Network infrastructure for CERN DataCenter HEPiX Fall 2015
Agenda Needs Situation Options Implementation Questions HEPiX Fall
Needs Support 40GbE, 100GbE and more Still available for 10GbE Also for low bandwidth (PDU, Management) High availability and reliability HEPiX Fall
Needs Supporting 40G, 100G and more imply At least OM3 optical infrastructure At least MPO connectors HEPiX Fall
Needs 10GbE compatible imply : LC connectors Convert MPO to LC Copper (Cat6A …) HEPiX Fall
Needs Low bandwidth for management and PDU Copper is enough HEPiX Fall
Needs High availability and reliability Respect of installation methods HEPiX Fall
Needs HEPiX Fall High availability and reliability Respect of installation methods Cabling organization
Needs HEPiX Fall High availability and reliability Respect of installation methods Cabling organization Operation methods “Inspect before you connect !”
Situation Old infrastructure Copper from 1995 OM2 Racks Extension of the DC locally but also in Wigner site HEPiX Fall
Options Copper Which use ? Management and PDU May come the need for 10G uplink HEPiX Fall
Options Optical fiber quality OM3 allow 100GbE over 100m OM4 allow 100GbE over 150m HEPiX Fall
Options Connector MPO, LC, … ? MPO-12 or MPO-24 ? What about MTP ? HEPiX Fall
Options Optical cabling type A, B, C, …? key up, key down ? HEPiX Fall
Options Type A HEPiX Fall
Options Type B HEPiX Fall
Options Type C HEPiX Fall
Options Module type 1 MPO to 12 LC ? 2 MPO to 24 LC ? How many fiber per trunk and per chassis ? HEPiX Fall
Options Cable type A same MPO to LC module but different patches HEPiX Fall
Options Cable type B same patches but different MPO to LC module HEPiX Fall
Options No type C if you want more than 10GbE ! HEPiX Fall
Options Same patches and same MPO to LC module Patented solution HEPiX Fall Manufacturer dependent solution
Implementation Aggregation and ToR switches for Management ToR Data switches HEPiX Fall
Implementation HEPiX Fall Infrastructure every 3 or 5 racks New copper in new rooms Old copper cabling reused for management and PDU
Implementation OM4 72 fibers with MTP-12 Type B HEPiX Fall