DAY 4 CHAPTER 3 CONDUCTOR SIZES,TYPES, ETC.. Continuous Load. A load where the maximum current is expected to continue for 3 hours or more. Continuous.
2014 CHANGES TWO MINUTE DRILL COPYRIGHT TED “SMITTY” SMITH ©2014.
©Ted “Smitty” Smith This speed drill focuses on calculations that will be required for the journeyman and masters examination. The question slide.
Copyright 2005 Ted "Smitty" Smith Two Minute Drill Number Three Improving your skill in code Look Up Increasing Speed Drill.
Two Minute Drill Number 32- Journeyman Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Copyright 2008 Ted "Smitty" Smith Two Minute Drill Number 25- Residential Improving your skill in code Look Up Increasing Speed Drill.
©Ted “Smitty” Smith  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead.
Two Minute Drill #8 Copyright 2005 Ted "Smitty" Smith Practice Code Look Up.
Two Minute Drill Number 26- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.
Equipment Use In Occupancies  A receptacle shall not be grouped or ganged in enclosures with other receptacles unless they are so arranged so that voltage.
Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith.
Two Minute Drill Number 27- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Calculation Speed Drill # NEC
Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1.
Copyright 2005 Ted "Smitty" Smith Practice Code Look Up Two Minute Drill #6.
©Ted “Smitty” Smith This speed drill focuses on subjects that will be required for the journeyman and masters examination arranged by chapter of.
Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Two Minute Drill Number 31- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Two Minute Drill Number 22- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith Two Minute Drill Number 24- Residential.
Speed Drill 51 Wireways and Raceways.
2008 Code Drills (C) Copyright 2008 Ted "Smitty" Smith 1 Smitty’s Speed Drills.
Ag. Mechanics for Beginning Teachers
Copyright 2008 Ted "Smitty" Smith Two Minute Drill Number 21- Residential Improving your skill in code Look Up Increasing Speed Drill.
2014 NEC C ODE C HANGES C LASS P ART III C ALCULATIONS Ted “Smitty” Smith 8/15/2014 E Light Electric Services, Inc.
2014 NEC C ODE C HANGES C LASS P ART II Ted “Smitty” Smith 8/15/2014 E Light Electric Services, Inc.
ELECTRICAL WIRING WIRING BASICS Written by Bobby Joslin
P RACTICE C ODE L OOK U P Two Minute Drill #7 Copyright 2005 Ted "Smitty" Smith.
Smitty’s Two Minute Drill Grounding
Smitty’s Two Minute Drill Grounding
Advanced Calculations Drill 1 for the 2011 NEC
License Examination Practice Drill
2011 Changes Two Minute Drill
Smitty’s Two Minute Drills
Smitty’s Two Minute Drill Overcurrent Protection
Smitty’s Two Minute Drill Mixed Content -05
Theory and Calculations
Smitty’s Two Minute Drill #9: Special Occupancies
Practice Code Look Up Two Minute Drill #7
Conductors and Cables 2017 NEC
Ampacity Calculations and Overcurrent Protection 1
Calculation Speed Drill #1
Calculations: Transformers and Service Conductor Calculations
Smitty’s Two Minute Drill #1: Feeders and Branch Circuits
Two Minute Drill: Raceways and Boxes 2017
Smitty’s Two Minute Drill Photovoltaic Systems
2014 Changes Two Minute Drill
Two Minute Drill Number 29- Conductors and Raceways
Smitty’s Two Minute Drill Grounding and Bonding
Transformer Calculations: Word Problems
2008 Code Drills Health Care Facilities
Smitty’s Two Minute Drill Services, Feeders, and Branch Circuits 1
Load Calculation Speed Drill
Two Minute Drill – Residential 3
Smitty’s Two Minute Drill Varied Number 7
Smitty’s Two Minute Drill General Knowledge
Smitty’s Two Minute Drill The BIG 5 Drill 1
Two Minute Drill – Residential 2
Smitty’s Two Minute Drill General Knowledge 2
Calculations Review Drill
Cooking , Electric Dryer and Appliance Calculations 3
Calculation Speed Drill Varied-1
Varied Calculations Drill 2
Presentation transcript:

Copyright 2008 Ted "Smitty" Smith

 Left click on the presentation ICON located at the bottom of the slide directory to the left of the this slide.  Each slide will transition to the correct answer automatically in 2:00 minutes. The correct answer will transition in 10 seconds. You may also left click on the slide to manually transition.  Do not worry about writing down the correct answer for now. You will have the opportunity to do that at the end of the two minute drill  Good luck  Remember to start the slide show to activate the timer. Copyright 2005 Ted "Smitty" Smith

 This drill is a mixture of calculations and code look up questions. You have seen many of them before. Focus on time. Try to find all the answers before the slide transitions.  Remember do not worry about writing down the right answer for now. When you reach the end all of the slides will be repeated without the timer so you can take your time to find the ones you missed and write down the correct answers then.  Click on the slide to proceed. Copyright 2005 Ted "Smitty" Smith

1. Equipment grounding conductors shall be permitted to be sectioned within a listed multiconductor cable, provided the combined _______________ complies with A. Current and load B. Voltages of all applied loads C. Circular mill area D. None of the above Copyright 2008 Ted "Smitty" Smith

 Circular mill area  Copyright 2005 Ted "Smitty" Smith

 A conductor with insulation marked ZW will be suitable for use in all:  Wet locations  Hospital operating rooms  House boats  None of the above Copyright 2005 Ted "Smitty" Smith

 Wet locations  Table (A) Copyright 2005 Ted "Smitty" Smith

 Where more than one calculated or ____________ ampacity could apply for a given circuit, the lowest value shall be used.  Determined  Tabulated  Corrected  Derated Copyright 2005 Ted "Smitty" Smith

 Tabulated (A)(2) Copyright 2005 Ted "Smitty" Smith

 Where bare or covered conductors are installed with insulated conductors, the temperature rating of the bare or covered conductor shall be _____________ for the purpose of determining ampacity  Equal to the lowest temperature rating of the insulated conductors  Equal to the highest temperature rating of the insulated conductors  Equal to the average temperature ratings of the insulated conductors.  None of the above Copyright 2005 Ted "Smitty" Smith

 Equal to the lowest temperature rating of the insulated conductors  (B)(3) Copyright 2005 Ted "Smitty" Smith

 A 2 AWG TW conductor is installed in a location where the ambient temperature is expected to be 108 degrees F. The temperature correction factor for conductor ampacity in this location is _________. .96 .88 .82 .71 Copyright 2005 Ted "Smitty" Smith

.71  Table Bottom, 60c wire at 102 degrees F.  I recommend using a straight edge when using NEC tables. A clear plastic 6 inch ruler is best. Copyright 2005 Ted "Smitty" Smith

 If the ambient temperature is 30 degrees C, the minimum insulation that a conductor must have and still have the capacity to carry current is __________  60 C  105 C  90 C  Any of these Copyright 2008 Ted "Smitty" Smith

 Any of these  All of these conductors are rated for 30 degrees C Copyright 2005 Ted "Smitty" Smith

 Determine the minimum sized THHN aluminum conductor that can be installed to feed a load of 104 amperes that is located in a freezer that has an ambient temperature of 22 degrees Celsius.  1 AWG  2 AWG  3 AWG  1/0 AWG Copyright 2008 Ted "Smitty" Smith

 100 A 1/0 AWG  (c) will require you handle 104 amperes in the 75 C column, so another two wire sizes will be required, therefore 1/0. Copyright 2005 Ted "Smitty" Smith

 The ampacity of six-current carrying 10 AWG RHW aluminum conductors in a raceway in an ambient temperature of 75 degrees F is ___________ › 30A › 22A › 16A › 12A Copyright 2005 Ted "Smitty" Smith

 15.75A  Table and (B)(2)(a) Copyright 2005 Ted "Smitty" Smith

 The ampacity of nine current carrying 10 AWG THW conductors installed in a 20 inch long raceway is _________. › 25A › 30A › 35A › None of these Copyright 2005 Ted "Smitty" Smith

 35A  Bundle factors do not apply to raceways that are 24 inches in length or less. Copyright 2005 Ted "Smitty" Smith

 Enclosures for switches or over current devices shall not be used as junction boxes, auxiliary gutters, or raceways for conductors feeding through or tapping off to other switches or over current devices, unless adequate space for this purpose is provided. The conductors shall not fill the wiring space at any cross section to more than _______ percent of the cross-sectional area of the space. › 20 › 25 › 35 › 40 Copyright 2005 Ted "Smitty" Smith

 40  Copyright 2005 Ted "Smitty" Smith

 What is the area in square inches for a 14 AWG RHW without outer covering conductor? › › › › Copyright 2005 Ted "Smitty" Smith

  Table 5, Chapter 9 Copyright 2005 Ted "Smitty" Smith

 What is the cross sectional area in square inches for 12 AWG RHH with outer covering conductors? › › › › Copyright 2005 Ted "Smitty" Smith

  Table 5, Chapter 9 Copyright 2005 Ted "Smitty" Smith

 A 200A feeder installed in Schedule 80 rigid non-metallic conduit has three 3/0 AWG THHN, one 2 AWG THHN and one 6 AWG THHN conductors. What is the minimum sized raceway required?  2 inch  2.5 inch  3 inch  3.5 inch Copyright 2005 Ted "Smitty" Smith

 2 inch Copyright 2005 Ted "Smitty" Smith

 What size rigid metal nipple is required for three 4/0 AWG THHN, one 1/0 AWG THHN and one 4 AWG THHN conductors?  1.5 inch  2 inch  2.5 inch  None of these Copyright 2005 Ted "Smitty" Smith

 1.5 inch   60% fill based on note 4 to Table 1 Copyright 2005 Ted "Smitty" Smith

 What size outlet box is required for one 12/2 NM cable that terminates on a switch, on 12/3 NM cable that terminates on a receptacle, and the box has manufactured internal cable clamps. › 4 x 1 1/4 square › 4 x 1 1/2 square › 4 x 2 1/8 square › None of these Copyright 2005 Ted "Smitty" Smith

 4 x 2 1/8 Square Copyright 2005 Ted "Smitty" Smith

 Machine screw type fasteners that engage not less than two and thread forming machine screws that engage not less than two threads in the enclosure may be used to mount equipment grounding bars, buses and lugs to enclosures. › True › False Copyright 2005 Ted "Smitty" Smith

 True  Copyright 2005 Ted "Smitty" Smith

 What is the net computed demand load for the air conditioning and heat for a 40 unit multifamily building that has an air conditioner ( 3hp, 3.91 kW 230V) and two baseboard heaters (3 kW) in each unit. › 160 kW › 240 kW › 6 kW › 5 kW Copyright 2005 Ted "Smitty" Smith

 240 kW  Heat is larger load than A/C Copyright 2005 Ted "Smitty" Smith

 What is the demand load on the main service entrance of an apartment complex that is supplied with a 120/208V single phase service for twelve 3.25 kW ovens?  10 kW  18 kW  15 kW  20 kW Copyright 2005 Ted "Smitty" Smith

 18 kW Copyright 2005 Ted "Smitty" Smith

 What is the general lighting load for a dwelling unit with 2,700 square feet of living space not including open porches, garages, or unused or unfinished spaces not adaptable for future use? › 8100 VA › VA › 2700 VA › 6480 VA Copyright 2005 Ted "Smitty" Smith

 8100 VA Copyright 2005 Ted "Smitty" Smith

 What is the feeder or service demand for two 3 kW ranges? › 3 kW › 4.8 kW › 4.5 kW › 3.9 kW Copyright 2005 Ted "Smitty" Smith

 4.5 kW Copyright 2005 Ted "Smitty" Smith

 If the total demand is 30 kW for a 120/240V dwelling unit, what is the minimum sized service and feeder copper conductor size allowed?  4 AWG  3/0 AWG  2 AWG  1/0 AWG Copyright 2005 Ted "Smitty" Smith

 2 AWG  30,000/240= 125A  Table (B)(6) shows 2 AWG copper for 125A services Copyright 2005 Ted "Smitty" Smith

 What is the demand on the main service entrance of a single family dwelling of a range with a nameplate rating of 13.9 kVA at 240 volts? › 8000 VA › 8800 VA › 9600 VA › VA Copyright 2005 Ted "Smitty" Smith

 8800 VA Table Note 1 Copyright 2005 Ted "Smitty" Smith

 The disconnecting means for surge protective devices shall not be considered a disconnecting means when determining the maximum number of handles for the service disconnecting means.  True  False Copyright 2005 Ted "Smitty" Smith

 True  (A)(2) Copyright 2005 Ted "Smitty" Smith

 Metal enclosures and raceways for service conductors and equipment shall be connected to the _______________ system conductor if the electrical system is grounded or to the ________________ conductor for electrical systems that are not grounded.  Grounded/ ungrounded  Grounded/ grounding electrode  Grounding/ grounded  None of the above Copyright 2005 Ted "Smitty" Smith

 Grounded/ Grounding electrode  Copyright 2005 Ted "Smitty" Smith

Each of the slides will now be repeated. They are not timed in this segment. To change a slide, click on the side with your left mouse button. Be sure to physically look up the answers in your code book to improve your look up speed and skill. Copyright 2005 Ted "Smitty" Smith

1. Equipment grounding conductors shall be permitted to be sectioned within a listed multiconductor cable, provided the combined _______________ complies with A. Current and load B. Voltages of all applied loads C. Circular mill area D. None of the above Copyright 2008 Ted "Smitty" Smith

 Circular mill area  Copyright 2005 Ted "Smitty" Smith

 A conductor with insulation marked ZW will be suitable for use in all:  Wet locations  Hospital operating rooms  House boats  None of the above Copyright 2005 Ted "Smitty" Smith

 Wet locations  Table (A) Copyright 2005 Ted "Smitty" Smith

 Where more than one calculated or ____________ ampacity could apply for a given circuit, the lowest value shall be used.  Determined  Tabulated  Corrected  Derated Copyright 2005 Ted "Smitty" Smith

 Tabulated (A)(2) Copyright 2005 Ted "Smitty" Smith

 Where bare or covered conductors are installed with insulated conductors, the temperature rating of the bare or covered conductor shall be _____________ for the purpose of determining ampacity  Equal to the lowest temperature rating of the insulated conductors  Equal to the highest temperature rating of the insulated conductors  Equal to the average temperature ratings of the insulated conductors.  None of the above Copyright 2005 Ted "Smitty" Smith

 Equal to the lowest temperature rating of the insulated conductors  (B)(3) Copyright 2005 Ted "Smitty" Smith

 A 2 AWG TW conductor is installed in a location where the ambient temperature is expected to be 108 degrees F. The temperature correction factor for conductor ampacity in this location is _________. .96 .88 .82 .71 Copyright 2005 Ted "Smitty" Smith

.71  Table Bottom, 60c wire at 102 degrees F.  I recommend using a straight edge when using NEC tables. A clear plastic 6 inch ruler is best. Copyright 2005 Ted "Smitty" Smith

 If the ambient temperature is 30 degrees C, the minimum insulation that a conductor must have and still have the capacity to carry current is __________  60 C  105 C  90 C  Any of these Copyright 2008 Ted "Smitty" Smith

 Any of these  All of these conductors are rated for 30 degrees C Copyright 2005 Ted "Smitty" Smith

 Determine the minimum sized THHN aluminum conductor that can be installed to feed a load of 104 amperes that is located in a freezer that has an ambient temperature of 22 degrees Celsius.  1 AWG  2 AWG  3 AWG  1/0 AWG Copyright 2008 Ted "Smitty" Smith

 100 A 1/0 AWG  (c) will require you handle 104 amperes in the 75 C column, so another two wire sizes will be required, therefore 1/0. Copyright 2005 Ted "Smitty" Smith

 The ampacity of six-current carrying 10 AWG RHW aluminum conductors in a raceway in an ambient temperature of 75 degrees F is ___________ › 30A › 22A › 16A › 12A Copyright 2005 Ted "Smitty" Smith

 15.75A  Table and (B)(2)(a) Copyright 2005 Ted "Smitty" Smith

 The ampacity of nine current carrying 10 AWG THW conductors installed in a 20 inch long raceway is _________. › 25A › 30A › 35A › None of these Copyright 2005 Ted "Smitty" Smith

 35A  Bundle factors do not apply to raceways that are 24 inches in length or less. Copyright 2005 Ted "Smitty" Smith

 Enclosures for switches or over current devices shall not be used as junction boxes, auxiliary gutters, or raceways for conductors feeding through or tapping off to other switches or over current devices, unless adequate space for this purpose is provided. The conductors shall not fill the wiring space at any cross section to more than _______ percent of the cross-sectional area of the space. › 20 › 25 › 35 › 40 Copyright 2005 Ted "Smitty" Smith

 40  Copyright 2005 Ted "Smitty" Smith

 What is the area in square inches for a 14 AWG RHW without outer covering conductor? › › › › Copyright 2005 Ted "Smitty" Smith

  Table 5, Chapter 9 Copyright 2005 Ted "Smitty" Smith

 What is the cross sectional area in square inches for 12 AWG RHH with outer covering conductors? › › › › Copyright 2005 Ted "Smitty" Smith

  Table 5, Chapter 9 Copyright 2005 Ted "Smitty" Smith

 A 200A feeder installed in Schedule 80 rigid non-metallic conduit has three 3/0 AWG THHN, one 2 AWG THHN and one 6 AWG THHN conductors. What is the minimum sized raceway required?  2 inch  2.5 inch  3 inch  3.5 inch Copyright 2005 Ted "Smitty" Smith

 2 inch Copyright 2005 Ted "Smitty" Smith

 What size rigid metal nipple is required for three 4/0 AWG THHN, one 1/0 AWG THHN and one 4 AWG THHN conductors?  1.5 inch  2 inch  2.5 inch  None of these Copyright 2005 Ted "Smitty" Smith

 1.5 inch   60% fill based on note 4 to Table 1 Copyright 2005 Ted "Smitty" Smith

 What size outlet box is required for one 12/2 NM cable that terminates on a switch, on 12/3 NM cable that terminates on a receptacle, and the box has manufactured internal cable clamps. › 4 x 1 1/4 square › 4 x 1 1/2 square › 4 x 2 1/8 square › None of these Copyright 2005 Ted "Smitty" Smith

 4 x 2 1/8 Square Copyright 2005 Ted "Smitty" Smith

 Machine screw type fasteners that engage not less than two and thread forming machine screws that engage not less than two threads in the enclosure may be used to mount equipment grounding bars, buses and lugs to enclosures. › True › False Copyright 2005 Ted "Smitty" Smith

 True  Copyright 2005 Ted "Smitty" Smith

 What is the net computed demand load for the air conditioning and heat for a 40 unit multifamily building that has an air conditioner ( 3hp, 3.91 kW 230V) and two baseboard heaters (3 kW) in each unit. › 160 kW › 240 kW › 6 kW › 5 kW Copyright 2005 Ted "Smitty" Smith

 240 kW  Heat is larger load than A/C Copyright 2005 Ted "Smitty" Smith

 What is the demand load on the main service entrance of an apartment complex that is supplied with a 120/208V single phase service for twelve 3.25 kW ovens?  10 kW  18 kW  15 kW  20 kW Copyright 2005 Ted "Smitty" Smith

 18 kW Copyright 2005 Ted "Smitty" Smith

 What is the general lighting load for a dwelling unit with 2,700 square feet of living space not including open porches, garages, or unused or unfinished spaces not adaptable for future use? › 8100 VA › VA › 2700 VA › 6480 VA Copyright 2005 Ted "Smitty" Smith

 8100 VA Copyright 2005 Ted "Smitty" Smith

 What is the feeder or service demand for two 3 kW ranges? › 3 kW › 4.8 kW › 4.5 kW › 3.9 kW Copyright 2005 Ted "Smitty" Smith

 4.5 kW Copyright 2005 Ted "Smitty" Smith

 If the total demand is 30 kW for a 120/240V dwelling unit, what is the minimum sized service and feeder copper conductor size allowed?  4 AWG  3/0 AWG  2 AWG  1/0 AWG Copyright 2005 Ted "Smitty" Smith

 2 AWG  30,000/240= 125A  Table (B)(6) shows 2 AWG copper for 125A services Copyright 2005 Ted "Smitty" Smith

 What is the demand on the main service entrance of a single family dwelling of a range with a nameplate rating of 13.9 kVA at 240 volts? › 8000 VA › 8800 VA › 9600 VA › VA Copyright 2005 Ted "Smitty" Smith

 8800 VA Table Note 1 Copyright 2005 Ted "Smitty" Smith

 The disconnecting means for surge protective devices shall not be considered a disconnecting means when determining the maximum number of handles for the service disconnecting means.  True  False Copyright 2005 Ted "Smitty" Smith

 True  (A)(2) Copyright 2005 Ted "Smitty" Smith

 Metal enclosures and raceways for service conductors and equipment shall be connected to the _______________ system conductor if the electrical system is grounded or to the ________________ conductor for electrical systems that are not grounded.  Grounded/ ungrounded  Grounded/ grounding electrode  Grounding/ grounded  None of the above Copyright 2005 Ted "Smitty" Smith

 Grounded/ Grounding electrode  Copyright 2005 Ted "Smitty" Smith