Raceways 12” (A)

Copyright 2005 Ted "Smitty" Smith Equipment Any wiring behind heating or heating panel sets located in interior walls or partitions shall be considered as operating at an ambient temperature of _______________ degrees Celsius and the ampacity shall be calculated on the basis of the correction factors given Article 310.

Copyright 2005 Ted "Smitty" Smith Equipment 40 degrees (B)

Copyright 2005 Ted "Smitty" Smith Overcurrent Protection According to Article ___________________ of the 2005 NEC, nonstandard fuses are permitted.

Copyright 2005 Ted "Smitty" Smith Overcurrent Protection True 240.6(A)

Copyright 2005 Ted "Smitty" Smith Services A cable tray may serve to carry service- entrance conductors along with other conductors as long as there is a ________.

Copyright 2005 Ted "Smitty" Smith Services Barrier Ex

Copyright 2005 Ted "Smitty" Smith Services True of False, the disconnect for a TVSS is not counted as one of the six disconnects allowed for a service.

Copyright 2005 Ted "Smitty" Smith Services True (A)

Copyright 2005 Ted "Smitty" Smith Services The service head for entrance-conductors should be located above the point of attachment but may be located elsewhere as long as the attachment is within __________ feet.

Copyright 2005 Ted "Smitty" Smith Services 2 feet (C) Ex

Copyright 2005 Ted "Smitty" Smith Grounding For multiple separately derived systems the common grounding electrode conductor shall not be smaller than __________________.

Copyright 2005 Ted "Smitty" Smith Grounding 3/0 CU or 250Kcm AL (A)(4)(a)

Copyright 2005 Ted "Smitty" Smith Raceways The minimum burial depth for a nonmetallic raceway with no vehicular traffic shall be __________________ inches.

Copyright 2005 Ted "Smitty" Smith Raceways 4" Table Col. 3

Copyright 2005 Ted "Smitty" Smith Calculations A conductor passing through a junction box with a loop length of ______________ shall be counted twice for box fill calculations.

Copyright 2005 Ted "Smitty" Smith Calculations Twice the minimum length required by Article (B)(1)

Copyright 2005 Ted "Smitty" Smith Grounding When bonding equipment, __________shall not be used for this connection and the termination shall not depend solely on__________________.

Copyright 2005 Ted "Smitty" Smith Grounding Sheet metal screws, solder 250.8

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits The size of a feeder, grounded conductor shall not be smaller than required by_________, except that _________ shall not apply where grounded conductors are run in parallel.

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits , (F) 215.2(A)

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits Where the premises wiring system has branch circuits supplied from more than one nominal voltage system, each ungrounded conductor of a branch circuit, where accessible, shall be identified by __________.

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits System 210.5(C)

Copyright 2005 Ted "Smitty" Smith Equipment Use The size of the industrial control panel supply conductor shall have an ampacity not less than ________ percent of the full load current of all resistance heating loads plus 125% of the full load current rating of the highest rated motor plus the sum of the full load current ratings of all connected motors and apparatus based on their duty cycle that may be in operation at the same time.

Copyright 2005 Ted "Smitty" Smith Equipment Use 125%

Copyright 2005 Ted "Smitty" Smith Equipment Use A ballast in a fluorescent luminaire that is used for egress lighting and energized only during a failure of the normal supply shall not have ________________.

Copyright 2005 Ted "Smitty" Smith Equipment Use Thermal Protection (E)(4)

Copyright 2005 Ted "Smitty" Smith Grounding The earth shall not be considered as an effective ground fault current path. True or False

Copyright 2005 Ted "Smitty" Smith Grounding True 250.4(A)(5)

Copyright 2005 Ted "Smitty" Smith Overcurrent Protection Can the next standard sized overcurrent protective device be used to protect tap conductors for transformer secondary conductors?

Copyright 2005 Ted "Smitty" Smith Overcurrent Protection NO (C)

Copyright 2005 Ted "Smitty" Smith Grounding All grounding electrodes as described in (A)(1) through (A)(6) that are ____________ at each building or structure served shall be bonded together to form the grounding electrode system.

Copyright 2005 Ted "Smitty" Smith Grounding Present

Copyright 2005 Ted "Smitty" Smith Equipment Use Handhold enclosure covers shall have an _____________________ that prominently identifies the function of the enclosure.

Copyright 2005 Ted "Smitty" Smith Equipment Use identifying mark or logo (D)

Copyright 2005 Ted "Smitty" Smith Conductors and Cable Assemblies Type MC cable does not have to be supported if it is not more than 2 feet long and it is being used to provide flexibility to a termination. True or False

Copyright 2005 Ted "Smitty" Smith Conductors and Cable Assemblies True (D)

Copyright 2005 Ted "Smitty" Smith Equipment Use Wiring installed in aircraft hangars in unclassified locations that are adjacent to areas in which flammable liquids or vapors are not likely to be released, such as stock rooms or electrical control rooms, which are adequately ventilated and are effectively cut off from the hangar itself by walls or partitions, shall be permitted to be of any suitable type wiring method recognized by chapter 3 of the NEC. True or False

Copyright 2005 Ted "Smitty" Smith Equipment Use True Exception to 513.7

Copyright 2005 Ted "Smitty" Smith Equipment Use A 1/2" knockout will be made in a fluorescent light fixture that will be mounted over a junction box. The light fixture will be mounted with toggle bolts. A 1/2" chase nipple will be installed so that the conductors from the box can be brought into the fixture for make up. Is this is legal installation according to the NEC?

Copyright 2005 Ted "Smitty" Smith Equipment Use No (A)

Copyright 2005 Ted "Smitty" Smith Equipment Use Is thermal protection required for the ballast of a fluorescent exit light?

Copyright 2005 Ted "Smitty" Smith Equipment Use No (E)(3)

Copyright 2005 Ted "Smitty" Smith Equipment Use The 480 volt auxiliary equipment of an electric discharge lamp is permanently installed in a luminaire and the luminaire is mounted on a pole for the illumination of a highway. What is the minimum height above the ground the auxiliary equipment must be mounted?

Copyright 2005 Ted "Smitty" Smith Equipment Use 22 ft 210.6(D)(1)(a)

Copyright 2005 Ted "Smitty" Smith Equipment Use Is the terminal of an electric discharge lamp rated in excess of 1000V considered to be a live part according to the NEC?

Copyright 2005 Ted "Smitty" Smith Equipment Use Yes (C)

Copyright 2005 Ted "Smitty" Smith Grounding Is an equipment grounding conductor required to be installed in listed metal flexible conduit that is 2 feet in length and is used only to provide flexible connection to a motor?

Copyright 2005 Ted "Smitty" Smith Grounding Yes (5)(d)

Copyright 2005 Ted "Smitty" Smith Grounding Exposed, non-current carrying, metal parts of motion picture projection equipment that is fastened in place shall be grounded regardless of voltage. True or False

Copyright 2005 Ted "Smitty" Smith Grounding True (H

Copyright 2005 Ted "Smitty" Smith Grounding Exposed, non-current carrying, metal parts of equipment that is connected by cord and plug, regardless of voltage, that is installed in non-hazardous locations shall be grounded. True or False

Copyright 2005 Ted "Smitty" Smith Grounding False (1) and (2)

Copyright 2005 Ted "Smitty" Smith Grounding The connection of a grounding electrode conductor or bonding jumper to fire-proofed structural steel shall not be required to be accessible if it is made with an irreversible compression connection. True or False

Copyright 2005 Ted "Smitty" Smith Grounding True (A) Exep. 2

Copyright 2005 Ted "Smitty" Smith Grounding A ground rod of 8 feet in length must be installed so that the connection point of the grounding electrode conductor remains accessible and above the ground. True or False

Copyright 2005 Ted "Smitty" Smith Grounding False (G) and (A) Exp. 1

Copyright 2005 Ted "Smitty" Smith Equipment Use Handhold enclosure covers shall have an _____________________ that prominently identifies the function of the enclosure.

Copyright 2005 Ted "Smitty" Smith Equipment Use identifying mark or logo (D)

Copyright 2005 Ted "Smitty" Smith Grounding The ground fault current path of the equipment grounding system is intended to return fault current back to the earth. True or False

Copyright 2005 Ted "Smitty" Smith Grounding False Back to the source

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits Where calculations result in a fraction of an ampere that is less than __________, such fractions shall be permitted to be dropped.

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits (B)

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits Outlets for heavy duty lamp holders shall be calculated at a minimum of _______ volt- amperes.

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits (E)

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits A load not less than ___________ volt amperes shall be included for each 2-wire laundry branch circuit installed as required by (C)(2).

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits (B)

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits An alternate load calculation for determine if the existing service or feeder is of sufficient capacity to serve additional loads in an existing dwelling unit is found in __________________.

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits The rules for calculating the load on fixed multi-outlet assemblies are found in _______________.

Copyright 2005 Ted "Smitty" Smith Feeders and Branch Circuits (H)

Copyright 2005 Ted "Smitty" Smith The End Each of the slides will now be repeated. They are not timed in this segment. To change a slide, click on the side with your left mouse button. Be sure to physically look up the answers in your code book to improve your look up speed and skill.