1 HBD Air Cooling System TK Hemmick for the HBD group 8/25/06
2 Why is Cooling Needed? The noise debugging of the HBD showed that RF shield covers must be applied above the pre-amp cards. These covers give excellent noise performance but trap heat. The pre-amps & LDO regulators reach C. These temperatures are not a fire hazard, but they would limit the lifetime of the pre- amps. So…we designed a way to cool them.
3 How can cooling be accomplished? The covers: Block normal convention (the problem). Form a channel for air (the solution). There are 6 covers around the azimuth and 6 gaps between the covers. The gaps have sufficient room for a 3/8” tube from which to supply air. How much air? How to deliver air?
4 Overview of Information System requirements: Power load handling. Amount of air required (theory) Amount of air required (measurement) Air handling system. Pressure & Flow (theory) Pressure & flow (measurement) System parts (Prototype & Proposal) Exploded view of parts. Materials list. MSDS links.
5 Power load. One preamp card requires: +6V at 1.8 A -6V at 1.2 A 18 Watts LDO regulators on board can handle higher temp, preamps cannot. Pre-amps = +5V at 1.8 A & -5V at 1.2 A 15 Watts. Air flow should remove 15 Watts from every board.
6 Air requirements (theory) One board… 15 Watts = 15 Joules/sec. Air can be approximated well as an ideal diatomic gas (C P =7/2 R) 15 Joules in one second. Allow 20 degree rise. Requires 0.64 liters in one second. Requires ~40 l/min~80 cfh NOTE: Upper limit (ignores natural convective cooling)
7 Air requirements (measurement) One circuit card was outfitted with a small tube to spread air flow over card. Tube = 3/8” diameter, 2.5” water, 5 small holes (uniform flow w/ reasonable pressure & small holes) Pre-amp temp as a function of flow is plotted. 50 cfh is good target for cooling each board. 6 board per side = 300 cfh = 5 cfm per side.
8 Pressure and Flow (theory) P in final tube = 2.5” water P tot <0.2” water to assure uniform air delivery. F = 5 cfm, L=15” (conservative) =1.8x10 -5 Pascal x sec r = 0.26 inches (d=0.52 inches). Flow is not purely laminar… Set ID of tubing to ¾” F 5/6 F 4/6 F 3/6 F 2/6 F 1/6 F
9 Pressure & Flow (measurement-1) Assemble prototype manifold. All tubing dimensions correct. Measure air flow parameters.
10 Pressure & Flow (measurement-2) Measured parameters: 5 cfm flow. Pressure in tubes = 2.5” water. 0.1” water difference from first to last tube. 6” water is pressure at supply. Design parameters met exactly. 100% success. Air flow uniform in all holes.
11 Exploded (Prototype) Part List Tubing ¾” ID Poly-flow tubing ½” ID Latex (surgical) tubing Nylon plumbing TEE, coupling; hose barb; elbow; cap. PTEG Plastic: 3/8” nominal tubing. Link pointing to MSDS Files:
12 Example Commercial Blower… The above small (2” x 2”) commercial blower meets all the specifications for our needs. This will be evaluated and compared to other similar units. Blower selection will be discussed separately.
13 Proposed System Manifold: PVC pipe, ¾” ID, running underneath HBD cable tray. Nylon NPT 3/8”Hose Barb at 6 locations. Jumper (manifold individual tube) 3/8” latex surgical tubing. Flow tube: 3/8” ID mylar tube (0.010” thick wall) Nylon cap.