February 8th 2008ATC/ABOC session 5 - summing up 1 ATC/ABOC Days Summary Session 5 MTTR & Spare Policy: TS Groups.

Slides:



Advertisements
Similar presentations
KPI Familiarisation.
Advertisements

Software Quality Assurance Plan
Long shutdown 2013: Electrical distribution activities 09/03/2012 IEFC 2012 Workshop F. Duval on Behalf of EN/EL group.
Intervention Priority Management This talk will show the CERN priority list, the corresponding check list and the tools used by operators to diagnose a.
LHC UPS Systems and Configurations: Changes during the LS1 V. Chareyre / EN-EL LHC Beam Operation Committee 11 February 2014 EDMS No /02/2014.
Information about system status Piquet backup call Supervision of fire alarm systems Control room backup Computer support for HCI’s/terminals Confirmation.
PowerCare Customer Support Agreement LP Products and Systems 2013 PM.
MSIS 110: Introduction to Computers; Instructor: S. Mathiyalakan1 Systems Design, Implementation, Maintenance, and Review Chapter 13.
Computer Security: Principles and Practice
DITSCAP Phase 2 - Verification Pramod Jampala Christopher Swenson.
MFI Office Maintenance Management Project Presentation 30th of May
Christophe Delamare EDMS Accelerator Consolidation Workshop GS/ASE activities.
D. Bozzini, EN-EL-HT, ATOP Days 2009, 4-6 March ELECTRICAL NETWORK: 18 KV NETWORK REVIEW AND STATUS OF THE SPS CONSOLIDATION PLAN D. Bozzini on.
Maintenance Specificities in the CERN Cooling and Ventilation Group Asset and Maintenance Management Workshop CERN, November 2013 I. El Hardouz,
1 EL Consolidation IEFC Workshop F. Duval on behalf of EN/EL
Consolidation of access systems for the injector Complex ATOP days 4-6 March 2009 P. Ninin & R, Nunes in behalf of the PS and SPS access project teams…
Principles of Information Systems, Sixth Edition Systems Design, Implementation, Maintenance, and Review Chapter 13.
112/09/2013. Summary  Events on the network  Incidents  Network reconfigurations  Network operation  Update on activities  Tests  Projects and.
Review of the Project for the Consolidation and Upgrade of the CERN Electrical Distribution System October 24-26, 2012 THE HIGH-VOLTAGE NETWORK OF CERN.
LHC ACCESS SYSTEM 1Authors: P, Ninin, S. Grau & LHC access team EDMS: Access System during the LHC Injection tests P. Ninin, S. Grau - TS/CSE Workshop.
LHC Access System August 2006 LHC Access System – Status and Planning August 2006 Elena Manola-Poggioli Eva Sanchez-Corral TS-CSE on behalf of the LHC.
LS1 : EL Upgrades & Consolidation Chamonix– February 8 th 2012 F. Duval on behalf of EN/EL The goal of LS1 is to implement everything needed for a safe.
Christophe Mugnier, on behalf AB/PO Group ATC-ABOC days, 23 January 2008 AB/PO equipment review and Stand-by service description for the power converter.
Life cycle services for automation products
Corporate Technical Infrastructure Management From MP5 to a Corporate Technical Infrastructure Management System.
Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.
An overview of current & future functionality David Widegren TS/ASE/EPS 23 February 2008EDMS:
12/8/2015PLC Software Configuration WG - CCB1 PLC Software Configuration WG Members Philippe Gayet Fréderic Havart Renaud Barillère [Mathias Dutour]
Safety Commission databases support TS/CSE 1 EDMS TS Workshop 2005 SAFETY COMMISSION DATABASE SUPPORT Presented at the TS Workshop 24 th May 2005 S. Petit,
Utility Engineers, PC.  Generation  Transmission  Distribution.
CMS Proposal for a Maintenance & Operation agreement with EN/CV/DC for fluorocarbon detector cooling circuits v.2 P. Tropea For the CMS experiment.
Principles of Information Systems, Sixth Edition 1 Systems Design, Implementation, Maintenance, and Review Chapter 13.
ATC/ABOC 23 January 2008Session 5 / MTTR and spare parts Review of MTTR and spares parts policy in TS-EL F. Rodriguez-Mateos.
J. Pedersen, ST/EL Consolidation of the CERN technical infrastructure and civil engineering. J. Pedersen ST 6 th ST workshop, Thoiry, 1 – 3 April 2003.
Static Var Compensator Status (SVCs for Booster and SPS) Situation in 2009 Karsten KAHLE, TE-EPC ATOP days March 2009.
CERN General Infrastructure Services Department CERN GS Department CH-1211 Geneva 23 Switzerland Db Futures Workshop
Overview of the main events related to TS equipment during 2007 Definition Number and category of the events Events and measures taken for each machine.
ABOC/ATC days Electrical Network: Selectivity and Protection Plan José Carlos GASCON TS–EL Group 22 January 2007.
Erman Taşkın. Information security aspects of business continuity management Objective: To counteract interruptions to business activities and to protect.
Consolidation needs for the Electrical Distribution, Control Cables and Optical Fibres Equipment F. Duval.
EDMS Session 2 - Operation at high intensity of the CERN machines ATC/ABOC 21 January ARCON – RAMSES Bridge ATC/ABOC Days CERN – 21 to 23.
Quality assurance - documentation and diagnostics during interventions Corrective maintenance seen from the Technical Infrastructure operation Peter Sollander,
ATC/ABOC 23 January 2008Session 5 / MTTR & Spare parts 1 MTTR and Spare Parts in TS/ASE Rui NUNES TS-ASE.
AB/CO Review, Interlock team, 20 th September Interlock team – the AB/CO point of view M.Zerlauth, R.Harrison Powering Interlocks A common task.
TS workshop 2004U. Epting, M.C. Morodo Testa - TS department1 Improving Industrial Process Control Systems Security Uwe Epting (TS/CSE) Maria Carmen Morodo.
SAFETY SERVICES PROVISION I. Bejar Alonso. Transfer Executive Safety Tasks from SC to Departments In application of the document “Safety policy at CERN”
Conclusions on UPS powering test and procedure I. Romera Acknowledgements: V. Chareyre, M. Zerlauth 86 th MPP meeting –
ATC / ABOC 23 January 2008SESSION 6 / MTTR and Spare Parts AB / RF GROUP MTTR, SPARE PARTS AND STAND-BY POLICY FOR RF EQUIPMENTS C. Rossi on behalf of.
TE-CRG Activities D. Delikaris, TE-CRG.
Product Lifecycle Management with the CERN EDMS David Widegren CERN, TS/CSE 8 Nov 2005EDMS:
Anytime, Anywhere Access Benefits Functionality Work Order Administration Dispatch Work Order Work Order Details New Work Order Additional Functionality.
C. Mugnier, D. Lafarge, C. Perolini, R. Pilon, J. Ruiz-Cabezas
CV works in the non- LHC accelerator complex during 2008 and plans for 2009 ATOP days 2009.
Computer Security: Principles and Practice First Edition by William Stallings and Lawrie Brown Lecture slides by Lawrie Brown Chapter 17 – IT Security.
YETS & LS2 Works EN-EL / Power distribution
Situation of the Static Var Compensators at CERN.
Technical Services: Unavailability Root Causes, Strategy and Limitations Data and presentation in collaboration with Ronan LEDRU and Luigi SERIO.
ARIES WP 6 / Task September 2017
Performance monitoring framework for the technical infrastructure
YETS & LS2 Works EN-El on LHC / Power distribution
the high-voltage network of CERN ToMORROW
Quality Assurance applied to Accelerator Safety
Renovation of the 45-year old PS magnets
the CERN Electrical network protection system
Lecture 6. Information systems
YETS & LS2 Works EN-EL / Power distribution
Managing infrastructure faults to minimize accelerator down time
KPI Familiarisation
Infor EAM in the Handling Engineering Group at CERN
ILO Industrial Opportunities Days, 6-7 June 2019
Presentation transcript:

February 8th 2008ATC/ABOC session 5 - summing up 1 ATC/ABOC Days Summary Session 5 MTTR & Spare Policy: TS Groups

ATC/ABOC session 5 - summing up 2 February 8th 2008 Talks session 5 TS/EL by Felix Rodriguez Mateos TS/CV by Joaquin Inigo Golfin TS/ASE by Rui Nunes AB/ABP by Richard Scrivens (summing up presented by S.Myers) Maintenance management with D7i by David Widegren

ATC/ABOC session 5 - summing up 3 February 8th 2008 TS/EL F. Rodriguez-Mateos 1/5 Design principles for minimizing MTTR Design principles for minimizing MTTR Re-powering by reconfiguration of the network. n+1 redundancy.  400kV power transformers and breakers, SVCs in BE, most of the cables in SPS, 18 kV inter-site links, 48V safety control systems Repair/replacement of equipment there where no n+1 redundancy exists  Transformers, many UPS, HV and LV breakers, the SVC for the LHC even points and Meyrin site, filters, capacitors, PLC, etc… Single point failures (a few examples)  Incoming 400 kV line, 38 MVA Transformers, 66kV Cables, 18 kV Cables for the pulsed BE-BA4 link, Bus bar failures in HV or LV switchboards

ATC/ABOC session 5 - summing up 4 February 8th 2008 TS/EL F. Rodriguez-Mateos 2/5 YearMCHF/y 20011, Evolution of the maintenance budget

ATC/ABOC session 5 - summing up 5 February 8th 2008 TS/EL F. Rodriguez-Mateos 3/5 Spares  Transformers – No spares, consolidation studies, gentlemen agreement with RTE Existing 110 MVA x 2, 90 MVA x 3, 70 MVA x 2, 38 MVA x 5 A single failure of 110 MVA, 90 MVA or 70 MVA can be remedied by re-configuration A double failure would compromise CERN’s mission for approximately 2 years Single failure of any 38 MVA transformer stops the LHC operation for 2 years (see EDMS ) Distribution transformers – spares for some types

ATC/ABOC session 5 - summing up 6 February 8th 2008 TS/EL F. Rodriguez-Mateos 4/5 Spares exist for  HV breakers – Spare parts, not spare units  SVCs – SVC3 in operation week 6, SVC1 “hot spare”  Harmonic filters  ENS (control system)  48V DC power supplies  UPS Hot stand-by UPS systems required for LHC

ATC/ABOC session 5 - summing up 7 February 8th 2008 SPS 18kV Cables: strategy 5/5 Replacing all cables is too costly (15 MCHF)  Consolidation includes BA6-BA7 plus one additional equivalent length (total of 2 MCHF) We have to get re-powering redundancy everywhere => consolidation for BA4 urgent, foreseen end of 2008 TTR a faulty cable varies from 1 week to 1 month  Many variability factors (location, weather, access rights to locations,…)  In the meantime, operation in open loop configuration  Double faults kill this possibility, low probability which will increase with time… 30% of the cables have been replaced in SPS loops, none for the SMB cables BA6-BA7 can be used as a “pilot programme” for the future procedure  Cables will be laid within PVC pipes A new procedure “Guide pour la réparation des câbles du SPS” has been prepared, will soon be published

ATC/ABOC session 5 - summing up 8 February 8th 2008 TS/CV J. Inigo-Golfin 1/7 N+1 principle  Should not be tampered with (for savings)  Where reasonably possible (i.e. not for towers) Many different installations  Analysis of major events show no trend in faults Ventilation is not a safety system Legionella risk  Not only CV, but also user problem (no flow)

ATC/ABOC session 5 - summing up 9 February 8th 2008 Major Event Summary – Charts 2/7

ATC/ABOC session 5 - summing up 10 February 8th 2008 Major events for injectors chain: Summary 3/7 In the last 3 years 27 major events, with:  total time = 120 hr, (MTTR = 4.4) Many isolated cases which do not fall easily into any large category:  even those falling within the same category have little resemblance (lack of maintenance, aging equipment)  new category with radiation damage!

ATC/ABOC session 5 - summing up 11 February 8th 2008

ATC/ABOC session 5 - summing up 12 February 8th 2008 Organisation of CV Stand-by service 5/7  Who intervenes? One team (two people) per zone (LHC, SPS, PS) PS & SPS at the charge of maintenance contractors LHC and 513 in charge of CV staff  How are teams contacted? Stand by phone number available in CCC Contacted mainly by CCC  Interventions timescale? Contractual obligation to arrive on site within 15 min. during working hours 45 min. outside working hours Diagnosis and troubleshooting within 1 h after arrival If no solution is found, escalation procedure  Factors external to CV that could influence MTTR Procedure for intervention in the vicinity of asbestos Procedure for Radio Protection or confined spaces, special access procedures Procedure for interventions in SPS in the vicinity of electrical equipment not defined. “Consignation” Environmental factors (legionella) may require stop of plants

ATC/ABOC session 5 - summing up 13 February 8th 2008 CV spare parts 6/7  D7i contains at present information on : List of spare parts available in the CV stores 70% of process components have their associated spare parts defined Four different CV stores totaling 5130 m2, containing referenced parts of these parts available on-site  Foreseen in the mid term: Determine key spares for critical equipment (defined as single point of failure, not following the N+1 general rule) Determine and buy minimum stock of spares Create a list of process control spare parts (common with other services)  Mostly relevant for Preventive maintenance. Troubleshooting based on N+1 redundancy policy  Yearly stores activity: 4800 parts for 1.2 MCHF (bought, accepted, stored and dispatched) 44 shipping for repairs organized 1 person only for this activity as from Jan. 1 st 2008

ATC/ABOC session 5 - summing up 14 February 8th 2008 CV conclusions 7/7 The analysis of the major events shows little repeatability in the breakdowns. Around 1/3 of breakdowns with Physics loss is linked to equipment, rest of stops due to accidental or unauthorised manipulation of the CV systems. Room for improvement A comparison between the major events and the numbers of calls from CCC shows that most of the breakdowns and events do not stop the accelerators Major effort done to improve the TS/CV policy to reduce MTTR mainly through stand- by duty training The spare part management cannot be underestimated, for rapid reaction in interventions Effort underway in the identification of critical elements and provision of compensatory measures (replacement equipment or consolidation) Experience indicate, that spares play a limited role in the reduction of MTTR. Most stand-by actions consist in troubleshooting, (N+1 warm stand-by policy). Repairs in hidden time

ATC/ABOC session 5 - summing up 15 February 8th 2008 TS/ASE -- R. Nunes Safety and access systems  Safety systems  no beam interlock  Access systems  beam interlock Maintenance  External contractors including on-call service Spares  Safety systems – standard equipment, spares exist  Access systems – custom equipment, no spares to buy (PS,SPS) Dependencies – Controls  Substantial effort to keep computing environment up to date with latest patches  Safety and access system dependent on Technical Network Consolidation – Equipment should be renewed by 5% per year  As it is not, urgent and expensive consolidation works on failure

ATC/ABOC session 5 - summing up 16 February 8th Consolidation projects to be started 1. PS primary access (to be started ASAP)  Awaiting functional specs/requirements from AB  We TS-ASE remain available to advise and guide the technical issues 2. PS & SPS ZORA Video & intercom renewal  Service transferred from IT/CS in 2007  To migrate to VideoOverIP due to total obsolescence 3. SPS primary access  To be started imediately after PS  Structure very similar to LHC 4. SPS secondary acces Structure identical to PS primary areas that is functional and working since 1 year now. 5. SPS fire detection consolidation Complete revision of the SPS underground shall be needed to insure performance

ATC/ABOC session 5 - summing up 17 February 8th Conclusion ASE deals with Safety & Security Systems  Maintenance and Consolidation of these systems are strategic for the operation of the machines and for personnel safety Maintenance via external contractors allows CERN to optimise internal resources for “core” issues However these systems are evolving in technology and require an evolving competence in controls and computing  Networks, automation, databases and SCADA Better usage of tools (such as D7i) are needed in order to obtain more significant statistics and KPI (key performance indicators)  This gives better fundamentals for consolidation activities  Would be useful that AB/OP logbook refers to specific categories to help the ASE maintenance teams to track OP problems Homogenisation of Access systems is fundamental for improving the quality of the maintenance service and reducing the impact on operation of machines

ATC/ABOC session 5 - summing up 18 February 8th 2008 DataStream 7i – D. Widegren Maintenance Management system at CERN for 20+ years Used in many groups  TS equipment groups, AT/ACR, AT/ECR, via MTF in TS,AB,AT,PH and SC departments  A large part of LHC equipment already in D7i through MTF Over one million equipment in D7i at CERN Oracle database with native and in-house web interfaces

ATC/ABOC session 5 - summing up 19 February 8th 2008 D7i and MTF D7i is the CMMS at CERN but it is also the foundation of the MTF application, which has been used for the manufacturing, installation and commissioning follow-up of LHC. This means that all equipment registered and followed-up with MTF are already registered in D7i and ready to benefit from the available maintenance management functionality. A complete equipment lifecycle follow-up can be provided – if required! Manufacturing Installation & Commissioning Operation & MaintenanceDismantling MTF Datastream 7i User interfaces: Project phases: …? Underlying system: Datastream 7i

ATC/ABOC session 5 - summing up 20 February 8th 2008 D7i Asset management  Associate technical characteristics with equipment, describe hierarchical relationships, log meter readings, historical tracking, … Work management  Preventive and corrective maintenance, work orders, diagnostics, material and task listings, Analysing performance  Maintenance costs, MTTR, MTBF, … Spare parts management  Allocates materials to work orders, identifies materials that needs purchasing according to current stock level, … Reporting  Many (100+) reports available, direct Oracle interface for users available

ATC/ABOC session 5 - summing up 21 February 8th 2008 D7i summary D7i has proven to be a very useful tool for improving, automating formalizing and documenting maintenance processes at CERN. Significant amounts of time, money and frustration (not finding documentation etc) can be saved if using D7i to organizing the maintenance work. D7i is integrated with the EDMS-MTF applications and provides this way a complete platform for managing and tracing information about your equipment throughout their entire lifecycle. Help to get started – contact:

ATC/ABOC session 5 - summing up 22 February 8th 2008 GLOBAL REMARKS ON TS’ SESSION N+1 policy (EL,CV) Spare parts policy to consolidate Urgent consolidation plan (approved, to be implemented) CV: users to be “educated” (fluids distribution and legionella) for on call interventions assistance from AB/OP and priorities list D7I as a general purpose tool for maintenance CERN wide