Testing Fan Filter Units

Slides:



Advertisements
Similar presentations
AIR DISTRIBUTION (Additional information. Also see Chapter 18) General The proper delivery of air for heating, cooling, or ventilation is a crucial part.
Advertisements

1 Procuring a Design Project engineers perspective on starting the design process and establishing the A/E scope of work Frank C. Quigley General Engineer.
HVAC CONTROLS (See section 18.9)
Performance measurement
SUPPLY DUCT SYSTEMS (Additional information. Read sections 18.4, 18.5, & 18.6) General –The supply duct system conveys conditioned air from an AHU to the.
ASHRAE Chapter Meeting Acoustics in HVAC Design
Coupling a Network HVAC Model to a Computational Fluid Dynamics Model Using Large Eddy Simulation Jason Floyd Hughes Associates, Inc Fire + Evacuation.
VALIDATION OF HVAC SYSTEMS
Part F Practical Applications. 28. Fan-Cooled Enclosure of a PC System Physical System The physical system of interest is a fan-cooled enclosure containing.
Nonmetallic ducts (Additional information) –Fiberglass (also see section 18.5) Made of glass wool insulating material in which the stranded fiber wool.
AIR FLOW IN DUCTS Shaharin Anwar Sulaiman
Local Exhaust Hoods. 2 Introduction:  Designed to capture and remove harmful emissions from various processes prior to their escape into the workplace.
Siemens Building Technologies, Inc. ED&G 100 Design Project Fume Hood Face Velocity Control Spring 2004.
Airflow Properties & Measurement
Trevor Thompson Senior Project II Vermont Technical College Spring 2011.
System Effects Presented by: Joe Brooks, AMCA International, Inc. AMCA International Technical Seminar 2009.
ARCH-4372/6372 HVAC Distribution & Sizing HVAC Distribution Systems
1 Residential Air Filtration. 2 Residential Issues Cleaner Air –Removal of Particulates –Removal of Odors Maintain Airflow Customers Change Filters.
AMBIENT AIR FILTRATION IN THE WOODSHOP By Lou Gatch.
NAFA Guide to Air Filtration. Chapter 13 Owning and Operating Cost By Dirk ter Horst April 19 th, 2012 Another Approach…. Air Filter Comparison.
COMMERCIAL PAGING AND MUSIC SYSTEMS NBFAA CEU# CARL FOUTZ.
Design of Heat Sinks P M V Subbarao Mechanical Engineering Department IIT Delhi Success Based on Cooling Challenges …….
What is the difference between this two pictures
2007 ASHRAE Annual Meeting Conserving Natural Resource Use in Buildings William Tschudi – Tengfang Xu – Lawrence Berkeley.
FEASIBILITY OF COMPONENTS CLARA ECHAVARRIA & JONATHON LOCKE.
Copyright National Air Filtration Association 2006 Rev. 2 Clean Spaces.
Cleanrooms: Two promising research areas William Tschudi – LBNL Peter Rumsey – Rumsey Engineers November 4, 2004.
Air Ceiling Unidirectional ceiling air distribution system.
Houston Material Handling Society October 2008 Baghouse Cleaning Control Presented by: T.J. Winalski.
November Top Ten Approaches to Lowering Fan Energy in Cleanrooms.
Drafts and Duct System Sizing
Architectural Engineering Senior Thesis Mechanical System Redesign Saint Joseph Medical Center Chris Nicolais.
Alex Gee Jon Locke Joe Cooper Kylie Rhoades Clara Echavarria Ice Energy Extraction.
AIR FLOW IN DUCTS Shaharin Anwar Sulaiman
Objectives Describe room distribution basics Select diffusers
Informations and comments on ECE-TRANS-WP.29-GRB e 1 Louis-Ferdinand PARDO (France) Transmitted by the expert from France Informal document GRB
Objectives Finish with Duct Design Review the design procedure and explain the theoretical background Diffuser Selection Answer question related to the.
FLEXIBILITY = Tecniplast is ready and willing to satisfy all the customers needs and provide the right solution for a professional outcome STAND ALONE.
High Accuracy Lab in the Private Sector Doug Cooper.
 Market Survey  Design, supply, delivery and installation of a Clean Room Facility  at the entrance of the LAr detector tank,  used for the storage.
Day 1 Part 1 Technician’s Guide & Workbook for Home Evaluation and Performance Improvement.
Objectives Finish heat exchangers Air Distribution Systems
Clean rooms HVAC System
This is the final release: 13Jun09 Review: 15 June 2009 Brooke Gregory
Maryland Transportation Authority Police Training Facility
HVAC DUCT CONSTRCTION EXAMPLES
Maria’s Restaurant Lesson 21 Appendix C Duct Design
Sound Attenuator (UPC-26C)
Airflow Quantity and Velocity
Integrating Modeling and Physical Testing for Assessing Filtered Exhaust Stack Sampling Probe Location Xiao-Ying Yu, Kurtis P. Recknagle, John A. Glissmeyer,
Tengfang (Tim) Xu, Ph.D., PE Lawrence Berkeley National Laboratory
Maria’s Restaurant Chapter 4 Section 15
Design and Implementation of New Cleanroom for Tunnel Work
Media Velocity Panel vs Extended Surface
Presented by Harry C. Elinsky, Jr. Filtech, Inc.
Technician’s Guide & Workbook for Duct Diagnostics and Repair
In-Situ Filter Testing
NAFA Guide To Air Filtration
MECH 8250 – Building Systems Winter 2015
VENTILATION NOISE.
Applied Acoustics Dan Int-Hout, Chief Engineer, Krueger
Unico Installation Rules
HW4 Problem (Use TITUS Square Ceiling MCD diffuser
Sound Attenuator (UPC-26C)
Fan-Filter Testing - The Results Are In
High Performance HVAC Installation
Variability in 52.2 Testing
Mathematics of Air Filtration
Nafa Tech Seminar Phoenix Arizona 2004
Objectives Air Distribution Systems Duct design HW4.
Presentation transcript:

Testing Fan Filter Units Monroe A. Britt Manager, Research & Technology Clarcor Air Filtration Products Louisville, KY 502 969 2304 x1260 -- mbritt@clcair.com

Testing Fan Filter Units Objectives To develop procedure for testing Fan Filter Units that will be recognized and used by manufacturers, consultants, contractors, and end-users IEST has formed tentative Working Group to prepare Recommended Practice for publication First Meeting – Held November 4, 2003, Approx 15 Attendees Next Meeting – April at ESTECH – Las Vegas

Approach to Test Procedure Develop procedures that can be readily conducted in manufacturers facility or after installation of units in cleanrooms Instrumentation should be apparatus commonly used is the cleanroom industry Standardized Reporting Form Conduct blind “Round Robin” test program between various manufacturers and test labs to verify uniformity of test results

Testing Fan Filter Units Physical Size -- Up to 4 Ft. x 4 Ft. Units Test Parameters Air Flow – CFM Power (watts, amps, PF, volts) Available External Static Pressure Sound (pressure and power levels) Filter Air Velocity Uniformity - FPM Vibration

Air Flow - CFM Efficiency of Media -- HEPA Media, ULPA Media, ePTFE Media Pack -- Depth of Pack & Pleat Spacing Pre-Filters Various Efficiency Levels of Particulate Filters Gas Phase Filters Room/Enclosure Pressurization and Exit Losses Inlet Duct Connections & Duct Work Height of Plenum above FFU Air Inlet Current -- 50 or 60 Hertz Acoustical Packages Other Variables

Air Flow - CFM Required Air Flow Expressed as Velocity -- FPM Expressed as Volume -- CFM CFM = Area x FPM Area is Active Flow Area of Filter (Typical 2 x 4 filter Without Center Bar Contains 7.15 Ft2 of Active Filter Flow Area) CFM at 90 FPM 90 FPM X 7.15 Ft2 = 640 CFM

Fan Filter Unit (FFU) FFU’s Without Constant Flow Control AC Units ECM Units FFU’s With Constant Flow Control

Air Flow - CFM vs Static Pressure Test Plenum Resistance (Pre-Filter) Fan Housing Static Pressure Tap Watt Meter Filter Flow Hood Measure CFM Static Pressure Watts, Amps, PF, Volts Transition Needed For 4 x 4 FFU

Air Flow - CFM vs External Static Pressure FFU’s w/o Constant Flow Control HEPA Filter ULPA Filter Pressure - Inches W.G. ULPA Filter w/Pre-Filter No Scale Air Flow - CFM

Air Flow vs Watts FFU’s w/o Constant Flow Control ULPA Filter w/Pre-Filter ULPA Filter Power Consumption – Watts HEPA Filter No Scale Air Flow - CFM

Air Flow - CFM vs External Static Pressure FFU’s with Constant Flow Control HEPA Filter ULPA Filter Pressure - Inches W.G. ULPA Filter w/Pre-Filter No Scale Rated Air Flow Air Flow - CFM

Air Flow vs Watts FFU’s with Constant Flow Control ULPA Filter w/Pre-Filter ULPA Filter HEPA Filter Power Consumption – Watts No Scale Air Flow - CFM

Air Flow---Power---Static Pressure Minimum Reporting Data Complete Description of Fan Unit, Final Filter, and Pre-Filter -- Part Numbers, Construction Codes, etc Nominal Rated Air Flow Air Flow - CFM Watts, Amps, Power Factor, Volts, Hertz Available External Static Pressure Dimensions and Active Filter Flow Area

Sound Pressure and Power Levels Background Levels -- Recorded as First Step Sound Pressure Levels -- To be Measured as Overall dBA, Overall dBL, and as dBL for Octave Bands -- Used to Report Sound Levels and Establish NC Curves for One Fan Filter Unit Installed in Typical Operating Environment Sound Power Level -- To be Determined as Overall dB and as dB for Octave Bands -- Used by Acoustical Engineers to Predict Sound Pressure Levels in Actual Operating Environments. These Calculations Will Consider Number of FFU’s, Location of FFU’s and Sound Characteristics of Materials, Equipment, and Other Activity in the Individual Cleanroom

Sound Pressure Level Test Environment --- 8 x 8 x 8 Soft Wall Room Mic Acoustical Tiles 3 ft. Mic Location 8 Ft. 7 Ft. Concrete Floor - No Covering

Sound Pressure Levels Minimum Reporting Data Complete Description of Fan Unit, Final Filter, and Pre-Filter -- Part Numbers, Construction Codes, etc Nominal Rated Air Flow Background Sound Pressure - dBL & dBA Background Octave Band Sound Pressure - dB Overall Sound Pressures -- dBL & dBA Octave Band Sound Pressures – dB

Sound Power Level Test Environment --- 8 x 8 x 8 Soft Wall Room Acoustical Tiles 3 In. Plane of Mic Locations 8 Ft. 7 Ft. Concrete Floor - No Covering

Sound Power Levels Sub-divide active filter area into equal square areas, maximum of 12” x 12”, minimum of 4 areas/filter Measure overall sound levels for center points Average all sound levels measured -- LP Compute Sound Power Level for FFU -- LW LW = LP + 10 Log (S1/S0) LW = Sound Power Level, dB re 10 -12 Watts LP = Sound Pressure Level, dB re 10-5 N/m2 S1 = Total Area of Measurement Surfaces - m2 S0 = 1.0 m2

Sound Power Level Minimum Reporting Data Complete Description of Fan Unit, Final Filter, and Pre-Filter -- Part Numbers, Construction Codes, etc Nominal Rated Air Flow Grid with Measured Values – dB Average of Measured Values -- dB Calculated Overall Sound Power -- dB

Air Velocity Uniformity Sub-divide active filter area into equal square areas, maximum of 12” x 12”, minimum of 4 areas/filter Measure center point velocity for each area at 6 inches downstream of filter or protective grid Take measurements for minimum of 5 seconds, using apparent average during that period as value for reporting

Air Flow Uniformity Minimum Reporting Data Complete Description of Fan Unit, Final Filter, and Pre-Filter -- Part Numbers, Construction Codes, etc Nominal Rated Air Flow Grid with Measured Values – FPM Standard Deviation of Measured Values

Vibration “Site Under Construction” Current Plans Mount FFU in stiff aluminum frame that will simulate proper sized ceiling grid Suspend frame by flexible cables Measure vibrations at corner of frame Comments/Input Solicited

Future Activity Complete “Working Draft” of Proposed RP Develop Comprehensive Data Reporting Form Distribute Draft to First Meeting Members and All Interested Parties Solicit Comments and Recommendations IEST Working Group Next Official Meeting April 25 – 28 , 2004 Riveria -- Las Vegas, NV WG 036 Meets On April 26 at 8:00 AM