ECE 476 Power System Analysis Lecture 8: Transmission Line Parameters, Transformers Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.

Slides:



Advertisements
Similar presentations
Announcements Be reading Chapters 8 and 9
Advertisements

Twisted Pairs Another way to reduce cross-talk is by means of a twisted pair of wires. A twisted pair of wires will be modeled as a cascade of alternating.
EE 369 POWER SYSTEM ANALYSIS
ECE 530 – Analysis Techniques for Large-Scale Electrical Systems
EE 369 POWER SYSTEM ANALYSIS
Announcements Be reading Chapter 6. HW 3 is due now.
Lecture 3 Three Phase, Power System Operation Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
ECE 333 Renewable Energy Systems Lecture 14: Power Flow Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
ECE 333 Renewable Energy Systems Lecture 13: Per Unit, Power Flow Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois.
Announcements Be reading Chapters 1 and 2 from the book
Announcements Be reading Chapter 3
1 Voltage Collapse Animation (AC) Created by Peter W. Sauer Department of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
Lecture 8 Transmission Lines, Transformers, Per Unit Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
Lecture7 Development of Transmission Line Models Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
EE369 POWER SYSTEM ANALYSIS
Single Phase Transformer
1.6 Real Single-Phase Transformer.
Electrical Resistance and Ohm’s Law Electric circuits are used to convert electrical energy into some other form of energy we need.
ECE 476 Power System Analysis Lecture 6: Power System Operations, Transmission Line Parameters Prof. Tom Overbye Dept. of Electrical and Computer Engineering.
EE 369 POWER SYSTEM ANALYSIS
ECE 530 – Analysis Techniques for Large-Scale Electrical Systems
Announcements For lectures 8 to 10 please be reading Chapter 3
Announcements Please read Chapter 3 H4 is 4.34, 4.41, 5.2, 5.7, 5.16
ECE 476 Power System Analysis Lecture 7: Transmission Line Parameters Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois.
ECE 476 Power System Analysis Lecture 5:Transmission Line Parameters Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois.
Announcements Please read Chapter 4 HW 1 is due now
Crosstalk Crosstalk is the electromagnetic coupling between conductors that are close to each other. Crosstalk is an EMC concern because it deals with.
Power System Fundamentals EE-317 Lecture 3 06 October 2010.
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
Announcements Please read Chapter 3; start on Chapter 6
Announcements Homework #4 is due now Homework 5 is due on Oct 4
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye University of Illinois at Urbana-Champaign 1 Lecture 26: Modal Analysis,
ECE 476 Power System Analysis Lecture 11: Ybus, Power Flow Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
Announcements For lectures 9 and 10 please be reading Chapter 3
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
BASIC ELECTRICAL TECHNOLOGY Chapter 6: Single Phase Transformer
ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign
Lecture 13 Newton-Raphson Power Flow Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
ECE 476 Power System Analysis Lecture 17: OPF, Symmetrical Faults Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois.
Announcements Read Chapters 8 and 9 HW 9 quiz today
Announcements Please read Chapters 1 and 2
ECE 476 Power System Analysis Lecture 22: System Protection, Transient Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.
Announcements Read Chapters 10 and 11
ECE 476 Power System Analysis Lecture 12: Power Flow Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
ECE 476 Power System Analysis Lecture 14: Power Flow Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
Announcements Read Chapters 11 and 12 (sections 12.1 to 12.3)
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
ECE 476 Power System Analysis Lecture 18: LMP Markets, Symmetrical Faults and Components Prof. Tom Overbye Dept. of Electrical and Computer Engineering.
Lecture 24 Transient Stability Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
ECE 476 Power System Analysis Lecture 13: Power Flow Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
ENE 490 Applied Communication Systems
EKT 441 MICROWAVE COMMUNICATIONS CHAPTER 3: MICROWAVE NETWORK ANALYSIS (PART 1)
ELECTRICAL MACHINE DET 204/3 JIMIRAFIZI BIN JAMIL Transformer CHAPTER 1.
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye University of Illinois at Urbana-Champaign 1 Lecture 23: Small Signal.
Crosstalk Crosstalk is the electromagnetic coupling among conductors that are close to each other. Crosstalk is an EMC concern because it deals with the.
Announcements Please read Chapters 11 and 12
Announcements Please read Chapters 4 and 5 (skim 4.7, 4.11, 4.12)
Announcements Please read Chapter 6
Announcements Please read Chapters 4 and 5 Quiz today on HW 2
Announcements Please read Chapters 9, 10 and 11 HW 8 quiz today
Announcements Please read Chapter 3
Announcements For lectures 7 to 9 please be reading Chapter 5.
Announcements Please read Chapters 4 and 5
ECE 476 POWER SYSTEM ANALYSIS
ECE 476 Power System Analysis
ECE 476 Power System Analysis
ECE 333 Green Electric Energy
ECEN 460 Power System Operation and Control
ECEN 460 Power System Operation and Control
ECE 333 Green Energy Systems
Presentation transcript:

ECE 476 Power System Analysis Lecture 8: Transmission Line Parameters, Transformers Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign Special Guest Lecturer: TA Won Jang

Announcements Please read Chapters 5 and then 3 Quiz today on HW 3 H4 is 4.34, 4.41, 5.2, 5.7, 5.16 It should be turned in on Sept 24 (hence no quiz next week) 1

Leidos Engineering

Transmission Line Equivalent Circuit Our current model of a transmission line is shown below Units on z and y are per unit length! 3

Derivation of V, I Relationships 4

Setting up a Second Order Equation 5

V, I Relationships, cont’d 6

Equation for Voltage 7

Real Hyperbolic Functions For real x the cosh and sinh functions have the following form: 8

Complex Hyperbolic Functions For x =  + j  the cosh and sinh functions have the following form 9

Determining Line Voltage 10

Determining Line Voltage, cont’d 11

Determining Line Current 12

Transmission Line Example 13

Transmission Line Example, cont’d 14

Transmission Line Example, cont’d 15

Lossless Transmission Lines 16

Lossless Transmission Lines If P > SIL then line consumes vars; otherwise line generates vars. 17

Transmission Matrix Model Oftentimes we’re only interested in the terminal characteristics of the transmission line. Therefore we can model it as a “black box”. VSVS VRVR ISIS IRIR Transmission Line 18

Transmission Matrix Model, cont’d 19

Equivalent Circuit Model Next we’ll use the T matrix values to derive the parameters Z' and Y'. 20

Equivalent Circuit Parameters 21

Equivalent circuit parameters 22

Simplified Parameters 23

Medium Length Line Approximations 24

Three Line Models 25

Power Transfer in Short Lines Often we'd like to know the maximum power that could be transferred through a short transmission line V1V1 V2V I1I1 I1I1 Transmission Line with Impedance Z S 12 S 21 26

Power Transfer in Lossless Lines 27

Limits Affecting Max. Power Transfer Thermal limits – limit is due to heating of conductor and hence depends heavily on ambient conditions. – For many lines, sagging is the limiting constraint. – Newer conductors limit can limit sag. For example, in 2004 ORNL working with 3M announced lines with a core consisting of ceramic Nextel fibers. These lines can operate at 200 degrees C. – Trees grow, and will eventually hit lines if they are planted under the line. 28

Other Limits Affecting Power Transfer Angle limits – while the maximum power transfer occurs when line angle difference is 90 degrees, actual limit is substantially less due to multiple lines in the system Voltage stability limits – as power transfers increases, reactive losses increase as I 2 X. As reactive power increases the voltage falls, resulting in a potentially cascading voltage collapse. 29

Transformers Overview Power systems are characterized by many different voltage levels, ranging from 765 kV down to 240/120 volts. Transformers are used to transfer power between different voltage levels. The ability to inexpensively change voltage levels is a key advantage of ac systems over dc systems. In this section we’ll development models for the transformer and discuss various ways of connecting three phase transformers. 30

Transmission to Distribution Transfomer 31

Transmission Level Transformer 32