PID Controller Design and

Slides:



Advertisements
Similar presentations
Controller Design Based on Transient Response Criteria
Advertisements

Controller Tuning: A Motivational Example
Model-based PID tuning methods Two degree of freedom controllers
Chapter 9 PID Tuning Methods.
13. Controller Tuning and Troubleshooting
Tuning PID Controller Institute of Industrial Control,
10.1 Introduction Chapter 10 PID Controls
Optimization-based PI/PID control for SOPDT process
ERT 210 Process Control & dynamics
CHE 185 – PROCESS CONTROL AND DYNAMICS
INDUSTRIAL AUTOMATION (Getting Started week -1). Contents PID Controller. Implementation of PID Controller. Response under actuator Saturation. PID with.
Chapter 4: Basic Properties of Feedback
Controller Design, Tuning. Must be stable. Provide good disturbance rejection---minimizing the effects of disturbance. Have good set-point tracking---Rapid,
Ratio Control Chapter 15.
Nyquist Stability Criterion
Chapter 12. Direct Synthesis ( G includes G m, G v ) 1. Specify closed-loop response (transfer function) 2. Need process model, (= G P G M G V ) 3. Solve.
Lecture 8B Frequency Response
CHE 185 – PROCESS CONTROL AND DYNAMICS
CHE 185 – PROCESS CONTROL AND DYNAMICS
Controllers With Two Degrees of Freedom
Feedback Controllers Chapter 8
Control System Design Based on Frequency Response Analysis
Chapter Summer 2. Comparator 3. Block Blocks in Series
Controller Tuning: A Motivational Example
Development of Empirical Models From Process Data
Chapter 11 1 Closed-Loop Responses of Simple Control Systems In this section we consider the dynamic behavior of several elementary control problems for.
Process Control Instrumentation II
Feedback Controllers Chapter 8.
Lecture 7: PID Tuning.
بسم الله الرحمن الرحيم PID Controllers
Chapter 7 PID Control.
Proportional/Integral/Derivative Control
Control System Design Based on Frequency Response Analysis
DYNAMIC BEHAVIOR AND STABILITY OF CLOSED-LOOP CONTROL SYSTEMS
Controller Design (to determine controller settings for P, PI or PID controllers) Based on Transient Response Criteria Chapter 12.
Chapter 14 Frequency Response Force dynamic process with A sin  t, Chapter
Model Reference Adaptive Control (MRAC). MRAS The Model-Reference Adaptive system (MRAS) was originally proposed to solve a problem in which the performance.
Feedback Controllers Chapter 7.
Feedback Control system
بسم الله الرحمن الرحيم Advanced Control Lecture three Mohammad Ali Fanaei Dept. of Chemical Engineering Ferdowsi University of Mashhad Reference: C. C.
Chapter 7 Adjusting Controller Parameters Professor Shi-Shang Jang Chemical Engineering Department National Tsing-Hua University Hsin Chu, Taiwan.
SELF TUNING OF CONTROLLERS What is a Controller Controller is an active element or device that receives the information from the measurements and takes.
CHAPTER 12: Controller Design, Tuning, & Troubleshooting
ERT 210/4 Process Control Hairul Nazirah bt Abdul Halim Office: CHAPTER 8 Feedback.
Chapter 8 Feedback Controllers 1. On-off Controllers Simple Cheap Used In residential heating and domestic refrigerators Limited use in process control.
Miss Hairul Nazirah bt Abdul Halim
Control System Design Based on Frequency Response Analysis
Features of PID Controllers
Chapter 4 A First Analysis of Feedback Feedback Control A Feedback Control seeks to bring the measured quantity to its desired value or set-point (also.
ChE 182 Chemical Process Dynamics and Control
Feedback Controllers Chapter 8
Process Control Methods 1. Open-Loop Control 2 Process control operations are performed automatically by either open-loop or closed-loop systems Processes.
Lecture 9: PID Controller.
Process Control. Feedback control y sp = set point (target value) y = measured value The process information (y) is fed back to the controller The objective.
EEN-E1040 Measurement and Control of Energy Systems Control I: Control, processes, PID controllers and PID tuning Nov 3rd 2016 If not marked otherwise,
Control System Design Based on Frequency Response Analysis
Feedback Controllers Chapter 8
Workshop for Flipped Class
Controller Tuning: A Motivational Example
Tuning of PID controllers
Tuning of PID controllers
Controller Tuning: A Motivational Example
Features of PID Controllers
بسم الله الرحمن الرحيم PID Controllers
Nyquist Stability Criterion
Feedback Controllers Chapter 8
Closed-Loop Frequency Response and Sensitivity Functions
Controller Tuning: A Motivational Example
PID Controller Design and
Controller Tuning Relations
Presentation transcript:

PID Controller Design and Tuning Performance Criteria For Closed-Loop Systems The function of a feedback control system is to ensure that the closed loop system has desirable dynamic and steady-state response characteristics.

The desired performance of closed-loop system: The closed-loop system must be stable. The effects of disturbances are minimized, providing good disturbance rejection. Rapid, smooth responses to set-point changes are obtained, that is, good set-point tracking.

Steady-state error (offset) is eliminated. Excessive control action is avoided. 6.The control system is robust, that is, insensitive to changes in process conditions and to inaccuracies in the process model.

PID controller settings can be determined by a number of alternative techniques: Direct Synthesis (DS) method Internal Model Control (IMC) method Controller tuning relations Frequency response techniques Computer simulation On-line tuning after the control system is installed.

Method 1-5 based on process models (DS & IMC) Can be used to specify the controller settings before the control system is installed. Provide good initial controller settings that can subsequently be fine tuned on-line, if necessary Method 6 – online tuning – time consuming, very useful to have a good initial controller setting

Method 1-2 based on simple transfer function models---Section 12.2 Method 5 – Computer simulation of controlled process – MATLAB & Simulink Method 6 – Online tuning --- Section 12.5

Direct Synthesis Method In the Direct Synthesis (DS) method, the controller design is based on a process model and a desired closed-loop transfer function.

First-Order-plus-Time-Delay (FOPTD) Model Consider the standard FOPTD model, Substituting Eq. 12-10 into Eq. 12-9 and rearranging gives a PI controller, with the following controller settings: Second-Order-plus-Time-Delay (SOPTD) Model Consider a SOPTD model,

Substitution into Eq. 12-9 and rearrangement gives a PID controller in parallel form, where: Example 12.1 Use the DS design method to calculate PID controller settings for the process:

Consider three values of the desired closed-loop time constant: Consider three values of the desired closed-loop time constant: . Evaluate the controllers for unit step changes in both the set point and the disturbance, assuming that Gd = G. Repeat the evaluation for two cases: The process model is perfect ( = G). The model gain is = 0.9, instead of the actual value, K = 2. Thus, The controller settings for this example are: 3.75 1.88 0.682 8.33 4.17 1.51 15 3.33

The values of Kc decrease as increases, but the values of and do not change, as indicated by Eq. 12-14. Figure 12.3 Simulation results for Example 12.1 (a): correct model gain.

Fig. 12. 4 Simulation results for Example 12 Fig. 12.4 Simulation results for Example 12.1 (b): incorrect model gain.

Internal Model Control (IMC) A more comprehensive model-based design method, Internal Model Control (IMC), was developed by Morari and coworkers (Garcia and Morari, 1982; Rivera et al., 1986). The IMC method, like the DS method, is based on an assumed process model and leads to analytical expressions for the controller settings.

Figure 12.6. Feedback control strategies

On-Line Controller Tuning Continuous Cycling Method Relay Auto-Tuning Step Test Method

Continuous Cycling Method Ziegler and Nichols (1942) introduced the continuous cycling method for controller tuning. based on the following trial-and-error procedure: Step 1. After the process has reached steady state (at least approximately), eliminate the integral and derivative control action by setting: = zero = the largest possible value.

Step 2. Set Kc equal to a small value (e. g. , 0 Step 2. Set Kc equal to a small value (e.g., 0.5) and place the controller in the automatic mode. Step 3. Gradually increase Kc in small increments until continuous cycling occurs. The term continuous cycling refers to a sustained oscillation with a constant amplitude. Ultimate gain, Kcu - The numerical value of Kc that produces continuous cycling (for proportional-only control) Ultimate period, Pu - The period of the corresponding sustained oscillation

Step 4. Calculate the PID controller settings using the Ziegler-Nichols (Z-N) tuning relations in Table 12.6.

Step 5. Evaluate the Z-N controller settings by introducing a small set-point change and observing the closed-loop response. Fine-tune the settings, if necessary.

Figure 12.12 Experimental determination of the ultimate gain Kcu.

Relay Auto-Tuning Åström and Hägglund (1984) have developed an attractive alternative to the continuous cycling method. In the relay auto-tuning method, a simple experimental test is used to determine Kcu and Pu. For this test, the feedback controller is temporarily replaced by an on-off controller (or relay). After the control loop is closed, the controlled variable exhibits a sustained oscillation that is characteristic of on-off control (cf. Section 8.4). The operation of the relay auto-tuner includes a dead band as shown in Fig. 12.14. The dead band is used to avoid frequent switching caused by measurement noise.

Figure 12.14 Auto-tuning using a relay controller.

The relay auto-tuning method has several important advantages compared to the continuous cycling method: Only a single experiment test is required instead of a trial-and-error procedure. The amplitude of the process output a can be restricted by adjusting relay amplitude d. The process is not forced to a stability limit. The experimental test is easily automated using commercial products.

Step Test Method In their classic paper, Ziegler and Nichols (1942) proposed a second on-line tuning technique based on a single step test. The experimental procedure is quite simple. After the process has reached steady state (at least approximately), the controller is placed in the manual mode. Then a small step change in the controller output (e.g., 3 to 5%) is introduced. The controller settings are based on the process reaction curve (Section 7.2), the open-loop step response. Consequently, this on-line tuning technique is referred to as the step test method or the process reaction curve method.