Frankfurt (Germany), 6-9 June 2011 KOSTIAINEN– FI – S3– 0622 Paper 0622 TOWARDS SELF-HEALING POWER DISTRIBUTION BY MEANS OF THE ZONE CONCEPT Antti Kostiainen, ABB Oy, Finland, Presenter Pekka Manner, Fortum Oyj, Finland Kari Koivuranta, Fortum Oyj, Finland Göran Wiklund, ABB Oy, Finland
Frankfurt (Germany), 6-9 June 2011 KOSTIAINEN– FI – S3– 0622 Principles of the Zone Concept Network control center
Frankfurt (Germany), 6-9 June 2011 KOSTIAINEN– FI – S3– 0622 Self-healing network IEC Network topology Communication Fault location Remote controllable devices
Frankfurt (Germany), 6-9 June 2011 KOSTIAINEN– FI – S3– 0622 Power reliability indices of the pilot case Power reliability indices of the two pilot feeders in 2010 MAIFI 10,78 pcs /customer SAIDI 7,2 h /customer SAIFI 18,85 pcs /customer
Frankfurt (Germany), 6-9 June 2011 KOSTIAINEN– FI – S3– 0622 Feasibility of the pilot (ph.1) investment Total investment of the pilot case is € * Customer Interruption Costs YearsTotal CIC* savings in € Profitability in €
Frankfurt (Germany), 6-9 June 2011 KOSTIAINEN– FI – S3– 0622 Case: System operation during a fault Masala area has 20 remote controlled disconnector zones (red areas) Masala area has two remote controlled re- closer protected zones (blue areas) 110 kV 20 kV
Frankfurt (Germany), 6-9 June 2011 KOSTIAINEN– FI – S3– 0622 [0 s] A fault occurs Case: Fault occurs 110 kV 20 kV
Frankfurt (Germany), 6-9 June 2011 KOSTIAINEN– FI – S3– 0622 Case: Re-closer tries to clear out the fault [0 s] A fault occurs [1 s] remote re-closer operates 110 kV 20 kV
Frankfurt (Germany), 6-9 June 2011 KOSTIAINEN– FI – S3– 0622 Case: The system locates the fault [0 s] A fault occurs [1 s] remote re-closer operates [10 s] The system analyses and localizes the fault 110 kV 20 kV
Frankfurt (Germany), 6-9 June 2011 KOSTIAINEN– FI – S3– 0622 Case: The fault is isolated in 1 min [0 s] A fault occurs [1 s] remote re-closer operates [10 s] The system analyses and localizes the fault [1 min] remote controlled disconnectors isolate the end of the feeder 110 kV 20 kV
Frankfurt (Germany), 6-9 June 2011 KOSTIAINEN– FI – S3– 0622 Case: Back-up restoration in 2 min [0 s] A fault occurs [1 s] remote re-closer operates [10 s] The system analyses and localizes the fault [1 min] remote controlled disconnectors isolate the end of the feeder [2 min] remote controlled disconnector restores the power from another feeder 110 kV 20 kV
Frankfurt (Germany), 6-9 June 2011 KOSTIAINEN– FI – S3– 0622 Case: The service crew fixes the fault [0 s] A fault occurs [1 s] remote re-closer operates [10 s] The system analyses and localizes the fault [1 min] remote controlled disconnectors isolate the end of the feeder [2 min] remote controlled disconnectors restore the power from another feeder [~100 min] the service crew fixes the fault 110 kV 20 kV
Frankfurt (Germany), 6-9 June 2011 KOSTIAINEN– FI – S3– 0622 Case: Results 3 zones suffered an outage of <2min 1 zone suffered an outage of ~100 min Without the advanced system, the fault would have been located with time consuming trial & error method total outage ~200 min ~1 min ~2 min ~100 min 0 min 110 kV 20 kV ~1 min
Frankfurt (Germany), 6-9 June 2011 KOSTIAINEN– FI – S3– 0622 Accurate fault location, including also earth faults, is crucial for fast fault isolation Fast fault isolation enables fast power restoration SAIDI improvement Local automation confines the impact of a network fault to the limited area SAIFI improvement Utilize all ”senses” and use them to support each other. Conclusive statements
Frankfurt (Germany), 6-9 June 2011 KOSTIAINEN– FI – S3– 0622 Thank You for your attention