Announcements Read Chapters 10 and 11

Slides:



Advertisements
Similar presentations
Announcements Be reading Chapters 9 and 10 HW 8 is due now.
Advertisements

Submitted by: Name:Rajendra Kumar Choudhury Branch:Electrical Engg.
Announcements Be reading Chapters 8 and 9
SYMMETRICAL COMPONENETS OF POWER SYSTEM
GENERATOR PROTECTION.
Announcements Be reading Chapter 6. HW 3 is due now.
CIGRE 7-10 September 2009, Moscow
Power System Analysis/ Power System 1 EEE 4113/ EEE 3131
ECE 333 Renewable Energy Systems Lecture 14: Power Flow Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
ECE 333 Renewable Energy Systems Lecture 13: Per Unit, Power Flow Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois.
Announcements Be reading Chapters 1 and 2 from the book
Announcements Be reading Chapter 3
EE 369 POWER SYSTEM ANALYSIS
Generator Protection. Amount of Protection Rated power of the generator Ratio of its capacity to the total capacity of the system Configuration of the.
Chapter 7 SYSTEM PROTECTION
EE369 POWER SYSTEM ANALYSIS
POWER SYSTEM PROTECTION
Announcements Please read Chapter 3 H4 is 4.34, 4.41, 5.2, 5.7, 5.16
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
Lecture 18 Markets, Fault Analysis Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
Announcements Please read Chapter 4 HW 1 is due now
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
Need for protection Power system must be kept in operation continuously without major breakdowns This can be achieved in two ways: 1.Implement a system.
Announcements Please read Chapter 3; start on Chapter 6
Lecture 18 Fault Analysis Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
Protection of Microgrids Using Differential Relays
Lecture 22 Unbalanced Faults and Power System Protection Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
ECE 476 Power System Analysis Lecture 11: Ybus, Power Flow Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
Queensland University of Technology CRICOS No J Protection of distributed generation connected networks with coordination of overcurrent relays.
Protection & Switchgear
ECE 476 Power System Analysis Lecture 8: Transmission Line Parameters, Transformers Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.
Announcements Read Chapters 8 and 9
Announcements Read Chapters 8 and 9 HW 9 quiz today
Announcements Please read Chapters 1 and 2
Lecture 22 Unbalanced Faults and Power System Protection Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
ECE 476 Power System Analysis Lecture 22: System Protection, Transient Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.
Announcements Read Chapters 11 and 12 (sections 12.1 to 12.3)
ECE 476 Power System Analysis Lecture 18: LMP Markets, Symmetrical Faults and Components Prof. Tom Overbye Dept. of Electrical and Computer Engineering.
Lecture 24 Transient Stability Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
ECE 476 Power System Analysis Lecture 13: Power Flow Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
1 ELECTRICAL TECHNOLOGY EET 103/4 Define and analyze the principle of transformer, its parameters and structure. Describe and analyze Ideal transformer,
Lecture 19 Fault Analysis, Grounding, Symmetrical Components Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM.
ECE 498HZ: Power Distribution System Analysis
Protection of Power Systems
Protection of Power Systems
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye University of Illinois at Urbana-Champaign 1 Lecture 23: Small Signal.
 The figure below shows a protection system for a transmission line, consisting of a CT, PT, a relay and its associated circuit breaker.
Power System Protective Relaying-Part One
Power System Protective Relaying-Part Two
Lecture 22 Power System Protection, Transient Stability Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
Hao Zhu Dept. of Electrical & Computer Engineering University of Illinois, Urbana-Champaign ECE 498HZ: Power Distribution System Analysis.
Protection and Relay Schemes
Announcements Design Project has firm due date of Dec 4
Announcements Please read Chapters 8 and 9
Announcements Please read Chapters 9, 10 and 11 HW 8 quiz today
Announcements Design Project has firm due date of Dec 4.
Protection of Power Systems
Announcements Please read Chapter 3
Announcements Please read Chapters 9, 10 and 11
ECE 476 POWER SYSTEM ANALYSIS
ECE 476 Power System Analysis
ECE 476 Power System Analysis
ECEN 460 Power System Operation and Control
ECE 476 POWER SYSTEM ANALYSIS
Chapter 7 System Protection
A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Power Plants By: Stephanie Mercer.
Agenda Introduction of Protective Relays
Power System Protective Relaying-Part One
ECE 476 POWER SYSTEM ANALYSIS
ECE 476 POWER SYSTEM ANALYSIS
Presentation transcript:

ECE 476 Power System Analysis Lecture 21: Unsymmetrical Faults, System Protection Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu

Announcements Read Chapters 10 and 11 Design project due date has been extended to Tuesday, December 8 A useful paper associated with the design project is T. J. Overbye, "Fostering intuitive minds for power system design," IEEE Power and Energy Magazine, pp. 42-49, July-August 2003. You can download it from campus computers at http://ieeexplore.ieee.org/xpl/abstractAuthors.jsp?arnumber=1213526

Unbalanced Fault Analysis The first step in the analysis of unbalanced faults is to assemble the three sequence networks. For example, for the earlier single generator, single motor example let’s develop the sequence networks 2

Sequence Diagrams for Example Positive Sequence Network Negative Sequence Network 3

Sequence Diagrams for Example Zero Sequence Network There is no zero sequence connection to the machines because of the D-Y transformers 4

Create Thevenin Equivalents To do further analysis we first need to calculate the thevenin equivalents as seen from the fault location. In this example the fault is at the terminal of the right machine so the thevenin equivalents are: 5

Single Line-to-Ground (SLG) Faults Unbalanced faults unbalance the network, but only at the fault location. This causes a coupling of the sequence networks. How the sequence networks are coupled depends upon the fault type. We’ll derive these relationships for several common faults. With a SLG fault only one phase has non-zero fault current -- we’ll assume it is phase A. 6

SLG Faults, cont’d 7

SLG Faults, cont’d 8

SLG Faults, cont’d With the sequence networks in series we can solve for the fault currents (assume Zf=0) 9

Line-to-Line (LL) Faults The second most common fault is line-to-line, which occurs when two of the conductors come in contact with each other. With out loss of generality we'll assume phases b and c. 10

LL Faults, cont'd 11

LL Faults, con'td Recall during this fault the b and c phase voltages are identical 12

LL Faults, cont'd There is no zero sequence current because there is no path to ground 13

LL Faults, cont'd 14

LL Faults, cont'd 15

Double Line-to-Ground Faults With a double line-to-ground (DLG) fault two line conductors come in contact both with each other and ground. We'll assume these are phases b and c. 16

DLG Faults, cont'd 17

DLG Faults, cont'd 18

DLG Faults, cont'd 19

DLG Faults, cont'd The three sequence networks are joined as follows Assuming Zf=0, then 20

DLG Faults, cont'd 21

Unbalanced Fault Summary SLG: Sequence networks are connected in series, parallel to three times the fault impedance LL: Positive and negative sequence networks are connected in parallel; zero sequence network is not included since there is no path to ground DLG: Positive, negative and zero sequence networks are connected in parallel, with the zero sequence network including three times the fault impedance 22

Power System Protection Main idea is to remove faults as quickly as possible while leaving as much of the system intact as possible Fault sequence of events Fault occurs somewhere on the system, changing the system currents and voltages Current transformers (CTs) and potential transformers (PTs) sensors detect the change in currents/voltages Relays use sensor input to determine whether a fault has occurred If fault occurs relays open circuit breakers to isolate fault 23

Power System Protection Protection systems must be designed with both primary protection and backup protection in case primary protection devices fail In designing power system protection systems there are two main types of systems that need to be considered: Radial: there is a single source of power, so power always flows in a single direction; this is the easiest from a protection point of view Network: power can flow in either direction: protection is much more involved 24

Radial Power System Protection Radial systems are primarily used in the lower voltage distribution systems. Protection actions usually result in loss of customer load, but the outages are usually quite local. The figure shows potential protection schemes for a radial system. The bottom scheme is preferred since it results in less lost load. 25

Radial Power System Protection In radial power systems the amount of fault current is limited by the fault distance from the power source: faults further down the feeder have less fault current since the current is limited by feeder impedance Radial power system protection systems usually use inverse-time overcurrent relays. Coordination of relay current settings is needed to open the correct breakers 26

Inverse Time Overcurrent Relays Inverse time overcurrent relays respond instan-taneously to a current above their maximum setting They respond slower to currents below this value but above the pickup current value 27

Inverse Time Relays, cont'd The inverse time characteristic provides backup protection since relays further upstream (closer to power source) should eventually trip if relays closer to the fault fail Challenge is to make sure the minimum pickup current is set low enough to pick up all likely faults, but high enough not to trip on load current When outaged feeders are returned to service there can be a large in-rush current as all the motors try to simultaneously start; this in-rush current may re-trip the feeder 28

Inverse Time Overcurrent Relays Current and time settings had been adjusted using dials on the relay Relays have traditionally been electromechanical devices, but are gradually being replaced by digital relays 29

Protection of Network Systems In a networked system there are a number of difference sources of power. Power flows are bidirectional Networked system offer greater reliability, since the failure of a single device does not result in a loss of load Networked systems are usually used with the transmission system, and are sometimes used with the distribution systems, particularly in urban areas 30

Network System Protection Removing networked elements require the opening of circuit breakers at both ends of the device There are several common protection schemes; multiple overlapping schemes are usually used Directional relays with communication between the device terminals Impedance (distance) relays. Differential protection 31

Directional Relays Directional relays are commonly used to protect high voltage transmission lines Voltage and current measurements are used to determine direction of current flow (into or out of line) Relays on both ends of line communicate and will only trip the line if excessive current is flowing into the line from both ends line carrier communication is popular in which a high frequency signal (30 kHz to 300 kHz) is used microwave communication is sometimes used; radio can also be used Security is a concern 32

Line Carrier Communication, Line Traps Line traps are connection in series with lines to allow the power frequency (50 or 60 Hz) to pass with low impedance but to show high impedance at the line carrier frequency Image source: qualitypower.com/line-trap.html 33

Impedance Relays Impedance (distance) relays measure ratio of voltage to current to determine if a fault exists on a particular line

Impedance Relays Protection Zones To avoid inadvertent tripping for faults on other transmission lines, impedance relays usually have several zones of protection: zone 1 may be 80% of line for a 3f fault; trip is instantaneous zone 2 may cover 120% of line but with a delay to prevent tripping for faults on adjacent lines zone 3 went further; most removed due to 8/14/03 events The key problem is that different fault types will present the relays with different apparent impedances; adequate protection for a 3f fault gives very limited protection for LL faults 35