Electrical Machines LSEGG216A 9080V
Transformer Operation Week 4
Transformer Operation V+ CIVIL VoltageCurrent Magnetic Flux
Transformer Operation Applied Voltage Induced Voltage Induced Voltage in Secondary Resultant Current V1V1 V’ 1 V’ 2 IMIM
Induced Voltage Φ max =Maximum instantaneous flux F = Frequency N = Number of turns B max = Maximum permissible flux density in Wb A = CSA of core in m 2
Transformer Operation V1V1 IMIM IeIe IoIo I e = Iron loss current I o = No load current
V1V1 V’ 1 V’ 2 IoIo I’ 2 I’ 1 I1I1
Transformer Operation V1V1 V’ 1 V’ 2 IoIo I’ 2 I’ 1 I1I1
Transformation Ratio Magnetic flux is common coils Therefore the voltage can be varied by changing the number of turns
V1=V1=N1N1 N2N2 V2=V2= = k = Transformation Ratio
Transformation Ratio V 1 x I 1 N1N1 N2N2 =V 2 x I 2 = I1I1 I2I2
Transformation Ratio V 1 x I 1 VA V 2 x I 2 kVA Power InPower Out
Transformation Ratio V 1 x I 1 V 2 x I 200V100V 400 K = 2
Voltage Regulation E I Voltage Drop Due to R Voltage Drop Due to X L V Resistance Inductance Coils have both
Voltage Regulation E I V Lagging PF of 45 V less than E
E I V Leading PF of 45 V More than than E
100 x V No Load – V Full Load V Full Load R% = If PF = Unity 100 x I x (R x cos + X L x sin ) V Full Load R% =
Transformer Basic Tests Open Circuit Test Short Circuit Test Oil Tests Electrical Insulation Polarity Continuity
Open Circuit Test Used to determine Iron Losses Supply = Rated Voltage
Wattmeter reading V1V1 IMIM IoIo IeIe Supply Voltage Ammeter reading
Short Circuit Test Used to determine Copper Losses Supply Adjusted = Rated Secondary Current