Kirk Schneider American Electric Power Tulsa, Oklahoma AEIC Annual Load Research Conference Reno, Nevada September 10-13, 2006 System Load Calculation for AEP-Texas
What We Did Why We Did It How We Did It What We Found So What? Introduction
The American Electric Power System
ERCOT became single Control Area 7/31/01 Companies stopped checking tie lines. Installed IDRs on a Number of Tie-Lines Verified IDR Data for generation and tie-lines Rate filing for TCC and TNC later this year. Update loss studies. Update demand studies What We Did
What is System Load? Total power consumption on system Measure Power Received from Generators Measure Power Flow at Interconnect Points Can directly measure load, but not losses
“Top-Down” System Load Calculation Generation: Interchange: Net Load: 510 MW
“Bottom-Up” Load Calculation Load: RES 190 COM IND + 60 WHL Losses: Load: 520 MW UFE: - 10 MW
Power Consumption in North American Grid No Boundary Metering Power is consumed the instant it is generated Power Consumed = Power Generated Power Consumed = Power used + power “lost”
ERCOT Transmission System
ERCOT System Load Connected to grid with 3 DC ties System Load = generation + power imported over DC ties – power exported over DC ties SYSTEM LOAD = GENERATION – NET INTERCHANGE EPS Meters on Generation and DC Ties
AEP-Texas System Load Texas Central Co. (South Texas) Texas North Co. (West Texas) TCC ~ 30 Gens, 50 Interconnects TNC ~ 20 Gens, 40 Interconnects
Texas Central Transmission System
Texas North Transmission System
Demand Studies Σ Sales * Loss Factor = Estimated System Load Loss Studies Losses = System Load – Σ Sales Transmission Settlements Unbilled Sales Checks and Balances All Assume System Load is Correct Why AEP Needs System Load
About 12 complete – meter and CT / PTs About 24 meter only using existing CT / PTs Accuracy of Meters Leveraging Existing Metering In South Texas How did We Implement AEP-Texas Tie-Line Metering?
TCC Ties to South Texas EC
How Are We Collecting and Analyzing the Data? Collecting Data Using MV-90 System Data Validation Analyzing Data Using SAS Sent to CEAS System
PROBLEMS! Gaps in IDR Data Suspicious Looking Data Missing Meters Problems Getting Data from ERCOT
SCADA to the Rescue! PI Database Installed Oct 2004 Analog Measurements Accessible with ODBC or OLE SAS Table Containing SCADA Data
Data Validation Use SCADA Data to Validate IDR Data SCADA Strengths Complement IDR Data Use SCADA Data to Fill IDR Data Gaps Examples
Everything’s All Right – Generator 1
Everything’s All Right – Generator 2
Everything’s All Right – Tie 1
Everything’s All Right – Tie 2
Good Enough – SCADA at opposite end of line
Better than Nothing – SCADA at opposite end, load along line
Load Outside Boundary of Meters
Gap In IDR Data - Generator
Gap in IDR Data - Line
SCADA Goes “Flat-Line” for Short Period – Gen
SCADA Goes “Flat-Line” for Short Period – Line 1
SCADA Goes “Flat-Line” for Short Period – Line 2
SCADA Goes “Flat-Line” for Short Period – Line 3
SCADA Goes “Flat-Line” for Long Period – Line 1
SCADA Goes “Flat-Line” for Long Period – Line 2
SCADA Goes “Flat-Line” – Long Period - Gen
SCADA Resolution Problem – Small Line
SCADA Resolution Problem – Line
Time-Synch or Resolution??
No SCADA Available – Wholesale POD’s
General SCADA Failure – Example 1 Gen
General SCADA Failure – Example 2 Gen
General SCADA Failure – Example 3 Line
General SCADA Failure – Example 4
General SCADA Failure – Example 5 Line
Suspicious Generator Data
Impact on System Load Calc
Meter Configuration
Using Alternate SCADA Points
IDR Data vs. SCADA IDR Strengths True integrated values Distributed data collection Lower cost than SCADA SCADA Strengths Time synch extremely accurate Data available real-time Multiple backup measurements Together Provide Very Reliable, Accurate Data
Top Down vs. Bottom Up Summer
Top Down vs. Bottom Up Winter
Top Down System vs. Bottom Up At Meter
System Losses
Percent Losses
Summary of Results SCADA Bailed Us Out Strengths of IDR Data and SCADA Complementary Customer Load Aggregation Matches System Load Able to Perform Loss Study
So What? We Can Measure AEP-Texas System Load Two Measurements Better Than One Understand Your System Load Data Accurate System Load = $$$ Let’s Work Together Again!