MECHANICAL ENGINEERING FOR SYSTEM BALANCE ASHRAE MEETING 2/15/2007 NORTHERN NEVADA CHAPTER 126 MATT BRENNAN, TBE.

Slides:



Advertisements
Similar presentations
HVAC 13a CNST 305 Environmental Systems 1 Dr. Berryman
Advertisements

Chapter 3. HVAC Delivery Systems
HVAC Basics Bin Yan HVAC – Heating, Ventilation, Air-conditioning.
CON 4003 Construction Estimating Prof R. V. Locurcio.
Heating, Ventilating, and Air-Conditioning
Environmental Controls I/IG Lecture 14 Mechanical System Space Requirements Mechanical System Exchange Loops HVAC Systems Lecture 14 Mechanical System.
Commercial Mechanical Requirements
HVAC 101 The Basics of Heating, Ventilation and Air Conditioning
Foundations of Real Estate Management BOMA International ® Module 3: Building Operations I Heating, Ventilating, and Cooling the Building ®
Foundations of Real Estate Management TM BOMA International ® Module 3: Building Operations I Heating, Ventilating, and Cooling the Building.
Learning Outcomes Upon completion of this training one should be able to: Identify open loop and closed loop campus-type hydronic water system applications.
Simple installation. VAV SYSTEM FEATURES ( One Of Many Types ) Electric or Pneumatic or Digital Controls “In Duct” &/or “At Diffuser” Locations Pressure,
Fundamentals of Test & Balance for Engineers. Objectives Help the CxA understand and identify challenges of the TAB Agency Explain what can be accurately.
VAV DESIGN FOR IMPROVED INDOOR AIR QUALITY. “Air conditioning is the control of the humidity of air by either increasing or decreasing its moisture content.
UL/FM Fire Pump Systems Lunch & Learn 04/18/05
Control Valves: Specifications, Sizing & Technologies
Upon completion of this training one should be able to: Identify different types of hydronic heating systems Identify key components in a simple hydronic.
1 Meeting ASHRAE Fundamentals, Standard 55 & 62.1 with Chilled Beams Displacement Ventilation.
Engineer Presentation
© Belimo University 2011, All Rights Reserved
Active beams versus VAV with Reheat Analysis of May 2013 ASHRAE Journal article Ken Loudermilk Vice President, Technology & Developement.
Hydronic Loop Performance: Design vs. Installed Why design and modeling data don’t always match a building’s actual performance David Kandel New Mexico.
Refrigeration and Heat Pump Systems Refrigeration systems: To cool a refrigerated space or to maintain the temperature of a space below that of the surroundings.
Sean Kalman – Hays Fluid Controls
Piping Systems.
Hydronic Mechanical Controls
 Install new air cooled high efficiency screw chiller (variable speed)  Install new fan coils with ECM motors and low temperature heating coils and proper.
Static Pressure Control Loop The purpose of the static pressure control loop is to maintain an optimal static pressure in the ductwork. The control loop.
Lecture 16: Zone Air Paths and Air Distribution Units
AIR QUANTITY REQUIRED TO TRANSFER HEAT IN A FORCED AIR SYSTEM In all four mechanical systems considered, the transfer of heat, either by taking it out.
1 Multi-use Facility. 2 Occupancy – 140 persons Building Characteristics Single story 20,000 square feet (250’ x 80’) Standard construction.
Grundfos FLOW THINKING Air conditioning the Grundfos Way.
Important variables Water: Air: Conversion:
Announcements Midterm Project Prepare groups of 3 to 4 students You can submit the list at the end of next class Midterm Exam 03/09/10 - In class Exam:
1 Medical Office Building. 2 Occupancy – 400 persons 8 a.m. – 5 p.m. Monday - Friday Building Characteristics Three stories 40,000 square feet (200’ x.
Temperature Control Loop
Basics Air Flow Basics -Air is invisible -Everyone assumes adequate airflow -Frequently airflow is 30%-50% low -Cooling – 400 CFM per ton -Heating.
Ductwork Systems and Supply Arch 432. What You Need To Know Become familiar with the materials sizing ductwork Understand sizing units.
Drafts and Duct System Sizing
Architectural Engineering Senior Thesis Mechanical System Redesign Saint Joseph Medical Center Chris Nicolais.
Introduction to Energy Management. Week/Lesson 7 HVAC System Types.
System Components Let’s take a look at the Spacepak System Components.
1 Hospital Building and Campus Piping. 2 Hospital Building Occupancy – office and patient areas Patient areas: 24 hours per day Office areas: 8 am – 5.
Ductwork Systems and Supply Arch 432. What You Need To Know Become familiar with the materials sizing ductwork Understand sizing units.
Introduction to Energy Management. Week/Lesson 13 Control Strategies for Occupant Comfort.
Learning Outcomes Upon completion of this training one should be able to: Identify hydronic chilled water system applications. Define the difference between.
ME444 ENGINEERING PIPING SYSTEM DESIGN CHAPTER 10 : CONTROL VALVES IN CLOSED LOOP SYSTEMS.
Michael Reilly, Jr. – Mechanical Option Advisor – James Freihaut, PhD & Dustin Eplee The Pennsylvania State University Nassau Community College Life Sciences.
Elbow Sound Attenuator (UPC-26C) Outlet (UPC-56B) Plenum Supply Tubing (UPC-25) Blower Modules (2430,3642, 4860) Heating Module (MH2430, MH3660) Cooling.
WSHP Systems 1.
Chapter 14 Heating, Ventilation & Air conditioning (hvac)
Reheat Coil (Typical of 5)
System Diagrams Symbol Library – Black Background David Sellers
Technology in Architecture
BUILDING HEATING AND COOLING
Heating, Ventilating, and Air Conditioning
Heating Ventilating and Air Conditioning
HVAC Basics Arkan Arzesh HVAC – Heating, Ventilation, Air-conditioning.
Heating, Ventilating, and Air-Conditioning
Chilled Beam Performance:
VAV DESIGN FOR IMPROVED INDOOR AIR QUALITY
Air Conditioning System-1
Flip The Long House Let’s imagine the Long house example in Manual J has undergone a house flipping/energy savings update. The insulation was increased,
Follow-ups from Classes 8 and 9
Reheat Coil (Typical of 5)
Objectives Finish with Heat exchangers
4 CHAPTER The First Law of Thermodynamics: Control Volumes.
‘‘ BUILDING AUTOMATION’’
Presented by Mike Zacharias
Presentation transcript:

MECHANICAL ENGINEERING FOR SYSTEM BALANCE ASHRAE MEETING 2/15/2007 NORTHERN NEVADA CHAPTER 126 MATT BRENNAN, TBE

TRIPLE DUTY VALVES FUNCTIONS FUNCTIONS SIZING SIZING INSTALLATION INSTALLATION

FUNCTIONS 1. SHUTOFF VALVE 2. FLOW CONTROL 3. CHECK VALVE 4. FLOW METERING 5. STRAIGHT PATTERN VALVE CONVERTIBLE TO A RIGHT ANGLE VALVE

SIZING! DO NOT ASSUME THIS TO BE A LINE SIZE VALVE. DO INCLUDE A SCHEDULE FOR TDV’s, INCLUDE VALVE Cv & GPM 100% STEM RISE.

SIZING!

SIZING! AHSRAE 90.1 RECOMMENDS, IF THIS IS THE PRIMARY SYSTEM VALVE AND IS SET LOWER THAN 50% STEM RISE THAT THE IMPELLER BE TRIMMED TO THE NECESSARY DESIGN FLOW. THIS WILL REDUCE ELECTRICAL ENERGY CONSUMPION AND COMPLY WITH THE NATIONAL ENERGY BUILDING CODE STANDARD. AHSRAE 90.1 RECOMMENDS, IF THIS IS THE PRIMARY SYSTEM VALVE AND IS SET LOWER THAN 50% STEM RISE THAT THE IMPELLER BE TRIMMED TO THE NECESSARY DESIGN FLOW. THIS WILL REDUCE ELECTRICAL ENERGY CONSUMPION AND COMPLY WITH THE NATIONAL ENERGY BUILDING CODE STANDARD.

SIZING! MOST MANUFACTURES REQUIRE A MINIMUM STEM RISE OF 50% WITH A MINIMUM READING OF 3 FEET OF PRESSURE DROP AND MOST HAVE A MAXIMUM OF 25 FEET OF PRESSURE DROP. MOST MANUFACTURES REQUIRE A MINIMUM STEM RISE OF 50% WITH A MINIMUM READING OF 3 FEET OF PRESSURE DROP AND MOST HAVE A MAXIMUM OF 25 FEET OF PRESSURE DROP.

INSTALLATION DETAILS---DETAILS---DETAILS INCLUDE IN YOUR DETAIL SECTION A DETAIL THAT SHOWS THE TRIPLE DUTY VALVE INSTALLED AT A MINIMUM OF 5 PIPE DIAMETERS IN THE STAIGHT DOWN STREAM AND UPSTREAM OF THE VALVE. INCLUDE TEXT TO COMPLY WITH VALVE MANUFACTURES INSTALLATION RECOMMENDATIONS. INCLUDE IN YOUR DETAIL SECTION A DETAIL THAT SHOWS THE TRIPLE DUTY VALVE INSTALLED AT A MINIMUM OF 5 PIPE DIAMETERS IN THE STAIGHT DOWN STREAM AND UPSTREAM OF THE VALVE. INCLUDE TEXT TO COMPLY WITH VALVE MANUFACTURES INSTALLATION RECOMMENDATIONS.

DETAILS!

DETAILS!

DETAILS! GAUGE MANIFOLD

OPTIONS INSTALL A FLOW VENTURI OR CIRCUIT SETTER WITH A CHECK VALVE. VERY ACCURATE

OPTIONS WHEN USING VARIABLE PUMPING VIA TRANSDUCER AND VFD, DO NOT REQUIRE A TDV, ALL THAT IS NEEDED IS A CHECK VALVE AND ISOLATION VALVE.

DETAILS! SHOW PETE’S PLUGS AS THE FIRST DEVICE AT THE ENTERING AND LEAVING CONNECTIONS OF ANY HEAT EXCHANGER! IE COIL, CHILLER, HX, BOILER, etc. SHOW PETE’S PLUGS AS THE FIRST DEVICE AT THE ENTERING AND LEAVING CONNECTIONS OF ANY HEAT EXCHANGER! IE COIL, CHILLER, HX, BOILER, etc.

DETAILS! HAVE PETES PLUGS INSTALLED NEXT TO ALL TEMPERATURE AND PRESSURE CONTROL SENSORS FOR CALIBRATION.

CIRCUIT SETTERS

SIZING! DO NOT ASSUME THAT THIS IS TO BE A LINE SIZE DEVICE. DO NOT ASSUME THAT THIS IS TO BE A LINE SIZE DEVICE. IN MOST CASES ON SMALLER COILS (REHEAT), LINE SIZE IS TOO LARGE. IN MOST CASES ON SMALLER COILS (REHEAT), LINE SIZE IS TOO LARGE.

SIZING!

INSTALLATION HAVE DETAIL SECTION SHOW THE CORRECT AMOUNT OF STRAIGHT PIPE DIAMETERS BEFORE AND AFTER THE BALANCE VALVE. HAVE DETAIL SECTION SHOW THE CORRECT AMOUNT OF STRAIGHT PIPE DIAMETERS BEFORE AND AFTER THE BALANCE VALVE. INCLUDE A NOTE TO COMPLY WITH THE BALANCE VALVE MANUFACTURES RECOMMENDATIONS. INCLUDE A NOTE TO COMPLY WITH THE BALANCE VALVE MANUFACTURES RECOMMENDATIONS.

INSTALLATION

INSTALLATION

VAV BOXES TYPE TYPE SCHEDULE SCHEDULE SIZING SIZING

SERIES FAN POWERED FAN HANDLES ALL AIR THAT SERVES THE SPACE. FAN HANDLES ALL AIR THAT SERVES THE SPACE.

PARALELL FAN POWERED FAN ONLY HANDLES RETURN PLENUM AIR THAT GOES TO THE SPACE. FAN ONLY HANDLES RETURN PLENUM AIR THAT GOES TO THE SPACE.

VAV WITH REHEAT DAMPER CONTROLS ALL AIR THAT GOES TO THE SPACE. NO FAN. DAMPER CONTROLS ALL AIR THAT GOES TO THE SPACE. NO FAN.

SCHEDULE NUMBER EACH VAV WITH ITS OWN TAG NUMBER. NUMBER EACH VAV WITH ITS OWN TAG NUMBER. DO NOT SELECT 6 OR 7 TERMINALS AND SCHEDULE THEM WITH GENERAL INFORMATION. DO NOT SELECT 6 OR 7 TERMINALS AND SCHEDULE THEM WITH GENERAL INFORMATION. INCLUDE SPECIFICALLY; PRIMARY AIR MAXIMUM, MINIMUM, REHEAT AND FAN CFM. INCLUDE SPECIFICALLY; PRIMARY AIR MAXIMUM, MINIMUM, REHEAT AND FAN CFM. INCLUDE AREA SERVED AND ROOM #s. INCLUDE AREA SERVED AND ROOM #s.

SCHEDULE

SIZING! ALWAYS START BY SELECTING BOX SIZE TO PRODUCT 2000 FPM VELOCITY ±15% AT THE BOX INLET WHEN AT MAXIMUM COOLING CFM. ALWAYS START BY SELECTING BOX SIZE TO PRODUCT 2000 FPM VELOCITY ±15% AT THE BOX INLET WHEN AT MAXIMUM COOLING CFM.

SIZING! THIS WILL MAKE THE BOX MORE CONTROLABLE AT THE MINIMUM SET POINT AS MOST BOX GRAPHS AND CONTROLERS CANNOT CONTROL BELOW 0.03 IN. WC. PRESSURE DROP. IT WILL ALSO MAKE THE BOX MORE ACCURATE AT BOTH ENDS. THIS WILL MAKE THE BOX MORE CONTROLABLE AT THE MINIMUM SET POINT AS MOST BOX GRAPHS AND CONTROLERS CANNOT CONTROL BELOW 0.03 IN. WC. PRESSURE DROP. IT WILL ALSO MAKE THE BOX MORE ACCURATE AT BOTH ENDS.

SIZING!

SIZING! AN OVERSIZED BOX WILL CAUSE THE CONTROLER TO BE UNCALIBRATABLE AT THE MINIMUM CFM SET POINT AS WELL AS CAUSE FLOW HUNTING AND POOR HEAT TRANSFER. AN OVERSIZED BOX WILL CAUSE THE CONTROLER TO BE UNCALIBRATABLE AT THE MINIMUM CFM SET POINT AS WELL AS CAUSE FLOW HUNTING AND POOR HEAT TRANSFER.

SIZING! AN UNDERSIZED BOX WILL REQUIRE THE SUPPLY DUCT STATIC PRESSURE SET POINT TO BE RAISE TO A LEVEL THAT CONSUMES MORE ENERGY THAN NECESSARY. AN UNDERSIZED BOX WILL REQUIRE THE SUPPLY DUCT STATIC PRESSURE SET POINT TO BE RAISE TO A LEVEL THAT CONSUMES MORE ENERGY THAN NECESSARY.

SPORTING CLAY SHOOT ASHRAE FUNDRAISER ASHRAE FUNDRAISER APRIL 15, 2007 APRIL 15, 2007 SAGE HILL CLAY SPORTS SAGE HILL CLAY SPORTS 100 SPORTING CLAYS 100 SPORTING CLAYS SHOTGUN RAFFLE SHOTGUN RAFFLE BBQ LUNCH BBQ LUNCH FUN FOR ALL FUN FOR ALL