Dealing with Hotspots in Datacenters Caused by High-Density Computing Peter Hannaford Director of Business Development EMEA.

Slides:



Advertisements
Similar presentations
Presented by Paul Almond – Datacentre UK
Advertisements

SAN DIEGO SUPERCOMPUTER CENTER at the UNIVERSITY OF CALIFORNIA, SAN DIEGO Green Datacenter Initiatives at SDSC Matt Campbell SDSC Data Center Services.
Computer Room Requirements for High Density Rack Mounted Servers Rhys Newman Oxford University.
Data Center Design Issues Bill Tschudi, LBNL
Optimizing High Density Cooling Solutions for Data Centers
THE EVOLUTION OF TECHNOLOGY SPACES Dave McGrath Director Business Development Construction, Facilities and Engineering Division.
Clair Christofersen Mentor – Aaron Andersen August 2, 2012
Session Title: Demystifying Efficiency in the Data Center Utilizing Airflow as a System Presented By: Jon deRidder Enabled Energy.
1 Using CFD as a Guide When Making Changes to the Data Centre. Nagy Daniel Senior IT Manager Magyar Telekom Technical Unit, IT Operations Directorate.
Matt Warner Future Facilities Proactive Airflow Management in Data Centre Operation - using CFD simulation to improve resilience, energy efficiency and.
AIR DISTRIBUTION (Additional information. Also see Chapter 18) General The proper delivery of air for heating, cooling, or ventilation is a crucial part.
Hot Aisle vs. Cold Aisle Containment
Improving Cooling efficiency in tomorrow's data centre
Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers Data Centre Best Practises Workshop 17 th March 2009.
Cooling Product Positioning
Cloud Computing Data Centers Dr. Sanjay P. Ahuja, Ph.D FIS Distinguished Professor of Computer Science School of Computing, UNF.
PG&E and Altera Data Center Energy Efficiency Project.
© Future Facilities Ltd By Stuart Crump The Value of Blanking Plates Server equipment will suck the air supply it requires from wherever it can within.
VIACOM Data Center Optimization Project
Effect of Rack Server Population on Temperatures in Data Centers CEETHERM Data Center Laboratory G.W. Woodruff School of Mechanical Engineering Georgia.
Thermal Management Solutions from APW President Systems
Dynamic Reduced-order Model for the Air Temperature Field Inside a Data Center G.W. Woodruff School of Mechanical Engineering Georgia Institute of Technology.
HVACR416 - Design Pressure Measurement Part 2. Pressure Measurement Several pressure measurements exist. They all measure the same things, the force of.
 Site  Requirements  Local Resources  Initial layout ideas  Brief material selection  Supply options.
Computer Room Experiences A medium sized tier-2 site view Pete Gronbech GridPP Project Manager HEPIX April 2012.
All content in this presentation is protected – © 2008 American Power Conversion Corporation Rael Haiboullin System Engineer Capacity Manager.
September 18, 2009 Critical Facilities Round Table 1 Introducing the Heat Wheel to the Data Center Robert (Dr. Bob) Sullivan, Ph.D. Data Center Infrastructure.
All content in this presentation is protected – © 2009 APC by Schneider Electric Core | High Density | Rev 0 Build a Better Data Center with APC and Cisco.
Saving up to 60% of Energy With The Precision Cooling SmartAisle ™ Configuration.
Cooling: Best Practices and Economizers
Best Practices in HVAC Design/Retrofit
Applying Precision Air Conditioning Systems
Air Conditioning and Computer Centre Power Efficiency The Reality Christophe Martel Tony Cass.
Liam Newcombe BCS Data Centre Specialist Group Secretary Energy Efficient Data Centres.
Virtualization is only half the battle for efficiency in Data Centers Eduard Bodor System Engineer Romania & Bulgaria.
Infrastructure Gina Dickson – Product Manager Kevin Jackson – Sales Manager.
Thermal Design Project Final Report John Wallerich Principal Engineer Wallerich Group, LLC.
Electronics Enclosures
Schneider Electric: Total Cooling Solutions for Data Centers
Power and Cooling at Texas Advanced Computing Center Tommy Minyard, Ph.D. Director of Advanced Computing Systems 42 nd HPC User Forum September 8, 2011.
Cooling Solutions – RC and HACS. © 2005 APC corporation. InfraStruXure™ for Small and Medium Data Centers InRow RC Accessories  ACAC10001 – 300mm wide.
TS/CV/DC CFD Team CFD Study of the L3 Thermal Environment Sara C. Eicher
Containment Solutions. Cooling Efficiency Solutions Passive Thermal Containment Blanking Panels Foam, Skirts and Covers Raised Floor Grommets Brush Seal.
Energy Savings in CERN’s Main Data Centre
All content in this presentation is protected – © 2008 American Power Conversion Corporation Row Cooling.
1 ITM 4.1: A Three-Step Approach to Better Instrumentation of the Data Center and Use of KPIs in Decision Making George Clement.
Date of download: 5/27/2016 Copyright © ASME. All rights reserved. From: Experimentally Validated Computational Fluid Dynamics Model for a Data Center.
Hot /Cold Aisle Containment  Traditional Data Center/Telco designs are changing significantly!
1 PCE 4.4 New Development In DC Containment Steve Howell.
1 ITM 1.2 How IT Decisions Impact Data Center Facilities: The Importance of Collaboration Lars Strong P.E. Upsite Technologies, Inc.
1 PCE 2.1: The Co-Relationship of Containment and CFDs Gordon Johnson Senior CFD Manager at Subzero Engineering CDCDP (Certified Data Center Design Professional)
Ventilation & Airflow NetShelter CX 18U,24U,38U Ambient office air is drawn in to the soundproofed air-intake chambers on either side of the NetShelter.
InfraStruXure Systems Alex Tavakalov
Setting up the Zeroth level of a Computational Grid Vincenzo Spagnoletti District Manager
1 Copyright © 2016, The Green Grid The webcast will begin shortly Today’s live session will be recorded.
10 SERIES ® PAGODA STYLE VENT OPTIONS Crenlo’s newest Emcor Product.
CANOVATE MOBILE (CONTAINER) DATA CENTER SOLUTIONS
Containment Solutions
Lars Strong P.E. Upsite Technologies, Inc.
Unit 2: Chapter 2 Cooling.
The Data Center Challenge
Date of download: 10/12/2017 Copyright © ASME. All rights reserved.
Using Heat to Increase Cooling George Hannah BEng (Hons) CEng MIMechE
Date of download: 10/29/2017 Copyright © ASME. All rights reserved.
Date of download: 11/2/2017 Copyright © ASME. All rights reserved.
Data Center Controls Mark Hydeman, P.E., FASHRAE Taylor Engineering, LLC
Cloud Computing Data Centers
High-Power GPU Rack: Hybrid Cooling
Cloud Computing Data Centers
Liebert DSE High efficiency thermal management
Presentation transcript:

Dealing with Hotspots in Datacenters Caused by High-Density Computing Peter Hannaford Director of Business Development EMEA

InfraStruXure™ for Data Centers Thermal Management  The increase in power densities in modern electronics is having a direct impact on the environment housing them  Thermal management of equipment housed in an enclosure is fast becoming the most serious risk to availability in today’s Mission Critical Facilities (MCF)  Cooling high power density equipment demands a far more accurate method of controlling air movement in an MCF

InfraStruXure™ for Data Centers Cooling the server

InfraStruXure™ for Data Centers Cooling the cabinet

InfraStruXure™ for Data Centers Cooling the data center

InfraStruXure™ for Data Centers 300 cfm One 300 cfm(141.6 lps) vented tile per rack Typical Raised-Floor Airflow

InfraStruXure™ for Data Centers Grate tile Perf tile Blade Servers Standard IT Equipment With Effort Typical Capability Extreme Impractical [47.2] [94.4] [141.6] [188.8] [236.0] [283.2] [330.4] [377.6] [424.8] [471.9] Floor Tile Cooling Ability cfm Rack Power (kW) that can be cooled by one tile with this airflow

InfraStruXure™ for Data Centers Rack Cooling using Sub-Floor Airflow

InfraStruXure™ for Data Centers Implement Hot Aisle / Cold Aisle Racks face same direction Most rack-mounted servers draw air in the front and exhaust at the rear Exhaust air mixes with cold air with no aisle separation Racks facing each other Reduced temperature in cold aisle Reduced air mixing Higher return air temperatures to CRAC

InfraStruXure™ for Data Centers Effect of Adding Blanking Panels Without Blanking Panels With Blanking Panels

InfraStruXure™ for Data Centers Install Airflow Assisting Devices  Fan-tray devices, such as APC’s Air Distribution Unit, draw air from sub-floor plenum to create cold air curtain between front door and server inlets.  Rack densities increase to 3 kW  For higher densities replace rear door of rack with APC’s Air Removal Unit to draw air in horizontal plane from cold aisle into server inlets  Rack densities increased to 7kW

InfraStruXure™ for Data Centers In-Row Cooling

InfraStruXure™ for Data Centers High Density Cooling Enclosure

InfraStruXure™ for Data Centers 4 x 100kW AHU Air Flow Rate: 16,000 CFM (7550L/s) Supply Temp: 17.3degC 84 NetShelter VX racks 3kW Loading per rack Server Air Flow Rate: 160 CFM /kW 75.5L/s per kW 96 Floor Tiles 40% Open Area Ratio 4 x Structural Columns Geometry: Dimensions: 16.15m x 11.65m x 3.5m Floor Area:188 m 2 Floor Void Depth: 0.5m Raised Floor to Ceiling: 3.0m Cold Aisle Hot Aisle Case Study

InfraStruXure™ for Data Centers Phase1 Legacy Configuration Temperature at 1.8m Above Raised Floor Level Void Pressure 0.25m from Floor Y Velocity through Floor Tiles At 1.8m above raised floor level, some of the cabinets in the top two rows are seeing inlet temperatures of up to 28 o C. Slight ingress of warm are is occurring through the gaps in the third row.

InfraStruXure™ for Data Centers 12 x FM IR units Volume Flow Rate: 6,500CFM (3068L/s) Supply Temp: 20.0degC 104 NetShelter VX racks 3kW Loading per racks Server Flow Rate: 160cfm /kW 75.5L/s per kW Phase1 In Row Configuration 4 x Structural Columns Geometry: Dimensions: 16.15m x 11.65m x 3.5m Cold Aisle Hot Aisle Cold Aisle FM In Row design increases space utilisation to 104 racks

InfraStruXure™ for Data Centers Phase1 In Row Configuration Temperature at 1.8m Very good containment is maintained across the entire room with maximum inlet temperatures at the tops of the cabinets reaching no more than 21 o C.

InfraStruXure™ for Data Centers With increased loads of 4.5kW per rack, In Row systems cope extremely well with maximum inlet temperatures reaching around 24 o C. Legacy systems see temperatures exceeding 30 o C. Phase1 Comparison Increased Load to 4.5kW per Cabinet Temperature at 1.8m (42U) Legacy 4.5kW, 84 Racks, Total Load = 378kWIn Row 4.5kW, 104 Racks Total Load = 468kW Legacy 3kW, 84 Racks, Total Load = 256kWIn row 3kW, 104 Racks, Total Load = 312kW

InfraStruXure™ for Data Centers Phase1 Comparison N+1 Failure Scenarios at 3kW per Cabinet Temperature at 1.8m (42U) Legacy 3kW, 84Racks, Total Load = 256kW Legacy AHU Failure, 3kW = 256kW In row 3kW, 104 Racks, Total Load = 312kW In row FM IR Failure, 3kW = 312kW Inlet temperature >30 o CInlet temperature o C

InfraStruXure™ for Data Centers Conclusions  Blade servers and HD devices offer many benefits but draw from 2x to 5x the power when compared with older technology  Keep the data center operating in optimum condition to avoid equipment failures, unexplained slowdowns and shortened equipment life  Use new technology to keep HD racks cool.