Grid connection of distributed generation

Slides:



Advertisements
Similar presentations
“Power Factor” In Transmission System
Advertisements

Beckett Energy Systems
An Electronic System Power Supply Example
Submitted by: Name:Rajendra Kumar Choudhury Branch:Electrical Engg.
Operational Amplifiers
Operational Amplifiers 1. Copyright  2004 by Oxford University Press, Inc. Microelectronic Circuits - Fifth Edition Sedra/Smith2 Figure 2.1 Circuit symbol.
QUALITY AND TECHNOLOGY
BRIDGES IMPEDANCE MEASUREMENT Experiment # 4 September 20, 2000 EE 312 Basic Electronics Instrumentation Laboratory Fall 2000.
Lecture 25 Pulse-Width Modulation (PWM) Techniques
ECE Electric Drives Topic 6: Voltage-Fed Converters Spring 2004.
Chapter 4 DC to AC Conversion (INVERTER)
Wind Turbine Session 4.
Chapter 12 RL Circuits.
EXPERIMENTAL STUDY AND COMPARATIVE ANALYSIS OF TRANSFORMER HARMONIC BEHAVIOUR UNDER LINEAR AND NONLINEAR LOAD CONDITIONS.
Ch 191 Chapter 19 DC Circuits © 2002, B.J. Lieb Giancoli, PHYSICS,5/E © Electronically reproduced by permission of Pearson Education, Inc., Upper.
Fundamentals of Power Electronics 1 Chapter 19: Resonant Conversion Chapter 19 Resonant Conversion Introduction 19.1Sinusoidal analysis of resonant converters.
Power Electronics Lecture-10 D.C to D.C Converters (Choppers)
Operational Amplifiers
Instrumentation & Power Electronics
Generator Protection. Amount of Protection Rated power of the generator Ratio of its capacity to the total capacity of the system Configuration of the.
Chapter 7 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
Chapter 8 Inverters AC Power • Inverters • Power Conditioning Units • Inverter Features and Specifications.
POWER SUPPILES LECTURE 20.
EKT214 - ANALOG ELECTRONIC CIRCUIT II
Chapter 5 Series Circuits.
Importance of advanced simulations of electrical system in wind turbines April 2010.
Chapter 22 Alternating-Current Circuits and Machines.
Power Electronics and Drives (Version ) Dr. Zainal Salam, UTM-JB 1 Chapter 3 DC to DC CONVERTER (CHOPPER) General Buck converter Boost converter.
Chapter 2 Operational Amplifier Circuits
ECE Electric Drives Topic 10: Cycloconverters Spring 2004.
9/27/2004EE 42 fall 2004 lecture 121 Lecture #12 Circuit models for Diodes, Power supplies Reading: Malvino chapter 3, Next: 4.10, 5.1, 5.8 Then.
ON DIMENSIONING LVDC NETWORK CAPACITANCIES AND IMPACT ON POWER LOSSES
Power Supply Design J.SHANMUGAPRIYAN.
RECTIFICATION Normal household power is AC while batteries provide DC, and converting from AC to DC is called rectification. Diodes are used so commonly.
Industrial Electrical Engineering and Automation Structures of the Energy flow system Mechatronics 2007.
UNIT-1 Rectifiers & Power Supplies. Rectifier A rectifier is an electrical device that converts alternating current (AC), which periodically reverses.
POWER QUALITY.
Chapter 7 AC Power Analysis
Control and Grid Synchronization for Distributed Power Generation Systems Z.Leonowicz, PhD F. Blaabjerg, R. Teodorescu, M. Liserre, and A. V. Timbus: Overview.
Microelectronic Circuits, Sixth Edition Sedra/Smith Copyright © 2010 by Oxford University Press, Inc. C H A P T E R 02 Operational Amplifiers.
10/11/2015 Operational Amplifier Characterization Chapter 3.
1 Fundamentals of Microelectronics  CH1 Why Microelectronics?  CH2 Basic Physics of Semiconductors  CH3 Diode Circuits  CH4 Physics of Bipolar Transistors.
Power System Fundamentals EE 317 Lecture 9 27 October 2010.
8-1 School of Electrical Systems Engineering ABD RAHIM 2008 EET421 Power Electronic Drives - DC to AC converter / Inverter Abdul Rahim Abdul Razak.
Instrumentation & Power Electronics
1 ELECTRICAL TECHNOLOGY EET 103/4  Define and explain sine wave, frequency, amplitude, phase angle, complex number  Define, analyze and calculate impedance,
Protection of Microgrids Using Differential Relays
Operational Amplifiers The operational amplifier, also know as an op amp, is essentially a voltage amplifier with an extremely high voltage gain. One of.
Introduction to Power Supplies
Electronic. Analog Vs. Digital Analog –Continuous –Can take on any values in a given range –Very susceptible to noise Digital –Discrete –Can only take.
Inverter power supply symptoms can be typically broken down into the following categories: 1. All Outputs Normal: 2. All Outputs Dead (no output): 3.
Closed Circuits In applications requiring the use of current, electrical components are arranged in the form of a circuit. A circuit is defined as a path.
1 Chapter 8 Operational Amplifier as A Black Box  8.1 General Considerations  8.2 Op-Amp-Based Circuits  8.3 Nonlinear Functions  8.4 Op-Amp Nonidealities.
TECHNICAL PAPER ON SIMULTANEOUS AC-DC POWER TRANSMISSION
Power System Protective Relaying-Part Two
Transformers. Single Phase Transformers Principles of Operation – Single Phase.
Chapter 12 RL Circuits.
Rectifiers, Inverters & Motor Drives
HARMONIC MITIGATION USING PASSIVE FILTERS
IG BASED WINDFARMS USING STATCOM
Islamic University of Gaza
Fault detection Lecture (3).
Wind turbine technology
Indian Grid Code and Commissioning Test Procedure Dr
Power Electronic Drives - DC to AC converter / Inverter
Switch-Mode DC-AC Inverters
Interconnection of AES With The Grid
CHAPTER 59 TRANSISTOR EQUIVALENT CIRCUITS AND MODELS
Presentation transcript:

Grid connection of distributed generation Vesa Väisänen

Requirements for power conversion The requirements for a power conversion unit arise from three major sources: Fuel cell (or any other power source) The supplied load or network General requirements such as economical constraints, efficiency requirements, expected operating life, standards, patents…

Load/Network requirements There is not yet a worldwide standard available to connect distributed generation systems to the grid. However, existing standards include references for example to responses to abnormal conditions, power quality and islanding. The relevant standards are: IEEE 1547 [1] UL 1741 [2] IEC 61727 [3] VDE 0126-1-1 [4] VDE-AR-N 4105 [5]

Load/Network requirements Abnormal operating conditions Tripping (disconnection) is required, if there are too large variations in the grid frequency or voltage. Tripping limits set by various standards, when installed power > 30 kW.

Load/Network requirements Abnormal operating conditions After the fault has been cleared, there are certain conditions under which the system can be reconnected to the grid. The reconnection conditions have been defined for the frequency and voltage.

Load/Network requirements Power quality Power quality depends mainly on the amount of harmonic currents and DC current component. Harmonic currents are current components that have a higher frequency than the fundamental grid frequency. The harmonic frequencies can be even or odd multipliers of the grid frequency. Harmonic limits for Class A equipment in Europe are listed in the lower table.

Load/Network requirements Power quality In an AC network having sinusoidal waveforms the average current is ideally zero. If the average is not zero, there is a DC current component involved. The DC current can lead to saturation in the distribution transformers. The limits for DC current injection are listed in the table below.

Abnormal operating conditions Types of faults Symmetric faults Asymmetric faults (typical faults) 3-phase short circuit 3-phase ground fault 2-phase short circuit 1-phase (or 2-phase) ground fault

Abnormal operating conditions Passive fault detection Power flow between the power plant, load and the grid during normal operation [6]: When the plant and the load disconnect from the grid, they are in islanding mode. If apparent power ∆P ≠ 0 after islanding, there is a change in voltage and the voltage protection detects it. If reactive power ∆Q ≠ 0 after islanding, there will be a phase shift in load voltage and the converters tries to compensate this by varying frequency until ∆Q = 0. The change in frequency can be detected by the frequency protection. If ∆P and ∆Q are small, these protections may not work!

Abnormal operating conditions Passive fault detection Asymmetric faults can be detected also from the voltage vector trajectory in α-β coordinates. During normal operation the grid voltage vector draws a circle (there is only a positive component rotating counterclockwise). During an asymmetric fault a negative component (rotating clockwise) appears. The sum of the positive and negative component draws an ellipse instead of a circle. A zero component would shift the trajectory origin. [6]

Abnormal operating conditions Active fault detection Active fault detection methods include the passive methods but also some active detection method. For example the converter can try to sway the grid frequency and/or voltage. If the grid frequency can be actively changed, the system is likely in an island with the load. The method can detect islanding also in situations, where ∆P and ∆Q are small after the grid is disconnected.

Abnormal operating conditions Operations during fault Large plants need to stay connected during short duration faults. Small plants may stay connected, if the internal protection functions allow. In an inverter using DC link voltage control and current control there are several ways to react to a network fault: Immediate disconnect. Not advisable since there may be false trippings. Keep the DC link power constant  phase currents increase in case of voltage drop  operate until overcurrent  disconnect Limit the phase currents and let the DC link voltage increase  operation with a DC link brake resistor  disconnect

Abnormal operating conditions Operations during fault Grid disconnect (seen as an open circuit for the grid converter) Grid synchronization is lost, fault is indicated by the grid converter  inverter shutdown DC link voltage tends to rise  activation of DC link brake resistor DC/DC input current reduces due to increased DC link voltage. Current control helps to prevent overloading  DC/DC shutdown Fuel cell stack emergency shutdown procedures Voltage limiting of low voltage DC link by active or passive means.

Abnormal operating conditions Operations during fault Grid short circuit (seen as a decrease in line voltage) Inverter phase currents increase to maintain DC link power balance  observe the current limits and trip if necessary. DC/DC input current needs to be controlled to avoid overloading. Fuel cell stack emergency shutdown procedures, if the power conversion unit trips  voltage limiting of low voltage DC link by active or passive means

Abnormal operating conditions Operations during fault Grid converter fault (short circuit, open circuit) Fault is indicated by the grid converter  DC link break resistor is activated (if operational) to limit the DC link voltage. DC/DC input current is limited by control  shutdown Fuel cell emergency shutdown procedures  voltage limiting of low voltage DC link by active or passive means.

Abnormal operating conditions Operations during fault DC/DC converter fault (short circuit, open circuit) Fault is indicated by the DC/DC converter. DC link voltage tends to decrease  decrease in grid converter line currents until shutdown. If the DC/DC converter transistors are operational  DC/DC input current is limited by control  shutdown If the transistors are not operational  current cannot be limited by control  possible overloading of the fuel cell stack Fuel cell emergency shutdown procedures  voltage limiting of low voltage DC link by active or passive means.

Abnormal operating conditions Operations during fault Fuel cell or low voltage DC link fault (short circuit or open circuit) Fault is indicated by the plant controller DC/DC converter and the grid converter can transfer power and provide voltage limiting of low voltage DC link. Fuel cell emergency shutdown procedures Shutdown of the DC/DC and grid converter.

Galvanic isolation Common-mode voltages In a symmetrical 3-phase system the sum of phase voltages is zero. In practice, the sum is not equal to zero  common mode voltage at the converter output terminals! Voltage fluctuation between the output terminals and some other point (for example the negative DC-bus) causes current flow through parasitic capacitances. Negative DC-bus Common-mode current path Example of a non-isolated PV-system [7].

Galvanic isolation Common-mode voltages In case of galvanic isolation the common-mode current route is blocked. Only route is through the transformer capacitances, which are typically small  even large voltage variations cause only small leakage currents. Transformer capacitances Example of an isolated PV-system [7].

Galvanic isolation Other advantages The voltage levels between different systems can be adjusted by the transformer turns ratio. A transformer isolates the power plant galvanically from the grid, thus isolating any line or ground faults to the faulty side. If the ground potentials of two systems are connected together and if there is any voltage difference between the ground potentials, there will be a large DC current (limited by the small cable resistance). A transformer will isolate the ground potentials and block any DC currents from flowing.

Summary Standards and grid codes need to be taken into account when connecting distributed generation to the grid. Faults can be detected by passive and active methods. Both methods require measurements of current, voltage and frequency. The only uncontrollable power electronics fault in terms of power plant current limiting is a DC/DC converter fault, where some the primary transistors or the input capacitors are short circuited. Galvanic isolation is used to limit ground currents, to provide voltage conversion and to provide safety during fault situations.

References [1] IEEE Std 1541-2003, IEEE Standard for Interconnecting Distributed Resources With Electric Power Systems, 1547, The Institute of Electrical and Electronics Engineers, Inc. New York, USA. [2] Underwriters Laboratories Inc (2001), UL741 Inverters, Converters, and Controllers for Use in Independent Power Systems, 741, Underwriters Laboratories Inc. (UL), IL, USA. [3] IEC (2004), IEC 61727 Ed. 2, Photovoltaic (PV) Systems - Characteristics of the Utility Interface, 61727, International Electrotechnical Commission (IEC), Geneva, Switzerland. [4] VDE Verlag (2006), Automatic Disconnection Device between a Generator and the Public Low-Voltage Grid, 0126-1-1, VDE VERLAG GMBH, Berlin-Offenbach. [5] VDE-AR-N 4105 (2011), Generators connected to the low-voltage distribution network - Technical requirements for the connection to and parallel operation with low-voltage distribution networks. [6] Purhonen, M. (2009). Verkkovaihtosuuntaajan säätö verkon erikoistilanteissa polttokennosovelluksissa. M.Sc. Thesis. Lappeenranta University of Technology, Finland. [7] Kerekes, T., Teodorescu, R., and Liserre, M. (2008). Common mode voltage in case of transformerless PV inverters connected to the grid. In: IEEE International Symposium on Industrial Electronics. pp. 2390-2395.

Thank you! Any questions?