A water-cooling solution for PC-racks of the LHC experiments  The cooling concept  Rack Model  Cooling Test  Rack Performance  Failure Tests  Future.

Slides:



Advertisements
Similar presentations
Chapter 3. HVAC Delivery Systems
Advertisements

Energy and heat-aware metrics for data centers Jaume Salom, Laura Sisó IREC - Catalonia Institute for Energy Research Ariel Oleksiak, Mateusz.
Electronics Cooling MPE 635
Moisture to water converter. Out Line : Abstract Introduction Heat Pump Heat Pump Components Conclusion.
André Augustinus 16 June 2003 DCS Workshop Safety.
Basic Refrigeration Cycle
Energy Saving Control-Strategies for Reefer Containers Kresten Kjær Sørensen, Lodam electronics.
Cloud Computing Data Centers Dr. Sanjay P. Ahuja, Ph.D FIS Distinguished Professor of Computer Science School of Computing, UNF.
LECC V. Bobillier1 Overview of LHCb Electronics installation aspects V. Bobillier; L. Roy; J. Christiansen CERN - LHCb.
1 Absorber Heat Transfer and Other Issues A Comparison between MICE and the Forced Flow Absorber System Michael A. Green Lawrence Berkeley National Laboratory.
Thermal Management Solutions from APW President Systems
Variable Speed Indoor Blower Motor Robert Helt Technical Conference - Panama City Beach, Fl
CoolAir Temperature- and Variation-Aware Management for Free-Cooled Datacenters Íñigo Goiri, Thu D. Nguyen, and Ricardo Bianchini 1.
Ice Pile Air Conditioning Joseph Cooper: Project Lead Kylie Rhoades, Clara Echavarria, Jonathon Locke, Alex Gee.
Thermodynamics of Industrial Cooling Towers
Summary of thermal conduction gas tests for ANITA Goal: To measure the heat transport of different gases in a force-convection condition.
High Density Cooling Air conditioning for high density applications
Designing Solar PV Systems (Rooftops ). Module 1 : Solar Technology Basics Module 2: Solar Photo Voltaic Module Technologies Module 3: Designing Solar.
Air Conditioning and Computer Centre Power Efficiency The Reality Christophe Martel Tony Cass.
Thermodynamic Feasibility 1 Anna Haywood, Jon Sherbeck, Patrick Phelan, Georgios Varsamopoulos, Sandeep K. S. Gupta.
Sensor-Based Fast Thermal Evaluation Model For Energy Efficient High-Performance Datacenters Q. Tang, T. Mukherjee, Sandeep K. S. Gupta Department of Computer.
Mission Energy: Energy Efficient Cooling How Data Centre energy consumption and operating costs can be significantly reduced through readily available.
1 HBD Air Cooling System TK Hemmick for the HBD group 8/25/06.
1 07/09/2004Rack Coordination meeting Ph.Gavillet CERN/PH-LBO PC Racks - Status Content qNews, matters arising ãLast Experiment meeting (24/08) – Minutes.
Status and plans for online installation LHCb Installation Review April, 12 th 2005 Niko Neufeld for the LHCb Online team.
Submerged PC Cooling By: Patrick Hague Geoffrey Clark Christopher Fitzgerald Group 11.
Physical Infrastructure Issues In A Large Centre July 8 th 2003 CERN.ch.
HOW THE DUMP RESISTOR’S TANK LOOKS LIKE COOLING OF THE LHC ENERGY EXTRACTION RESISTORS G. Peón (ST/CV), K. Dahlerup-Petersen, G. Coelingh (AT/MEL) Air.
06-November-2013 Thermo-Mechanical Tests BE-RF-PM Review of the CLIC Two-Beam Module Program Thermo-Mechanical Tests L. Kortelainen, I. Kossyvakis, R.
Electronics Enclosures
LIEBE project: WP3 – Construction and tests Project coordination meeting – 30/01/ /01/2015 LIEBE project meeting1 M. Delonca on behalf of the WP3.
Dealing with Hotspots in Datacenters Caused by High-Density Computing Peter Hannaford Director of Business Development EMEA.
The LHC PC Rack Project Fred Wickens On behalf of the LHC PC-Rack Study Group 10th LECC Workshop Boston Sep 2004.
Summary of thermal conduction gas tests for ANITA Goal: To measure the heat transport of different gases in a force-convection environment. John Clem,
Thermal Aware Data Management in Cloud based Data Centers Ling Liu College of Computing Georgia Institute of Technology NSF SEEDM workshop, May 2-3, 2011.
Neil JacksonUK-V RAL 8th September Module to Disc Assembly Infrastructure –Services and test box –Evaporative cooling system –Disc Handling Tests.
We can…. 2 GLOBAL REFERENCES Rev: 00 References :
Virtualization Supplemental Material beyond the textbook.
ALICE PC Cooling System Sensor Marco Boccioli André Augustinus Giulia Fanti.
ATCA cooling tests Claudio Bortolin (PH-ADO) Damian Dyngosz (PH-DT) George Glonti (PH-UAT) Julian Maxim Mendez (PH-ESE) Lukasz Zwalinski (PH-DT) xTCA IG.
February 14, Comprehensive Review B. Schmidt Outline: Status and overview of activities: –Platforms and staircases –Muon Filters and beam plugs.
1 13 Octobre 2011 Laurent Roy ATCA Crate / Infrastructure in place -Rack in D3: dimension -Electrical power availability -Tell1 racks running in D3 (air.
CMS TriDAS project Infrastructure issues for the CMS online farm
A.Henriques (JCOV meeting 31/5/2001) ATLAS Calorimeter cooling project Goal: u Definition of a common frame work for the cooling of the ATLAS calorimeter.
ATCA COOLING PROJECT INTERSHIP FINAL PRESENTATION Piotr Koziol.
CERN - IT Department CH-1211 Genève 23 Switzerland t Power and Cooling Challenges at CERN IHEPCCC Meeting April 24 th 2007 Tony Cass.
Kaeser Direct Drive ESD Rotary Screw Compressor
Date of download: 5/27/2016 Copyright © ASME. All rights reserved. From: Experimentally Validated Computational Fluid Dynamics Model for a Data Center.
Free cooling on RTAF Chiller
Bernard Boutherin 1 Feedback after four years of operation.
Cooling System Get the engine up to optimum operating Temperature as quickly as possible and maintains it at that temperature. Controls the heat produced.
DSLAM Configuration in a Cabinet Heat and Noise testing December 2008.
R2E Report – P5 Safe-Room Update 20 th LSC Meeting, September 13 th 2013 CERN Radiation 2 Electronics (R2E) Project 20 th LSC Meeting September 13 th 2013.
ATLAS ATCA cooling evaluation project Claudio Bortolin (EP-ADO-PO) Michal Kalinowski (EP-ADO-PO) Lukasz Zwalinski (EP-DT-FS) ATLAS cooling team – 2016.
Power consumption (Watts) LBB27 ROS18 TSC50 TIM8 1 SC crate416 Alignment20 TOTAL per rack906~1 kW X2J22X2J02 With a water flow of 10 l/min, it should.
Free Air Cooling for Data Centres
CANOVATE MOBILE (CONTAINER) DATA CENTER SOLUTIONS
T-simulation OUTLINE Inputs to the T-simulation: chips, boards, crate mechanics and fan T-simulation performed into two steps: On large scale: simple AM.
FTK infrastructure in USA15 Status and plans for 2015 A
Using Heat to Increase Cooling George Hannah BEng (Hons) CEng MIMechE
Date of download: 11/2/2017 Copyright © ASME. All rights reserved.
CEDAR Detector Ventilation System Review
Effect of Using 2 TE units on Same Heat Sink
Cloud Computing Data Centers
Cloud Computing Data Centers
TEC assembly and commissioning at Lyon
Liebert DSE High efficiency thermal management
Electron Collider Ring Magnets Preliminary Summary
T-6B On-Board Oxygen Generation System (OBOGS)
Presentation transcript:

A water-cooling solution for PC-racks of the LHC experiments  The cooling concept  Rack Model  Cooling Test  Rack Performance  Failure Tests  Future rack-cooler prototype  Conclusions JCOV- 18Mar04 Nuno Alexandre ELIAS (PH-ATI)

JCOV Meeting /Mar-04 Nuno Alexandre ELIAS [PH - ATI] 2 Why test a water-cooling solution ? All LHC experiments will all have a cluster consisting of rack-mounted PC’s for data-taking (Event Filter Farm). CPU heat dissipation is increasing with clock speed. Assume: W/PC. Current air-cooling best practice for industrial data-centers of max kW per m2, would be very expensive. Water-cooling: can handle high-density heat loads. can profit from available water-cooling infrastructure for electronics. CONCEPT: H orizontally rack-mounted PC’s are cooled with a commercially available, vertically retrofitted heat exchanger, called rack-cooler.

JCOV Meeting /Mar-04 Nuno Alexandre ELIAS [PH - ATI] 3 Rack Simplified Model Horizontal mounted PC’s Rack Cooler –Heat Exchanger –Fans Air stream removes heat from PC’s Rack-cooler extracts heat from air Thermodynamic approach Heat Exchanger

JCOV Meeting /Mar-04 Nuno Alexandre ELIAS [PH - ATI] 4 Cooling Test-bed in ESS lab CERN 56U 19”- rack (LEP) Test a Liebert rack-mounted cooler / 8 kW nominal capacity. Measurement station running PVSS ( reading temperatures, loads, water flow and power consumption) Configurations with increasing number of PCs. Rack Configuration Melrow mono CPU Elonex mono CPU Elonex dual CPU 30 PCs PCs PCs25518

JCOV Meeting /Mar-04 Nuno Alexandre ELIAS [PH - ATI] 5 Cooling Test-bed

JCOV Meeting /Mar-04 Nuno Alexandre ELIAS [PH - ATI] 6 Rack-mounted 1U-PCs MELROW ELONEX ModelsPower consumption OffIdle100% Loaded Elonex mono(5.0 ± 0.5) W(55.0 ± 0.5) W(92.0 ± 0.5) W 40 VA100 VA121 VA Melrow mono(5.0 ± 0.5) W(59.0 ± 0.5) W(96.0 ± 3.0) W -67 VA103 VA Elonex dual(9.0 ± 0.5) W(89.0 ± 2.0) W(167.0 ± 5.0) W 24 VA99 VA180 VA PC configuration of the mono CPU models: single 2.4 GHz CPU, 512MB RAM, 1 Gbit NIC + 1 Fast Ethernet NIC, 40GB disk, PWS 250W (PFC). Perforated front panel serves as air inlet to cool CPU + additional air blower in box. Experience: –Packaging varies: different physical dimensions. –Internal layout is vendor dependent: position of PWS + blower + … 0% => 100% load:  Power= about +35 Watt per CPU

JCOV Meeting /Mar-04 Nuno Alexandre ELIAS [PH - ATI] 7 CPU operating temperatures Check operating conditions from point of view of single PC: will CPUs run at lower/higher T in a closed rack ? Good operating conditions for the PCs The rack-cooler removes the heat out of the racks. In rack with rack-cooler: CPUs operate at a slightly lower temperature than without rack-cooler (lower air flow through PC’s). Open rack in air-cooled room - T(room)=23ºC Load 0%Load 100% Elonex mono32 ± 145 ± 2 Melrow mono40 ± 352 ± 3 Elonex dual30 ± 239 ± 2 Closed rack with rackcooler - T(room)=22ºC Elonex mono29 ± 142 ± 1 Melrow mono40 ± 352 ± 3 Elonex dual28 ± 138 ± 1

JCOV Meeting /Mar-04 Nuno Alexandre ELIAS [PH - ATI] 8 Air flow measurements Measurements of the airflows for rack with 40 PCs. Measurement systematic error of about 15-20% for all measurements. Observations: –Air flow through the PCs when rack-cooler off is 25% lower than the normal air flow => need to test CPU heating in case of rack-cooler fan failure. –Some “holes and gaps” in a closed rack through which air escapes / is taken in: no problem when limited. –Rack-cooler enhances air flow through PCs by ~20% (consistent with CPU temperature results).

JCOV Meeting /Mar-04 Nuno Alexandre ELIAS [PH - ATI] 9 Air temperature mapping PC Load 0% - 48 PCs FrontMiddleBack 21.3 ± ± ± ± ± ± ± ± ± ± ± ± 0.3 Front AverageMiddle AverageBack Average 21.3 ± ± ± 0.4 PC Load 100% - 48 PCs FrontMiddleBack 22.3 ± ± ± ± ± ± ± ± ± ± ± ± 0.3 Front AverageMiddle AverageBack Average 22.4 ± ± ± 0.2 Efficient and homogeneous cooling of the heated air, back to room temperature (or below). Cooling also for PCs who are above/under direct rack-cooler surface. Advantage over inhomogeneous vertical airflow cooling (vertical temperature gradient). Temperature in the middle increases proportionally with the heat load. Depending on the load the air can exit the rack at a temperature higher/lower than the room.

JCOV Meeting /Mar-04 Nuno Alexandre ELIAS [PH - ATI] 10 Dissipated power measurements Difference between Power Dissipated by PC’s and Power removed on rack-cooler increases/decreases room temperature. Heat Loss: P LOSS = P AIR + P SIDE –Air (returned to room at higher/lower temperature) –Side Panels (natural convection + radiation) Highest point: P loss = P in - P out = (0.4±0.2) kW ~ (6±4)% of P in

JCOV Meeting /Mar-04 Nuno Alexandre ELIAS [PH - ATI] 11 Rack-cooler Performance P IN vs. P OUT Temperature of the inlet water (14.5ºC, 16.5ºC, 17.5ºC) Room temperature (20.8ºC>>24.1ºC) What’s the trend line? Can we predict other situations? Is it possible to parameterize?

JCOV Meeting /Mar-04 Nuno Alexandre ELIAS [PH - ATI] 12 Rack-cooler Performance P IN vs. P OUT (vs.  T*) It’s possible to know what’s the “optimal cooling point” for given conditions Results are ‘co-planar’ In the future the conditions will change only between ‘100% load’ and “idle mode’

JCOV Meeting /Mar-04 Nuno Alexandre ELIAS [PH - ATI] 13 Failure Tests Observations: –T_middle , reaches plateau after about 2 hours. –T_side  : heat flow through sides of the rack. Slow increase in room temperature (T_front). –  T(water): still about 50% of P(in) extracted by rack-cooler. –T of CPUs reaches plateau about 8-15 ºC above normal. Recommendations: –Remaining airflow induced by PC fans is enough to keep CPUs running: no immediate action required on PC level. –Fan failure signal would allow for failure handling by DCS. Rack-cooler fans stop (4/4 worst scenario) Central idea: In addition to cooling performance, one needs to check cooling behavior in failure scenarios similar to the ones expected at the experimental sites.

JCOV Meeting /Mar-04 Nuno Alexandre ELIAS [PH - ATI] 14 Failure Tests Observations: –T_middle , reaches plateau after about 2 hours. –T_side  : heat flow through sides of the rack. Slow increase in room temperature (T_front). –T(water): goes to room temperature. –T of CPUs rise slowly to about 6-9 ºC above normal after 2 hours. Recommendations: –Unchanged airflow is enough to keep CPUs running: no immediate action required on PC level. –Slow increase in room temperature: warming up of complete rack. Failure will be detected by water flow monitoring in DCS / barrack temperature in DSS. Cooling water stop

JCOV Meeting /Mar-04 Nuno Alexandre ELIAS [PH - ATI] 15 New Rack-cooler prototype New 10kW prototype rack-cooler from CIAT with integrated door to close the back of the rack. Thermo-dynamical parameters optimized for our cooling requirements. Delivery in the next weeks To be tested in new DAQ test-bed in 157

JCOV Meeting /Mar-04 Nuno Alexandre ELIAS [PH - ATI] 16 Rack Cooler Performance CONCLUSIONS: –Good agreement between theory and measurements –Design parameters play major role on performance –Results show that PC racks can be cooled efficiently with a retro-fitted rack- mounted heat exchanger –Estimation for 10kW was presented using actual data. –Tests on the farm allow us to understand the behavior of the system, and to set up basic parameters for future power dissipation. –A CIAT 10kW rack-cooler was purchased and new tests will start soon. –More detailed results in technical note (draft circulating)