BUrners TRAining CEntre CONTROL BOX RMO88.53
BUrners TRAining CEntre PRESS SERIES ONE STAGE TWO STAGE THREE STAGE Dedicated to: RL SERIES ONE STAGE TWO STAGE Light oil burners
BUrners TRAining CEntre PRESS SERIES TWO STAGE THREE STAGE RN SERIES TWO STAGE Dedicated to: Heavy oil burners
BUrners TRAining CEntre FEATURES MODELS RMO88.53A2RMO88.53A1 Main voltage…………….…...AC V +10% -15%AC V +10% -15% Frequency…………….… Hz +/-6% Under Voltage protection…...Approx. AC 170 VApprox. AC 70 V Primary fuse…………….…...Max 16 A Power consumption……..…...20 VA Internal fuse…….……..…...T6.3H250V (IEC )T6.3 Polarity...………….……..…...To be observed Flame signal (photoresistence) >450 K (pre-purge) <200 K (operation) >450 K (pre-purge) <200 K (operation) Mode operation………….…...Intermittent
BUrners TRAining CEntre Timings of cycle RMO88.530A2RL RMO88.530A1RL NOTES Waiting time………….…...2 sec…………………………..Beginning when both # 4 & # 8 are energised. If not input to # 4 within 600 sec since # 8 is energised lock out Pre-purge time (min)….…...23 sec…………………………. Pre-ignition time………….…...22 sec………………………... Ignition safety time……..…...5 sec Interval 1st 2nd stage..…... 7 sec………………………….Interval between # 10 # 13 outputs Post-ignition time……….…...5 sec(max) Interval 2st 3rd stage..…... 7 sec…………………………...Interval between # 13 # 14 outputs Interval between # 11 # 10 outputs Interval between # 12 # 10 outputs
BUrners TRAining CEntre CONTROL PROGRAM IN EVENT OF FAULT
BUrners TRAining CEntre INDICATION OF OPERATION
BUrners TRAining CEntre Operating concept Burner control has initiated lockout Red fault LED on ResetPress lockout reset button for about 1 s Diagnosis of cause of fault– Press lockout reset button for > 3 s – Read blink code of red fault LED «Error code table A» SELF-DIAGNOSTIC
BUrners TRAining CEntre Error code table A Blink code Possible cause 2 x No establishment of flame at the end of ignition safety time – Faulty or soiled flame detector – Faulty or soiled fuel valves – Poor adjustment of burner – Faulty ingnion equipment 4 x Extraneous light during pre-purging – Or internal device fault 7 x Loss of flame during operation – Poor adjustment of burner – Faulty or soiled fuel valves – Faulty or soiled flame detector 8 x Time-out release contact for oil pre-heater does not close 10 x Wiring error or internal fault, output contact, unidentifiable fault, e.g. faults that occurred simultaneously