Introduction To Protective Relays This training is applicable to protective relaying and System Monitoring tasks associated with NERC Standards PRC-001.

Slides:



Advertisements
Similar presentations
1. Four LLs were published in February Transmission Relaying – Undesired Blocking 2.Lack of Separation for Critical Control Power Supply Leads.
Advertisements

Announcements Be reading Chapters 9 and 10 HW 8 is due now.
FAULT TYPE SELECTION Jeff Roberts April 6 and 9, 2005.
New Energy Horizons Opportunities and Challenges Fault Current Contributions from Wind Plants Dean Miller PacifiCorp July 25,
Submitted by: Name:Rajendra Kumar Choudhury Branch:Electrical Engg.
Transmission Operator Protection System Misoperations 2014 ERCOT Transmission Protections System Misoperations Data – 138kV and 345kV Combined (Not including.
GENERATOR PROTECTION.
1 Distributed Generation and Power Quality. 2 Relaying considerations DG infeed may reduce the reach of overcurrent relays –DG feeds fault, so utility.
EAS Lessons Learned Summary Lessons Learned Published in May 2014.
Protective Relaying Refresher
Power System Analysis/ Power System 1 EEE 4113/ EEE 3131
Direct Current Circuits
Material used:  Tin  Lead  Zinc  Silver  Antimony  Copper  Aluminum.
EKT214 - ANALOG ELECTRONIC CIRCUIT II
During a mains supply interruption the entire protected network is dependent on the integrity of the UPS battery as a secondary source of energy. A potential.
Disconnect Switches There are many purposes for disconnect switches in substations and power lines. They are used to isolate or deenergize equipment for.
Substations. Substations Chapter 4 Substations Major types of equipment found in most transmission and distribution substations with their purpose,
Chapter 7 SYSTEM PROTECTION
Chapter 22 Alternating-Current Circuits and Machines.
Chapter 27 Lecture 12: Circuits.
Chapter 18 Direct Current Circuits. Sources of emf The source that maintains the current in a closed circuit is called a source of emf The source that.
POWER SYSTEM PROTECTION
NETWORK OPERATING DIVISION Operating Effectiveness
Connections of a CT and a PT to supply, load and relay.
Electrical Distribution Training
TESTING AND COMMISIONING
Need for protection Power system must be kept in operation continuously without major breakdowns This can be achieved in two ways: 1.Implement a system.
Situational Awareness UPDEA - Workshop. Awareness of the Situation 25,623 Alarms in 8 Hours 53 Alarms / min (average) 80% Are consequential Things to.
Lecture 22 Unbalanced Faults and Power System Protection Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
Queensland University of Technology CRICOS No J Protection of distributed generation connected networks with coordination of overcurrent relays.
Protection & Switchgear
November 4, 2013 Topic: Electric Circuit Objectives:
Utility Engineers, PC.  Generation  Transmission  Distribution.
Introduction to Power Supplies
Introduction To Protective Relays
Lecture 22 Unbalanced Faults and Power System Protection Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
Announcements Read Chapters 10 and 11
1 Distributed Generation and Power Quality-Continued.
Electronic. Analog Vs. Digital Analog –Continuous –Can take on any values in a given range –Very susceptible to noise Digital –Discrete –Can only take.
Introduction to switchgears
NERC Lessons Learned Summary LLs Published in September 2015.
A PRESENTATION OF PRACTICAL TRAINING ON “400KV GSS “ \
A Presentation On 132 KV GSS BEHROR
SEMINAR PRESENTATION ON 220 KV GSS UDAIPUR
ON 400 KV GSS RAISER JAIPUR ROAD ,BIKANER
Department of Electrical Engineering
A Training Presentation On 132 KV GSS JAIPUR Submitted in partial fulfillment For the award of the degree of BACHELOR OF TECHNOLOGY Submitted To:- Submitted.
A SEMINAR ON 400 KV GSS(RRVPNL) BIKANER.
Submitted To:- Submitted By:- Mr.
Introduction To Protective Relays This training is applicable to protective relaying and System Monitoring tasks associated with NERC Standards PRC-001.
Introduction To Protective Relays This training is applicable to protective relaying and System Monitoring tasks associated with NERC Standards PRC-001.
Protection of Power Systems
Protection of Power Systems
April 7, 2015 Washington, D.C. Area Low-Voltage Event Operations Training Seminar 2016 Erik Johnson System Operations Training (ERCOT)
SYNERGY INSTITUTE OF ENGINEERING AND TECHNOLOGY
Technical Panel Session. Sunday January 11, DC System Failure Modes IEEE PES SBC Winter Meeting. January 11 – 15, New Orleans, LA Part 3.
  The traditional molded-case circuit breaker uses electromechanical (thermal magnetic) trip units that may be fixed or interchangeable.  An MCCB provides.
 The figure below shows a protection system for a transmission line, consisting of a CT, PT, a relay and its associated circuit breaker.
Power System Protective Relaying-Part One
6 Week industrial Training Presentation
STUDY OF ELEMENTS OF A 220/132/33KV SUBSTATION
Chapter 18 Direct Current Circuits. Sources of emf The source that maintains the current in a closed circuit is called a source of emf The source that.
Protection and Relay Schemes
Sub Station.
NERC Published Lessons Learned Summary
ELECTRICAL INSTALLATION AND MAINTENANCE (EIM) 5 INSTALL ELECTRICAL PROTECTIVE DEVICES FOR DISTRIBUTION, POWER, LIGHTING, AUXILIARY, LIGHTNING PROTECTION.
Chapter 7 System Protection
Considerations and Benefits of Using Five Zones for Distance Protection Ricardo Abboud, Jordan Bell, and Brian Smyth Schweitzer Engineering Laboratories,
Agenda Introduction of Protective Relays
Power System Protective Relaying-Part One
Presentation transcript:

Introduction To Protective Relays This training is applicable to protective relaying and System Monitoring tasks associated with NERC Standards PRC-001 and TOP-006

Learning Objectives Upon completion of the training, the participant will be able to: 1.Recognize the importance of batteries in protective relaying. 2.Identify the 3 basic purposes of protective relays 3.Differentiate between Primary and Backup relaying. 4.Distinguish what determines the zones of protection verses tripping zones.

Applicable NERC Standards PRC-001 System Protection Coordination R1. Each Transmission Operator, Balancing Authority, and Generator Operator shall be familiar with the purpose and limitations of protection system schemes applied in its area. TOP-006 Monitoring System Conditions R3. Each Reliability Coordinator, Transmission Operator, and Balancing Authority shall provide appropriate technical information concerning protective relays to their operating personnel.

Station Battery NERC’s definition of a Protection System includes: Station dc supply associated with protective functions (including batteries, chargers, and non-battery based dc supply) Associated Alarms Loss of AC to Battery Charger Low Battery Voltage Loss of DC

Battery Chargers Convert an AC source to DC, and maintain adequate charge on the batteries. Do NOT have the capacity to carry the full station DC load.

Protective Relay Principles Cannot prevent faults Proactive – pilot wire relays; temperature relays Reactive – relays that initiate action after fault occurs Use inputs from Monitoring devices Current, Voltage, Temperature, Pressure Initiates corrective action as needed to remove fault Minimize Damage from the fault by quick interruption The quicker the fault is removed, the less damage. Isolate Only the Faulted Area (Zone). Maintain Service to Other Areas (Zones) During and/or after Isolation of the Fault.

Protective Relay Principles Designed & utilized to protect against Faults. But could potentially trip due to loading in excess Facility Ratings or System Operating Limits (SOLs). It is incumbent on the System Operator to alleviate these conditions real time and Day ahead planners pre-contingency. Settings determined with system normal During System Restoration / Islanding events May not have enough fault current available to reach trip values. Have Switching Personnel monitor ammeters when closing devices. When closing by supervisory control, monitor ammeters on SCADA.

G5 G4G2G3 G1 G6 30Ω 10Ω 70Ω 40Ω 20Ω 25Ω Fault Current 25,000 Amps Fault Current 2,000 Amps G5 G4G2G3 G1 G6 30Ω 10Ω 70Ω 40Ω 20Ω 25Ω Black Start Reduced available fault current during blackouts can affect relay operation

Network verses Radial Radial One source - fault interrupting devices are in series with lateral feeds to customers. Distribution Circuits are typically radial. Network Dual or Multiple Sources The Transmission system is largely a Transmission Network. Relay coordination becomes more complicated and more expensive. Magnitude of current and Time Delay Direction of current Communication channels

Primary verses Backup Relays Primary relays are normally expected to operate first and trip breakers when faults occur within the zone they protect. Instantaneous on Transmission and EHV (>500kV) circuits Sub-transmission (<100kV) may or may not be instantaneous Depending on relaying used and location of fault Backup relays operate to clear around a CB that fails to interrupt a fault within a specific time period. Local Backup (7 – 15 cycles) Breaker Failure or Transfer Trip relays at the local station Remote Backup (20 – 30 cycles) Time Delay or Zone 2 relays at remote stations

Zones of Protection Defined by Current Transformers (CTs) that sense current flow into the zone. Each zone will have unique targets All primary equipment is included in at least one zone of protection. Overlapping ensures no equipment is left unprotected. A B C D RRRRRRRR Elm Ash Oak

Various Zones of Protection Overlapping occurs even when a CB is not present. Transmission bushing has 2 CTs

LOR Tripped By Numerous Relays Transformer and Bus differential zones shown. Both zones will still trip the same LOR. LOR (lock-out relay) trips Distribution CBs, Circuit Switcher XT1 and MOAB X1 R R RR R LOR Fault in Bus Zone of Protection Bus Targets and LOR Fault in Transformer Zone of Protection Transformer Targets and LOR Fault in Trans Circuit Zone of Protection (Includes Transformer Surge Arresters ) Line Targets

Potential Sources for Relays Some relays require a voltage/potential input in addition to the current input, to monitor the zone determined by the associated CTs. Do NOT define the zone of protection Should be attached close to equipment they protect Sources of Relay Potential Potential Transformer (PT) – Most accurate Coupling Capacitor Potential Device (CCPD) Coupling Capacitor Voltage Transformer (CCVT) Resistive Potential Device

Fundamentals of Relay Protection Potential for Relaying (cont.) Coupling Capacitor Potential Device. (CCPD) Coupling Capacitor Voltage Transformer (CCVT) Uses a series capacitor voltage divider principle. Typically used for relay potential 138 kV and above. CCVT is more accurate and has more capacity.

Potential for Relaying (cont.) Cascading of Capacitor cans All cans intact, each group has same impedance and voltage divides equally. If one can fails in a group, the impedance of that group increases. That group then has more of the voltage. More stress on cans in the group. As other cans fail, more voltage (and more stress) is on cans in the group, and cascading can occur. RELAY RPD

Overcurrent Relays Can be Instantaneous (50) or time-delayed (51) Can be non-directional or directional. Non-directional used on radial circuits Directional used on Network circuits Ground Relay Sees only imbalance current. Usually set lower than phase relay Ground target only on some faults Phase relays Phase relays must be set above load current. Use Undervoltage scheme where load approaches available fault current ΦΦΦ G Phase Relays Ground Relay A B C CB Fault

Undervoltage/OverCurrent Scheme A special scheme in which the over-current relays can’t operate unless low voltage indicates a fault. The Voltage Relay keeps the over-current relay coils shorted for normal voltage Removes the short to place the over-current relay coils in service when voltage is depressed due to fault conditions. Cheaper than adding Electro-Mechanical impedance relay UV Relay Trip Coil Tripping Relay Relay Coil

Instantaneous Clearing of Fault Only in Middle 80% Fault between Breaker “A” and point “X” INST target at Breaker “A” and Time target at “B” Fault between points “A” & “B” AC B INST TOC INST TOC INST TOC X Fault AC B INST TOC INST TOC INST TOC X Y Fault

Differential Relaying Operate when the power into a protected zone does NOT equal the power out of the protected zone. Basically - CTs algebraically add for paths into and out of the zone to cancel at the relay operate coil. The differential relay is preset to operate instantaneously when the difference that is seen by the relay exceeds its trip setting. Bus Zones (87B) Transformer Zones (87T) Generator Zones (87G)

Differential Relaying – External Fault Current into the Zone equals the current leaving the Zone Secondary current sums to zero at the operate coil 10A 87B AB 600/5 1200A 0A BUS Fault

Differential Relaying – Internal Fault Current into the zone does not equal the current leaving the zone Secondary current combines and goes through the operate coil of the relay 10A 87B AB 600/5 1200A 20A BUS Fault

Differential Relays Trip Lockout Relays The 87T trips the lockout relay which in turn trips the associated breakers. 87T AB 138 kV69 kV 1200/5600/5 600A1200A 5A 10A Fault 5A 86T/ 87XT

Lockout Relays When reset, burning light monitors the trip coil Older LORs, the light was wired separately from the relay When tripped, the light will go off, and a target flag will show The second light will burn when a relay is sending trip to the Lockout Relay Older LORs do not have the Standing Trip light Trip Ckt OK Tripped Position Standing Trip Reset Position

Lockout Relays Never hold lockout relay in reset position; or try to reset if standing trip light is on Trip Contacts Coil Latch Coil Contact

Impedance (Distance) Relays Sub-transmission circuits have high impedances Instantaneous overcurrent relays can be set for proper coordination. Impedances of circuits operated at 138kV and above are much lower Coordination with overcurrent relays is more difficult Impedance (Distance) relays use the secondary current and secondary voltage during a fault to calculate the impedance to the fault. Since the impedance per mile of the circuit is known, the impedance to the fault can be used to estimate the distance to the fault. If impedance to the fault is within the Zone 1 setting, an instantaneous trip occurs.

Impedance (Distance) Relays Zone 1 is instantaneous Typical setting is 80-90% Zone 2 has up to a 40-cycle delay Typical setting is % Zone 3 has up to a 90-cycle delay Typical setting is 200% Zone 2 150% Zone 3 Zone 1 90% 21 DC AB 50 miles 75 miles FE 25 miles HG

Impedance (Distance) Relays Instantaneous clearing only in middle 80% of circuit Zone 2 A 21 B C Zone 1 Zone 2 Zone 1 80% Source Z2Z2 Z1Z1 21 Zone 2 A 21 B C Zone 1 Zone 2 Zone 1 80% Source Z1Z1 Z1Z1 21

Directional Comparison Carrier Blocking Impedance relays (Z1, Z2, Z3) remain in service, and function as Backup Relays The Directional Comparison Carrier Blocking scheme uses a Zone-3 impedance relay with no time delay Communication channel used only to transmit a blocking signal for external faults Relays of CB B will send blocking signal to prevent CB A from tripping for a fault on circuit C - D. Z-3 Instantaneous DABC 21A 21B E

Directional Comparison Carrier Blocking When fault current is detected A blocking signal is transmitted ONLY for external faults No signal is transmitted for internal faults Trip occurs when a fault is detected and no blocking signal is received Wave Traps Reverse looking Carrier Start element Forward looking tripping element

Directional Comparison Carrier Blocking Multiple circuits (Fault on G-H) Carrier Relays for CBs _________________see fault into the circuit; and therefore will not transmit Carrier Relays for CBs _______________ see fault into the bus; and therefore will transmit CBs G and H trip because their respective relays see fault current into the circuit and no blocking signal was received. AB DC FE HG A,D,E,G,H B,C,F

Phase Comparison Phase comparison systems use only current for fault location (i.e. internal or external) Very desirable on lines with variable impedance, such as a line with switched series capacitor or series reactor compensation. Upon fault detection, the comparer logic relay compares the current at each terminal. If the phase angle and magnitude are within a preset comparison window, no tripping will occur. If the angle reverses at either end (signifying a 180 o power reversal, (which is indicative of an internal fault), the comparer will initiate trip of the breaker.

Phase Comparison External Fault The over-current fault detector relays see fault current but neither comparer sees a difference in phase angle. No trip occurs for Breakers 1 or 2

Phase Comparison Internal Fault The over-current fault detector relays see fault current. Comparers see a 180 o difference in phase angles. Trip occurs for Breakers 1 & 2

Transfer Trip Schemes Direct Transfer Trip (DTT) Also used for Breaker failure to trip remote breakers, lines terminated by transformers, and with shunt reactors. Direct Under-reach Transfer Trip (DUTT) Permissive Under-Reach Transfer Trip (PUTT) Permissive Over-Reach Transfer Trip (POTT) Most common TT scheme used for line protection Guard signal is transmitted constantly to check integrity of the Transfer Trip Channel. When a trip signal is needed, the signal is shifted from the Guard frequency to the Trip frequency. Used as backup to the two redundant primary relays on EHV

Direct Under-Reach Transfer Trip When under-reaching Zone 1 element detects a fault: Trips local CB instantaneously, and Sends Direct Transfer Trip signal to trip remote CBs Upon receipt of Direct Transfer Trip signal, CBs trip instantaneously with no other condition necessary Transfer trip signal important when fault is beyond Z1 TT R Z1

Permissive Under-reach Transfer Trip When under-reaching Zone 1 element detects a fault: Trips local CBs instantaneously, and Sends permissive Transfer Trip signal to relays at remote terminal. If relays at remote terminal see only a Zone 2 fault: The permissive signal will bypass the time delay and allow the CBs at the remote terminal to trip instantaneously. For faults in the middle 80% CBs at both terminals will trip instantaneously by Zone 1 Will also receive TT signal For faults beyond Zone 1 reach of one terminal Permissive Transfer Trip signal becomes very important

Permissive Under-reach Transfer Trip For a fault close to CB 2 Permissive Transfer Trip will set up instantaneous tripping of CB 1 Z1 Z2 TTR

Permissive Over-reach Transfer Trip More common as line protection scheme than other TT schemes. If the overreaching Distance Relay sees a fault, a permissive TT signal is sent to the other end. To trip instantaneously: The overreaching Distance Relay must see a fault, and Receive a permissive transfer trip signal from the opposite terminal.

Permissive Over-reach Transfer Trip For a fault at any point on the circuit Fault is seen by over-reaching element at both terminals Both terminals receive the permissive signal Both terminals trip instantaneously Over-Reach Zone of CB 1 Over-Reach Zone of CB 2 Distance Relay

Zone Designation Comparison GE and SEL both use Zone 2 to designate the Pilot tripping zone (60-cycle delay) Traditionally this zone was designated Zone 3 FunctionTraditionalGESEL Inst trip zoneZone 1Z1Z1P 30~ delay zoneZone 2Z3Z4P 60~ delay & Pilot zoneZone 3Z2Z2P Pilot Block (Reverse looking)No TargetZ4Z3P

SEL 421 Targets Targets can be labelled as each region desires

Summary Standards require Operators to have knowledge of relay systems Importance of DC system in Protection systems Digital relays emulate control and reclose switch positions Principles of relay protections Can’t prevent faults Three main purposes Quick interruption of faults For permanent faults, isolate only the faulted zone Use reclosing relays to restore as much of the system as possible after a fault Transmission relays set for fault current During blackout restoration, relay protection is compromised

Summary Primary and Backup relays Zones of Protection Targets indicate in which zone the fault was Zones overlap at a CB Potential sources for relays Overcurrent relays Differential relays Lockout Relays Impedance (Distance) Relays Zones 1, 2 and 3

Questions?