How to reduce cooling duties in CLIC M. Nonis EN/CV CLIC Workshop 2014 - 4 th February 2014.

Slides:



Advertisements
Similar presentations
Antero Punttila Analyzing most typical energy saving measures Energy Efficiency of Steam and Condensate Systems Antero Punttila, Motiva Oy.
Advertisements

Environmental Controls I/IG Lecture 14 Mechanical System Space Requirements Mechanical System Exchange Loops HVAC Systems Lecture 14 Mechanical System.
Heat Recovery for Commercial Buildings
Learning Outcomes Upon completion of this training one should be able to: Identify open loop and closed loop campus-type hydronic water system applications.
Engineering Department EN Cooling and Ventilation issues 1 FUTURE EXPLOITATION OF THE EAST AREA EN-CV Michel OBRECHT.
CNG Refuelling station. A company located in Cherasco (Italy), is among the world leaders in the field of designing and manufacturing of components and.
Hydraulics.
Capture of Heat Energy From Diesel Engine After Cooler Circuit (2006 Annual Report) Mark Teitzel Alaska Village Energy Corporation
44 th Annual Conference & Technical Exhibition By Thomas Hartman, P.E. The Hartman Company Georgetown, Texas Sustainable Chilled Water.
UTSW Thermal Energy Plants, Power Generation and Electrical System What do we do to meet the Emission Reduction, Energy usage Reduction and Electrical.
Presentation Outline Introduction CHP Analysis Electrical Analysis Acoustical Analysis Thermal Storage Analysis System Optimization Analysis Conclusion.
Cooling and Heat Recovery at the Max IV Research Facility.
First Considerations on CLIC Cooling System Ch. Martel, J. Inigo-Golfin TS/CV.
Air-Source Heat Pumps I North Seattle Community College HVAC Program Instructor – Mark T. Weber, M.Ed. Airsource Heat Pump 1.
Water piping design.
Grundfos FLOW THINKING Air conditioning the Grundfos Way.
Preliminary Studies of the Electric Power Distribution for CLIC
Point 5 - Cooling Network - Key Primary Water Chilled Water Mixed Water Eau Bruite Standard Power Diesel Backup Comp Air Primary Water at 20-25C – Produced.
Chilled water Meyrin consolidation Study 1 st Part Many thanks for their contribution to: Pasquale Alemanno, Fortunato Candito, Alexander Putzu.
CV activities on LHC complex during the long shutdown Serge Deleval Thanks to M. Nonis, Y. Body, G. Peon, S. Moccia, M. Obrecht Chamonix 2011.
1 Medical Office Building. 2 Occupancy – 400 persons 8 a.m. – 5 p.m. Monday - Friday Building Characteristics Three stories 40,000 square feet (200’ x.
21/01/02 - ECAL Cooling - Arnaud Hormiere ST/CV 1 Development of ECAL COOLING PLANT Application to a Super Module.
Maintenance Specificities in the CERN Cooling and Ventilation Group Asset and Maintenance Management Workshop CERN, November 2013 I. El Hardouz,
Urban Water Department of Hydro Sciences, Institute for Urban Water Management Peter Krebs Dresden, Global water aspects 1 Introduction to urban.
Lindab Solus - Simply the natural choice.... lindab | comfort Chilled beam revolution! + Save up to 45 % cooling energy!* + Installation and investment.
The EWZ building Presentation of the building Presentation of the building The design issue The design issue The building concept The building concept.
Design of HVAC systems for bld 3862 – LHCb control room and for bld 2885 – LHCb new workshop.
Re-Commissioning of the Water Cooling System at Université de Sherbrooke Department of Buildings June 2008.
EN-CV during LS1: Upgrade, Consolidation, Maintenance, Operation M Nonis EN/CV Chamonix 2012 – LHC performance Workshop On behalf of EN/CV Group.
Drive beam magnets powering strategy Serge Pittet, Daniel Siemaszko CERN, Electronic Power Converter Group (TE-EPC) OUTLINE : Suggestion of.
HOW THE DUMP RESISTOR’S TANK LOOKS LIKE COOLING OF THE LHC ENERGY EXTRACTION RESISTORS G. Peón (ST/CV), K. Dahlerup-Petersen, G. Coelingh (AT/MEL) Air.
VENTILATION PRINCIPLE FOR THE DRIVE BEAM TUNNEL M Nonis – EN/CV – 28/7/2009 Already presented by C. Martel/ J Inigo Golfin on15 th October 2008 CLIC WORKSHOP.
IMPROVING COOLING SYSTEM EFFICIENCY WITH PRE-COOLING AJ Schutte 15 August 2012.
John Osborne : GS-SEM Civil Engineering 19 May 2009 Report on behalf of CLIC Civil Engineering and Services (CES) WG CTC 19 May 2009 Tunnel Cross Section.
Cooling and Ventilation Activities M. Battistin – EN/CV/PJ IEFC Workshop th March 2012 « CONSOLIDATION and UPGRADE PLANS for the INJECTOR COMPLEX.
Civil Engineering and Services - drawings for CDR - CDR chapter J.Osborne and M.Gastal for CES WG 1.
PSB dump: proposal of a new design EN – STI technical meeting on Booster dumps Friday 11 May 2012 BE Auditorium Prevessin Alba SARRIÓ MARTÍNEZ.
 Overview of the run 2009 for CV  Major improvements in Water treatment - Demineralised water production - Cooling control  Major concerns for.
COOLING & VENTILATION FOR THE DRIVE BEAM TUNNEL M Nonis – EN/CV – 16/9/2009 CLIC TWO BEAM MODULES REVIEW
Learning Outcomes Upon completion of this training one should be able to: Identify hydronic chilled water system applications. Define the difference between.
VENTILATION PRINCIPLE FOR THE DRIVE BEAM TUNNEL CERN TS/CV Wednesday 9 th July 2008 CLIC.
Building 180 NORMATEF TEST FACILITY Demineralized cooling water station upgrade R. Bozzi / EN-CV.
Risto Nousiainen, CLIC workshop ” Technical Issues, Integration & Cost ” working group Progress on Study of Module Cooling Risto Nousiainen.
Energy consumption and savings potential of CLIC Philippe Lebrun CERN, Geneva, Switzerland 55th ICFA Advanced Beam Dynamics Workshop on High Luminosity.
A two-stage system for the future cooling system.
COOLING & VENTILATION PLANTS M. Nonis – CERN EN Department / CV Group Annual Meeting of the FCC study – Rome 14 th April 2016.
CMS TK II cooling Brainstorming P. Tropea (update after meeting on June 13 th with Duccio, Antti, Hans, Jerome, Paolo, Bart) 20 June 2016.
Technical Review EHN1 Extension Cooling Systems and Pipework Jérôme Rodary / EN-CV.
CV works in the non- LHC accelerator complex during 2008 and plans for 2009 ATOP days 2009.
CV Activities for PSB-LIU POPS-B (new MPS for the PSB-LIU) B 245 PSB Demi water cooling plant Stefano Moccia, EN-CV Meeting 07/03/16.
Ullrich, DESY Dubna GDE XFEL The European X-Ray Laser Project X-Ray Free-Electron Laser 1 Water cooling XFEL Desingn of the XFEL water cooling.
EN-CV Progress EHN1 Extension Project Jérôme Rodary EN-CV-PJ 2016/02/04.
Update on the PSB Cooling and Ventilation Systems
Demineralised water cooling system
Design of the thermosiphon Test Facilities 2nd Thermosiphon Workshop
ARAC/H/F Air-cooled water chillers, free-cooling chillers and heat pumps Range: kW.
Sub-system integration for the VBOX
CLIC Civil Engineering & Infrastructure
Tunnel Cross Section Studies
(Potential) Site and Utilities
FCC Tunnel and Shaft Cross Sections
AUTOMATIC ON-LINE BRUSHING FOR HEAT EXCHANGERS AND CONDENSERS
Cooling systems for HL-LHC (WP17.3)
COOLING & VENTILATION INFRASTRUCTURE
Mauro Morandin & Antoine Daël
EN-CV: P8 systems and Detector Cooling
Energy Efficiency in District Coiling System
Oddgeir Gudmundsson, Jan Eric Thorsen and Marek Brand
Maintenance at ALBA facility: Strategy for the conventional services
Conceptual Design of the Central Process Systems
Presentation transcript:

How to reduce cooling duties in CLIC M. Nonis EN/CV CLIC Workshop th February 2014

Outline Original design Principles Constraints Open issues Possible optimizations on cooling Variation on temperature at exit of cooling towers Location of cooling towers Variation of temperature range Water treatment Conclusions 4th February 2014CLIC Workshop M. Nonis2 Aknowledgements: G Peon

Preamble (or disclaimer?) This presentation is rather qualitative than quantitative and does not have the objective of covering all possible options. Figures shown are either calculated, or deducted using some scaling parameter. Examples are on cooling systems for the main tunnel. The objective is to launch the discussion on some possible changes and see whether they are acceptable for CLIC or not. Then, specific cases might be studied in more detail. 4th February 2014CLIC Workshop M. Nonis3

Original design: general principles CLIC facilities have been divided into 5 major cooling sectors according to: Functional and operational requirements Thermal loads Dimensions, geographical distribution: Facilities (Drive beam injector building) HVAC and cooling plants (keep reasonable size) Environmental impact (no cooling towers on surface Points) Further (sub)separation possible during detailed design. 4th February 2014CLIC Workshop M. Nonis4 Ref: M Nonis - CLIC Cost & Schedule WG –

Design principles: constraints Distribution loads between air and water: 10% -90% Minimize space occupancy in main tunnel. Main cooling circuit in tunnel embedded in concrete. No cooling towers on surface Points, all cooling towers centralized in Prevessin. 4th February 2014CLIC Workshop M. Nonis5

Cooling: sectors 1, 2 & 5 Sector 5 (both sides) Sector 1 Sector 2 4th February 2014CLIC Workshop M. Nonis6

Cooling: sectors 3 & 4 Sector 3 Sector 4 (UTRs, dumps, loops) 4th February 2014CLIC Workshop M. Nonis7

Cooling open issues Available space in tunnel for main pipes/ducts and equipment: Booster pumps location; Bypass valves, manifolds (available space, balancing of circuit); Connection to drains. Available space in shafts. Optimising location of primary stations wrt shafts availability. 4th February 2014CLIC Workshop M. Nonis8 Ref: M Nonis - CLIC Cost & Schedule WG –

Cross section cooling major issues Manifold Bypass, connection to drain Missing items: fire fighting, compressed air, chilled water DN500 4th February 2014CLIC Workshop M. Nonis9 Ref: M Nonis - CLIC Cost & Schedule WG –

Main cooling parameters Total cooling power [MW]490.6 Circuit Circuit Circuit Circuit Circuit Total flow rate [m 3 /h]22’274 Temperature difference [K]20 Make up water (design value) [m 3 /h]940* 4th February 2014CLIC Workshop M. Nonis10 * Average water consumption at CERN: 750 m 3 /h

1.What can be done differently to improve operation cost or pending issues? 2.At which cost or drawback? 3.What do we gain? 4th February 2014CLIC Workshop M. Nonis11 Possible optimisations in cooling

1. Variation T out from cooling towers Follow wet bulb temperature variation through the day/months to reduce water temperature at exit of cooling towers, therefore reduce the flow rate needed on primary circuit. Extend the primary circuit to UTRC Regulate temperature of secondary circuit via a 3-way valve. Optimum working point does not coincide with the lowest possible approach Regulation on temperature more difficult 4th February °C 47 °C 27 °C °C Circuit 3 - Q 1 =4’ ’342 m 3 /h

4th February 2014CLIC Workshop M. Nonis13 1. Variation T out from cooling towers Cons: Creation of cooling station in the UTRCs Complexity in operation Additional pipes (primary circuit) in the main tunnel Prons Lower electrical power requested (15%) Bypass and manifold, connection to drain simplified Primary circuit combined with fire fighting network (tbc) Manifold Primary circuit Missing items: fire fighting, compressed air, chilled water DN250 Add circuit 3 – ND350 – in tunnel

2. Modify location of cooling towers 4th February 2014CLIC Workshop M. Nonis14 Group circuits in different way….each station closer to user Gain in electrical consumption (few %) Lose operational flexibility between independent systems (e.g. maintenance).

3. Cooling towers on surface Points 4th February 2014CLIC Workshop M. Nonis15 Each sector is cooled by a dedicated cooling tower located in the surface point. Concerned surface points will serve 2 sectors to maximize redundancies. Make up from local network. (50 m 3 /h)

3. Cooling towers on surface Points CIRCUIT 3 & 4CT in centerCT in surface points Total cooling capacity215 MW Cooling capacity/cell [MW]5011 CT requested surface [m 2 ]1’2801’840 Pump consumption electrical power [MW] MW Pipes in the tunnelDN800 DN500 DN350 DN250 Cost cooling towers [MCHF]20 (FRP)48 (concrete) Cost for piping (accessories excl.) [MCHF]14085 Cost gain in electrical consumption200 kCHF/yr 4th February 2014CLIC Workshop M. Nonis16

3. Cooling towers on surface Points Cons: Stronger environmental impact (outside CERN) Bigger surface needed for installation Impact on shaft dimensions? Prons Smaller pipe diameters in tunnel Lower electrical power requested (25%) No need for booster pumps Bypass and manifold, connection to drain simplified Balancing of circuit simpler and more reliable 4th February 2014CLIC Workshop M. Nonis17 Manifold Fire fighting? Missing items: compressed air, Fire fighting Chilled water DN250 Add circuit 3 – ND350 – in tunnel

4. Temperature range increase Increase of temperature difference between inlet and outlet; on primary side keep constant the range in the cooling towers of 20 K: Recover energy to be used internally at CERN if it matches run schedule. For a 5 K increase: T out = 52 °C acceptable for the equipment? Decrease of flow rates ~20% in concerned circuits. No change of size to be able to cope when heat recovery not running Decrease of electrical power for primary pumps >20% 4th February 2014CLIC Workshop M. Nonis18 45 °C 50 °C 52 °C 27 °C 25 °C 45 °C Circuit 3 - Q 1 =6’342 m 3 /h Q 2 =5’073 m 3 /h

4. Temperature range increase Cons: Higher installation cost Pending issues not solved Prons Lower electrical power requested (20%) Lower make up water consumption (20%) Waste heat recovery will help acceptance of the project. 4th February 2014CLIC Workshop M. Nonis19 Manifold Bypass, connection to drain Missing items: fire fighting, compressed air, chilled water DN500

Raw water (300 μS/cm) make up to compensate evaporation and discharge Discharge water (850 μS/cm) to prevent accumulation of dissolved salts Water treatment proportional to make up: + Treatment against scaling, fouling, corrosion + Biocide and biofilm treatment 5. Water treatment System to recycle water before reject 30 μS/cm Ultra filtration Filter at the size of the bacteria Disconnection tank Softener Reverse osmosis Discharge water from the circuit Demineralised water to the circuit Concentrate to the waste water

5. Water treatment This is a totally new proposal under study tests and assessment of the results to be done. (Possible) Cons: Investment cost to be evaluated with expected lifetime of the system Impact on operation of the recylcing system to ensure full performance. Prons Decrease of water consumption, >50% Decrease of use of chemicals and biocide Decrease of rejected water volumes…….(waste water drain) Compliance with new laws on water reject in France and Switzerland The company ensures that it is economically interesting (several hundreds kCHF overall) in operation cost: tbc with respect to CERN costs.

Summing up With respect to CDR solution Installation costsOperation cost Impact on operation Energy consumption Pending issues Variation T out from CTHigherLowerNo impact-15% (Elec)+ CT on surface pointsLower ++-25% (Elec)+ Range increase in circuitHigherLower++-20% (Elec)- Water treatmentHigherLowerTbd> 50% (Water)- Pending issuesPipesBypass, manifold, drain Booster pumps Circuit balancing Environm. impact CDR solutionDN800/DN500Not okYesDifficultOk Variation T out from CTDN900/DN350/DN250OkYesOk CT on surface pointsDN350/DN250OkNoOkHigher Range increase in circuitNo changeNot okYesDifficultBetter Water treatmentNo changeNot okYesDifficultOk

Ventilation DB Injector building 11 MW - modular solution, every mtrs according to precision requested. Optimize ventilation if temperatures higher than 25 °C accepted: passive cooling (e.g.: no cooling of air installed  no chilled water). Only heating in winter installed. Acceptable for a working place if for a limited number of working hours temperature >26 °C. Would 100 hrs be acceptable? Basic requirement: Good solar protection(colors, glazing) Good thermal isolation of the building. Ventilation during night Additional option: building partially underground shall increase the thermal inertia of the building would limit the maximum temperature at ~28 °C also in Summer. Other systems to increase thermal inertia (puits canadiens, dephaseurs) 4th February 2014CLIC Workshop M. Nonis23

Conclusions All data presented are to be considered as first estimate, several details/information missing. Most critical technical point at present to solve: available space in tunnels. Some of the solutions can be combined together Use of cooling towers in surface points is highly recommended. 4th February 2014CLIC Workshop M. Nonis24

THANK YOU FOR YOUR ATTENTION 4th February 2014CLIC Workshop M. Nonis25

Main cooling parameters 1/2 Power (kW)T inT outQ (m3/h) 1 156’ ’460 1,abldg drive beam inj108’702 4’674 1,btunnel drive beam inj12’ ,cfrequency multiplication18’ ,dtransfer lines6’ ,echilled water production11’ ’ ’ ’215 2,abldg main beam inj 16’ ,btunnel main beam inj 1’ ,csurface damping rings 12’ ,dtunnel damping rings 10’ ,etunnel booster linac 2’ ,fsurface booster linac gchilled water production 2’ th February 2014CLIC Workshop M. Nonis26

Main cooling parameters 2/2 Power (kW)T inT outQ (m3/h) 3 147’ ’341 3,atunnel e- 73’6103’171 3,btunnel e+ 73’6103’ ’ ’840 4,atunnel e- 33’0221’420 4,btunnel e+ 33’0221’ ’1423’ detector premises 14’ accelerator tunnel 53’9112’ chilled water production 4’ th February 2014CLIC Workshop M. Nonis27