FIRE SERVICES AT DATA CENTRE
FM200 TRAINING COURSE
Introduction of FM 200
THE PROPERTIES OF FM-200®
ASHRAE Designation = HFC227ea WHAT IS FM-200® ? C F H ASHRAE Designation = HFC227ea
THE PHYSICS OF FIRE Fire Triangle Fuel, oxygen, heat What is fire? A series of highly exothermic chain-branching free radical reactions Removal of any element of fire triangle results in suppression
Fast & Efficient Performance Removes heat, so fire can’t sustain itself
FM-200® CHEMICAL/PHYSICAL EXTINGUISHING MECHANISM 80% 20% Halon 1301 FM-200®
How is FM-200® Applied? Cup Burner Conc. [Heptane] - 5.8% Use Concentration [Minimum] - 7.5% for ISO compliance Maximum Discharge Time limited to 10 Seconds
FAST & EFFICIENT PERFORMANCE Compact storage space requirements Halon 1301 CO Inert Gas
HUMAN SAFETY FM-200® is completely safe for use in occupied spaces.
FM-200® IS FAST & EFFECTIVE Reaches extinguishing concentration within 10 seconds Provides ACTIVE Fire Protection FM-200® IS FAST & EFFECTIVE
FM-200® ENGINEERED SYSTEMS
ENGINEERED CENTRAL STORAGE FM-200® SYSTEM Distribution Pipe Smoke Detectors Discharge Nozzles Containers Manual Station Raised Floor
PRIMARY APPLICATIONS Computer Rooms
3M™ Novec™ 1230 Fire Protection Fluid Novec 1230 fluid has distinct environmental benefits Ozone depletion potential (ODP) of 0 5 day atmospheric lifetime Global Warming Potential (GWP) of 1 THE NEW CLEAN AGENT
FM200 CONTROL EQUIPMENT
FM200 CONTROL EQUIPMENT Kentec Panel Kentec lock off
FM200 CONTROL EQUIPMENT Kidde Panel Kidde Panel
Viking & Notifier Panel FM200 CONTROL EQUIPMENT Chubb Panel Viking & Notifier Panel
FM200 CONTROL EQUIPMENT Thorn Panel
FM200 CYLINDER
FM200 CYLINDER Kidde FM200
FM200 CYLINDER Chemetron FM200
FM200 CYLINDER ThornFM200
FM200 CYLINDER Fike FM200
FM200 CYLINDER Siemens FM200
Signage Box and Pressure Switch Pressure Switch for Fed-back Signal
Mode Selection - “System Inoperative” Signal Box Flash AUTO-MANUAL Mode Selection Provided Next to the Panel Outside the Room When Personal Before Enter the Room: - Switch the Auto-Manual Switch to “MANUAL” - “System Inoperative” Signal Box Flash - Switch Back to “AUTO” when Leave the Room
FM200 Operation In Auto Mode Two Detection Zones for Each System Cross Zone Operation Activating Anyone Zone: - Alarm Sound - “Do Not Enter” Sign Flash, Don’t Enter the Room
FM200 Operation in Auto Mode Two Zones Activated: - Two-Tone Sounder Raised - “Evacuate” Sign Flash, Evacuate Room Immediately - A/C in the Room Will Shunt Down - System Start Count Down for 30 Sec. - Gas Discharge to Room After Count Down
FM200 System Operation in Manual Mode When Personal Working inside the Room: One Zone of Alarm Activated and Alarm Sound: - Check Any Fire Happened in Room - Inform Others to Leave the Room if Fire Happened - Go out of the Room, Push the “Manual Release” Switch to Discharge Gas Two Zone Activated: - Evacuate Room Immediately
MAINTENANCE OF AFA AND FM200 SYSTEMS Check Smoke Detectors - Corrosion - Dirty - Generate False Alarm Frequently Check Modules - Simulate Tests to Check the Modules Working Properly
MAINTENANCE Monthly & Annual - To Be Carried-Out By FS Contractor
Introduction of VESDA system What is VESDA… Aspirating Smoke Detection 吸气式烟雾探测
THEINTRODUCTION OF VESDA SYSTEM VESDA ADVANTAGE…
Introduction of VESDA system VESDA Panel VESDA Panel
Introduction of HSSD system Kidde HSSD Panel Kidde HSSD Panel 主機板 鐳射探測器 風機
Introduction of HSSD system Kidde HSSD Sampling Point
Introduction of Pre-action system
Introduction of Pre-action system