LAMPS (Chapter 3) Lamp efficacy, life, and color Incandescent
Advertisements

Barjinder singh Senior Lecturer Electrical Engg.
16469 Low Energy Building Design Lighting Cameron Johnstone Department of Mechanical Engineering
16469 Lighting and Daylighting Design. Energy Efficient Lighting Lighting accounts for a significant portion of energy use in commercial buildings We.
Lighting Calculations
Light Visible electromagnetic radiation Power spectrum Polarization Photon (quantum effects) Wave (interference, diffraction) From London and Upton.
Chapter 13 Light and Reflection Hr Physics. Sound and Light They share several characteristics: They can be described as waves. They use the same v= formula.
9CM Name :B Vijaya kumari Designation : Lecturer Branch :Computer Engineering Institute :Smt.B.Seetha. Polytechnic, Bhimavaram, Year/semester :III.
K. F. Chan (Mr.)ELEC LUMEN METHOD Utilization factor -- Ratio of flux received by reference plane to total rated lamp flux in the installation. Utilization.
Light Quantity Lighting Metrics Luminous Flux Illuminance
Homeaboutpartnersnewsdownloads principlesin depthapplicationsteaching resourceslearning resourcesprinciples REF Physics of light REF Photometry Radiometry.
Chapter 2: Origin of Color What produces the color sensation?
Lighting calculations
Electrical Lighting & Cable Selection D.K.Pathirana.
Kitchen & Bath Lighting. A good lighting design should: Look good – both people and design space Provide the proper amount of light in every room Be.
CS348B Lecture 4Pat Hanrahan, 2005 Light Visible electromagnetic radiation Power spectrum Polarization Photon (quantum effects) Wave (interference, diffraction)
Photometric Data Photometry is the science of measurement of light.
Artificial Lighting Design Task lighting for general purpose rooms involves the installation of light sources that will provide the optimum amount of.
Light. Light Facts Light: The range of frequencies of electromagnetic waves that stimulate the retina of the eye. 400 nm – 700 nm ( 4 x to 7 x 10.
1 Lighting Learning outcome from this topic, the student is able to – recognize the definitions and meanings for terms used in lighting – calculate lighting.
Day 10 Environmental Systems I Daylight as a primary lighting source Artificial lighting as a secondary source Room 102 Architecture Building.
Chap 16-1 Light Fundamentals. What is Light? A transverse electromagnetic wave.
DAYLIGHT CALCULATIONS. Components of the Natural Light :  There are three separate components of the natural light that reaches any point inside a building:
Alpha College of Engg & Tech Khatraj, Gandhinagar EEE( ) 1 st SEM EE-A Group 10 1 PATEL ULKABEN RAJENDRAKUMAR ( ) 2 VINOD GIRI KHAMBHU.
CBE 150A – Transport Spring Semester 2014 Radiation.
1 Name of the faculty: V. Narsimha Reddy Designation: Lecturer in EEE Branch : E.C.E. Institute : GMR. Polytechnic Gajwel Year / Semester : VI Semester.
1 Department of Technical Education Andhra Pradesh Name: V. Narsimha Reddy Designation: Lecturer in EEE Branch : D.E.C.E. Institute : GMR. Polytechnic.
Department of Technical Education Andhra Pradesh
9EE605A.3to4 1 Department of Technical Education Andhra Pradesh Name Designation Branch Institute Year/Semester Subject Subject Code Topic Duration Sub.
Department of Technical Education
Department of Technical Education
Chapter 8 Quantity of Lighting © 2006 Fairchild Publications, Inc.
Waves and Energy Transfer 14.1 Wave Properties Wave A repeating disturbance or movement that transfers energy through matter or space.
9EE605A.13to141 Department of Technical Education Andhra Pradesh Name:V. Narsimha Reddy Designation:Lecturer in EEE Branch:D.E.C.E Institute:GMR. Polytechnic.
Department of Technical Education Andhra Pradesh
Describe how electromagnetic energy is transferred through space as electromagnetic waves of varying wavelength and frequency.
Physics 1 H Created by Stephanie Ingle
9EE605A.7to81 Department of Technical Education Andhra Pradesh Name Designation Branch Institute Year/Semester Subject Subject Code Topic Duration Sub.
Department of Technical Education
Objectives Learn about lighting design.
9EE605A.11 Name Designation Branch Institute Year/Semester Subject Subject Code Topic Duration Sub Topic Teaching Aids : P. Balanarsimlu : Lecturer : Electrical.
Light Waves Physics 1 H Created by Stephanie Ingle.
Functions of Lighting – Allow a person to see without straining his or her eyes – Enhance the look of a room or space – Improve safety in areas that may.
Light Waves Physics 1 L Mrs. Snapp. Light Light is a transverse wave. Light waves are electromagnetic waves--which means that they do NOT need a medium.
Lighting systems in labs & offices1 Subject: By:a.Yousefvand.
Chapter 14 Light & Reflection Physics. Light and Reflection ☺Electromagnetic Waves ☺Transverse Waves ☺Oscillating Electric and Magnetic Fields Perpendicular.
Light. The nature of Light Spherical and plane waves.
Chemical Effects The energy of light can chemically change the surfaces of materials absorbing it. Light changes the chemistry of the eye’s retina, so.
Illumination Basic & Scheme Elements of Electrical Design 5 TH SEMESTER Lakhani Ankit Hareshbhai Prepared by.
Light & Optics. Electromagnetic Waves Electromagnetic waves include: light, radio, microwaves, x-rays, gamma rays, ultra-violet, and infrared radiation.
© International Dark-Sky Association Lighting 101; A few basics International Dark-Sky Association
LEVEL 4 ENERGY ASSESSOR TRAINING 8. Level 3 re-cap lighting and Power Factor Correction.
UNIT VI ILLUMINATION, HEATING & WELDING. Q. 1 Explain the different factors to be considered while designing the lighting scheme? Q. 2 What is induction.
Incandescent Light Bulb LUMEN DESIGN METHOD Where: N = E A F UF LLF N = number of lamps E = level of illuminance A = Area at working plane.
ART 2640, Building Systems of Interior Environments Fall Semester 2016 Tuesdays & Thursdays 9:00-10:20 Grover Center E218 Matthew Ziff, Associate Professor.
Physics 1 H Created by Ingle
Lux The lux (symbol: lx) is the SI unit of illuminance and luminous emittance, measuring luminous flux per unit area.[1] It is equal to one lumen per square.
METHODS OF ILLUMINANCE CALCULATION
THE PHYSICS OF LIGHT INTRODUCTION CHARACTERISTICS PHOTOMETRY
ILLUMINATION.
LUMEN METHOD E= N x n x ø x UF x MF A
Point-by-Point Factors
Mr. Vijay Balu Raskar - Electrical Engineer
Construction Studies Resources
Announcement Filed trip is on Monday, May 6th from 8 to 9 AM
Announcement Next class: 15 minutes quiz
CHAPTER – 49 ILLUMINATION
Light Waves, Mirrors and Reflection
The Properties of Light
Presentation transcript:

Department of Technical Education Andhra Pradesh Name : P. Balanarsimlu Designation :Lecturer Branch :Electrical Engineering Institute :Govt. Polytechnic Nizamabad Year/Semester :VI Semester Subject :Electrical Utilisation and Traction Subject Code :EE605A Topic :Electric Lighting Duration :100 Mins :Design & Definitions of Lighting Sub Topic :PPT, Diagrams, Animation Teaching Aids Revised By : K. Chandra Sekhar, L/EEE, GPT, HYD 9EE605A.9to10 1

Recap Calculation of Illumination using Inverse Square Law In the last class you have learnt about Calculation of Illumination using Inverse Square Law Lambert’s Cosine Law 9EE605A.9to10 2

On completion of this topic you would be able to know Objectives On completion of this topic you would be able to know Definitions of terms used in design of lighting schemes. Design of Lighting Scheme for Drawing Halls Assembly Hall Factory 9EE605A.9to10 3

Definitions Utilization Factor or Co-efficient of utilization The following are some of the definitions which we come across in the design of electric lighting scheme. Utilization Factor or Co-efficient of utilization It may be defined as “the ratio of total lumens received on the working plane to the total lumens emitted by the light source”. i.e. Utilization factor = Lumens received on the working plane Lumens emitted by the lamp 9EE605A.9to10 4

Definitions Factors affecting the utilization factor Type light fitting Colour, surface of walls and ceiling Mounting height of lamps Area to be illuminated It’s value lies between 0.4 and 0.6 for direct fittings it varies from 0.1 to 0.35 for indirect fittings 9EE605A.9to10 5

Definitions 2. Depreciation or Maintenance factor It may be defined as “the ratio of illumination under normal working condition to the illumination when every thing is clean or new”. Illumination under normal working conditions i.e. D.F = Illumination when every thing is clean. It’s value will be between 0.6 to 0.8 9EE605A.9to10 6

Definitions Depreciation of illumination is due to the accumulation of dirt and dust on the lamp. Frequent cleaning of lamp improves the depreciation or maintenance factor It is also given as Illumination when every thing is clean. D.F.= Illumination under normal working conditions > 1 9EE605A.9to10 7

Definitions Waste light factor when a surface is illuminated by a number of lamps, there is certain amount of wastage due to overlapping of light waves. It’s value varies between 1.2 to 1.5. Area x illumination x waste light factor Total lumens = Utilisation factor x depreciation factor 9EE605A.9to10 8

Definitions 4. Reflection factor or Co-efficient of reflection It may be defined as “the ratio of luminous flux leaving the surface to the luminous flux incident on it”. Reflected light Reflection factor = Incident light It’s value will be always less than 1 9EE605A.9to10 9

Definitions 5. Reduction factor or spherical reduction factor It may be defined as “ the ratio of mean spherical candle power of a source to its mean horizontal candle power. M.S.C.P. Reduction factor = M.H.C.P. 9EE605A.9to10 10

It’s value varies from 0.5 to 1 Definitions 6. Absorption factor When the atmosphere is full of snow or smoke fumes, it absorbs some light Hence absorption factor may be defined as “the ratio of net lumens available on the working plane after absorption to the total lumens emitted by the lamp” Net lumens on working surface Absorption factor = Lumens emitted by the lamp It’s value varies from 0.5 to 1 9EE605A.9to10 11

Definitions Luminous efficiency or specific out put It may be defined as “the ratio of number of lumens emitted to the electric power in take of a source” it’s unit is lumen/watt (lm/W) 9EE605A.9to10 12

Definitions Some of the Examples of Luminous efficiency sl Type of lamp Colour Efficiency 1 Sodium vapour Yellow 40 to 80 2 Neon Red 15 to 40 4 Mercury vapour Bluish white 40 to 80 5 Incandescent white 10 to 20 9EE605A.9to10 13

It is measured in Watt/candela or Watt/MSCP Definitions 8. Specific energy consumption It may be defined as “the ratio power input to the light source to its luminous intensity”. It is measured in Watt/candela or Watt/MSCP power input to a lamp Specific consumption = Luminous intensity of the lamp 9EE605A.9to10 14

Definitions 9. Space height ratio It may be defined as “the ratio of the horizontal distance between the lamps to the mounting height of the lamps above working plane”. Space between lamps Space height ratio = Mounting height of lamp Its value varies from 0.8 to 1.5 9EE605A.9to10 15

Design of lighting scheme Problem 1 A room 9m x 12m is illuminated by twelve 100watt lamps. The luminous efficiency of the lamp is 30 luminous/watt and the co-efficient of utilization as 0.45. find the average illumination.? Given data Room dimensions = 9m x 12m Wattage of each lamp, P=100 watts No. of lamps=12 Luminous Efficiency=30 lumens/watt 9EE605A.9to10 16

Given data Utilisation Factor, U. F = 0 Given data Utilisation Factor, U.F = 0.45 Required data Average Illumination, E =? Solution Area = 9 x 12 = 108m2 Total wattage = 100 x 12 = 1200 w Total flux = 1200 x 30 = 36000 Lumen Flux reaching on the working plane, Ø = Total flux X U.F. = 36000 x 0.45 = 16200 Lumen. Illumination, E = Ø / A = 16200 / 108 = 150 Lux Ans. 9EE605A.9to10 17

INDOOR LIGHTING Fig.1 9EE605A.9to10 18

Design of Lighting Scheme Problems on Indoor Lighting Problem 2 A Hall 12mx8mx4m is to have direct lighting giving illumination of 80 lux on the working plane 70 m above the floor. Co-efficient of utilization of 0.5 and maintenance factor 0.8. Find the number of fluorescent tube lamps required and their rating. Lamp efficiency may be taken as 40 lumen/watt. Assume suitable space height ratio and draw the layout. 9EE605A.9to10 19

Coefficient of utilization, UF =0.5 Given Data Area, A= 12x8 = 96 m2 Illumination, E = 80 lux Coefficient of utilization, UF =0.5 Maintenance factor, MF = 0.8 Lamp efficiency = 40 lumen/watt Required Data Number of fluorescent lamps ? Rating of fluorescent lamps ? Draw the layout 9EE605A.9to10 20

Flux required on working plane ,Ø Solution Total flux = E x A = 80 x 96 = 7680 lumen Flux required on working plane ,Ø Total Flux 7680 = = = 19200 lumen Ø UF x MF 0.5 x 0.8 Flux,Ø 19200 Total wattage = = = 480 watt η 40 9EE605A.9to10 21

Number of 40 watt fluorescent lamps Solution Number of 40 watt fluorescent lamps Total wattage 480 12 = = = 40 40 12 m 3m 3m 8 m 1.5m 1m 9EE605A.9to10 22

Problems on Indoor Lighting A drawing hall 30mx13m with ceiling height of 5m is to be provided of with general illumination of 120 lux. Taking coefficient of utilization of 0.5 and depreciation factor as 1.4, determine the number of fluorescent lamps required, their spacing, mounting height and total wattage. Luminous efficiency of 80 W fluorescent lamp is 40 lumen/watt. Show the disposition of lamps with sketch. 9EE605A.9to10 23

Coefficient of utilization, UF =0.5 Given Data Area, A= 30x13= 390 m2 Illumination, E = 120 lux Coefficient of utilization, UF =0.5 Depreciation factor, DF = 1.4 Lamp efficiency = 40 lumen/watt Required Data Number of fluorescent lamps ? Rating of fluorescent lamps ? Spacing and mounting height 9EE605A.9to10 24

Solution Total flux = E x A = 120x390 = 46,800 lumen Flux required on working plane Total Flux Ø = x DF UF 46800 = x 1.4 = 1,31,040 lumen 0.5 Flux,Ø 0.5 x 0.8 Total wattage = = η 40 = 480 watt 9EE605A.9to10 25

Solution Flux,Ø 131040 Total wattage = = η 40 = 3726 watt Contd.. Flux,Ø 131040 Total wattage = = η 40 = 3726 watt Number of 40 watt fluorescent lamps Total wattage = 80 3726 = 80 = 40.95 = say 40 lamps 9EE605A.9to10 26

Disposition of Lamps Assuming mounting height = 3m 3 Then space height ratio = = 1 3 9EE605A.9to10 27

Problem 3 A hall 20mx12mx4m is to be illuminated with incandescent lamps of average illumination of 100 lumens/m2 on working plane. Find the number, size and mounting height of the lamps. Show the disposition of the lamp. Assume the depreciation factor and utilization factor as 1.25 and 0.5 respectively. Take the space height ratio as 1 Lamp Size 100w 200w 300w Luminous Efficiency 12 15 18 9EE605A.9to10 28

Given Data Required Data Area, A = 20x12 = 240 m2 Illumination, E = 100 lux Coefficient of utilization, UF =0.5 Depreciation factor, DF = 1.25 Lamp efficiencies = 12, 15, and 18 Required Data Number of incandescent lamps ? Rating of incandescent lamps ? Disposition and mounting height 9EE605A.9to10 29

Solution Flux required on working plane ,Ø E x A = x DF Ø UF 100 x 240 Contd… Flux required on working plane ,Ø E x A = x DF Ø UF 100 x 240 = x 1.25 0.5 = 60,000 lumen 9EE605A.9to10 30

Solution Number of 100 watt lamps required 60000 = 50 = 12 x 100 Contd… Number of 100 watt lamps required 60000 = = 50 12 x 100 Number of 200 watt lamps required 60000 = = 20 15 x 200 9EE605A.9to10 31

Solution Number of 300 watt lamps required 60000 = 12 = 18 x 300 Contd… Number of 300 watt lamps required 60000 = = 12 18 x 300 Assuming mounting height as 3m and lamps are 200w 9EE605A.9to10 32

Disposition of Lamps 4 space height ratio along length wise = 1.33 = 3 space height ratio along width wise = = 1 3 9EE605A.9to10 33

Summary In this class we have discussed about Definitions of terms used in design of lighting scheme Problems on design of lighting 9EE605A.9to10 34

Quiz 1) The ratio of the illumination on a surface under normal conditions to that of ideal conditions is called A) Utilization factor. B) Reduction factor. C) Depreciation factor. D) Reflection factor. 9EE605A.9to10 35

Quiz 2) The ratio of the total lumens received on the working plane to the total lumens emitted by the light source is A) Utilization factor. B) Reduction factor. C) Depreciation factor. D) Reflection factor. 9EE605A.9to10 36

Frequently Asked Questions Define utilization factor and depreciation factor. Define reduction factor and space height ratio. State the factors affecting utilization factor. 9EE605A.9to10 37

Frequently Asked Questions Problem 1 A minimum illumination of 80lux is required in the factory shed of 50mx12m. Calculate the number, the location and wattage of the lamp used. Assume that the depreciation factor is 0.8, coefficient of utilization is 0.4 and the efficiency lamp is 14 lumen/watt Ans : 36 lamps in 3 rows, 12 lamps in each row 9EE605A.9to10 38

Frequently Asked Questions Problem 2 In street lighting scheme, lamps having luminous intensity of 100 candela are hung at a height of 6m. The distance between two lamp posts is 16m. Find the illumination under the lamp and at center in between the lamp posts. Ans : a) 2.9 lux, b) 1.2 lux 9EE605A.9to10 39