ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.

Slides:



Advertisements
Similar presentations
Electrical Circuits.
Advertisements

CricketSat Assembly.
EE188L EE I Laboratory Lab #2 Resistive Circuits.
ADT490 TroubleShooting Locating Grounds A. 2 Introduction ‣ Fire Alarm Panels cannot tolerate grounds ‣ A ground on any fire alarm circuit is detected.
Trouble - Shooting ELR - Electric Latch Retraction.
ADT490 TroubleShooting Locating Grounds A. 2 How are the Circuits Installed ‣ Before looking for the actual location of a fault on a circuit, look at.
Which type of circuit has more than one path for electricity to flow?
Register Digital Multimeter Usage Click Register to begin the course.
MICROCONTROLLERS MODULE 2 Programming, Controlling and Monitoring.
Using a Multimeter.
Landing and Taxi Lights Anti-collision Lights Navigation Lights Cockpit and Cabin Lights Instrument Panel Lights Click on a System Link to Start.
March 2004 Multimeters How to use them. March 2004 The Multimeter We have black and yellow ones – the black ones are the ‘newest’… Some of the yellow.
Colorado Space Grant Consortium Timing Circuit HW #4 Class #07 Timing Circuit HW #4 Class #07.
California Friendly ® Landscape Training Irrigation System Troubleshooting The Metropolitan Water District of Southern California and the Family of Southern.
Residential Wiring Facts
Embedded Programming and Robotics Lesson 1 Basic Electricity and Electronics Transistor Basics Lesson 1 -- Basic Electricity1.
Charging System Service
Register Digital Multimeter Usage Click Register to begin the course.
MElec-Ch1 - 1 Chapter 1 Properties of Electricity Properties of Electricity.
Register Digital Multimeter Usage Click Register to begin the course.
1 INTRUSION ALARM TECHNOLOGY CABLING FOR BURGLAR ALARMS.
INTRUSION ALARM TECHNOLOGY
+ -. Methode Connector  This is the standard USGS connection for the DCP.  Some manufacturers do not recommend using a methode connector. However, we.
PRACTICAL ELECTRICITY
RP-2000 Series Deluge & Agent Releasing Panels
Troubleshooting Electric Control Devices
Solar Energy Station Directions. Making a Solar-Powered Circuit 1.Make sure your solar panel is in direct sun. 2.Get the clear LED bulb. 3.Use a red jumper.
 Four Components of a circuit  Power supply  Conductor  Load device  Controlling device  Power Supply  Generator  Line source (wall outlet)  Transformer.
Using a DVOM.
ADT490 TroubleShooting Introduction to Troubleshooting.
7.1.3 Student Book © 2005 Propane Education & Research CouncilPage Applying a Systems Approach to Gas Appliance Troubleshooting Troubleshooting.
ADT490 TroubleShooting Device Failures. 2 Introduction ‣ Many problems are external to FAS ‣ Many are device problems.
Wiring the Control Box Battery Conductor(s) Resistor.
BOOT MODE 1 BOOT MODE 2 BIOS COMMUNICATION DEFAULT CONTROLLER INVERT RELAY OPERATION ENABLE COMM FAIL RELAY CONTROL RELAY OFF / ON COMM.
Register Digital Multimeter Usage Click Register to begin the course.
Electronics Series Resistive Circuits 1 Copyright © Texas Education Agency, All rights reserved.
1 Basic Electrical Series and Parallel Circuits. 2 Introduction So far we have looked at circuits that have one path for electricity to go as well as.
2 nd ESO - TECHNOLOGY DEPARTMENT. WE USE CIRCUITS… At Home In Cities In Industry.
ADT490 TroubleShooting Locating Opens. 2 Power Supply Grounding Power Supply has circuit -> allows positive & negative outputs to float relative to ground.
 An electric circuit is a complete, closed path through which electric charges flow.  A circuit always begins and ends in the same place. It ends in.
Unit 5 Learning Objective(s) L5.1a To understand the need for safe working practices when carrying out practical electronics L5.1b To understand relevant.
 Source of voltage difference ◦ Battery, outlet  At least one device that uses the electrical energy ◦ Radio, microwave, clock, etc  Conductor that.
ADT490 TroubleShooting Grounds. 2 Prior to Troubleshooting ‣ Before starting to work on the FACP, what do you do? 2.
ADT490 TroubleShooting Locating Opens B. 2 Review a Circuit 2 Before we start to investigate a Trouble condition caused by a circuit fault, we should.
ADT490 Panel Theory. 2 System Power Supply Grounding ‣ Circuit separates positive / negative from Ground ‣ Ground fault - resistance to ground ≤ 10 kΩ.
FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model Amps9 Amps.
Basic Equipment and Schematic Reading. Objectives Learn the basic equipment that will be used in the Lab. Learn some of the basic symbols used on electrical.
The Basics Electronics. To familiarise yourself with electronics To have an understanding of how and why we test electronic circuits. To complete a test.
In this lesson, you will learn how to set up a Digital Multimeter (DMM) to perform various measurements Click on each question to learn more How is the.
Electricity. What is electricity? Is the movement of electrons from atom to atom. Some substances have atoms that allow electrical flow, others do not.
Using electrical Test Equipment To accompany the Georgia Agriculture Curriculum Course: AG-AG-AMII Using Electrical Test Equipment 2010 VGP.
BASIC ELECTRICITY AND MAGNETISM
© NTScience.co.uk 2005KS3 Unit 7j - Circuits 1 Circuits.
Electrical Current & Circuits. Components of an electrical circuit Source of electrical energy (battery) A conductor of electrical energy (wire) Device.
Using a Multimeter.
ELECTRICAL CIRCUITS Multimeter.
Introduction to Handshaking Communication with SSC-32U
GROUND-FAULT GROUND-CHECK MONITOR
Introduction to Handshaking Communication with SSC-32
Parallel and Series Circuits
DC Circuit Analysis Experiment - 4
Circuits Lecture 3.
22 Chapter Basic Electrical Tests. 22 Chapter Basic Electrical Tests.
Electric Circuits Ch 17, section 4.
Electrical components and systems
FIRE ALARM DRILL 26 © Ted Smith 2017.
Presentation transcript:

ADT490 TroubleShooting Locating Opens A

2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System Trouble LED is lit. Open on a conventional Initiating circuit Yellow Zone LED -> on

3 Introduction ‣ Open on signal circuit indicate ‣ circuit is Open ‣ “Circuit” or “NAC” yellow LED ‣ System Trouble ‣ LED ‣ Buzzer 3

4 Introduction ‣ Class B Initiating circuit : 4

5 Typical Input Circuit ‣ Continuous power ≅ 24 Vdc ‣ EOL Installed after last device ‣ Regulates current ≅ 5 to 6 mA ‣ Current called -> supervisory current ‣ Break -> current stops -> 0 mA ‣ Sketch – why no supervisory current ‣ Insert Multimeter (series) at FACP, set to mA -> 0.0 mA ‣ Insert Multimeter (parallel) at FACP, set to V -> 25 Vdc 5

6 Typical Input Circuit ‣ Break -> ome devices still operate ‣ If 1st device is a Manual Station Operated ‣ Places short on circuit prior to break (still powered) ‣ Causes Alarm Condition ‣ Remaining three devices electrically disconnected ‣ Cannot cause Alarm ‣ Devices panel side of break – function ‣ Device on EOL side of break - inoperable 6

7 Simple Exercise - 1 ‣ Example of using senses, logic and DMM to find an open circuit in a simple Class B circuit ‣ Imagine the circuit in Trouble is on Zone 2 on a 4 Zone FACP ‣ In this Apartment Building Zone 2 is the entire Second Floor 7

8 Simple Exercise - 2 8

9 Simple Exercise - 3 ‣ Wire disconnected somewhere on this circuit. ‣ “ Disconnected ” implies what type of a circuit fault? ____________________________ ‣ What will FACP to tell us? 1)_____________________________ 2)____________________________ 9

10 Simple Exercise - 4 Visit 2 nd floor. ‣ What will suggest where the open has occurred? 1)_______________________________________ 2)_______________________________________ 10

11 Simple Exercise - 5 The raceway layout might look like this: 11

12 Simple Exercise - 6 After a visual inspection ‣ open location not obvious (hanging device, damage caused by renovation or repair, etc.), and ‣ will probably require some meter work to locate it. ‣ Visual inspection suggests problem -> middle to end of circuit 12

13 Simple Exercise - 7 What clue(s)? Remember: “ Any device on the panel side of a break in a Class B circuit will continue to work, while any device after the break is inoperable ”. 1)____________________________________ 2)____________________________________ 13

14 Simple Exercise - 8 Inspection -> both hallway smokes flashing LEDs First Manual Station worked Last one did not. Let ’ s look at the circuit again: 14

15 Simple Exercise - 9 Open circuit has occurred between the last smoke detector and last Manual Station. we haven ’ t to access into any suites. 15

16 Simple Exercise - 10 ‣ Convenient test point is second smoke because: __________________________________and, because of the way the conduit is run, we can_______________________________ 16

17 Simple Exercise - 11 Remove the second smoke & Check with Meter 17

18 Simple Exercise - 12 Meter to conductors into octagon-box from the FACP. What should meter be set for? _______________________________ What reading is expected (app.)?______________________________ 18

19 Simple Exercise - 13 We got what we were looking for Look the other way down the circuit to the EOL. Locate other two wires removed from smoke detector. 19

20 Simple Exercise - 14 Do we leave the meter as previously set?________________ What setting is going to be helpful? ________________ If this part good (pretty sure it isn ’ t) What read should we expect? (app.)? _______ With circuit open between Test Point and the EOL What reading will you get? _____________________ 20

21 Simple Exercise - 15 Wiring looks like this: 21

22 Simple Exercise

23 Simple Exercise - 17 Open is between octagon box and the EOL. 23

24 Simple Exercise - 18 Resistance reading of 4.8 kΩ, seeing EOL. Open is not between the octagon box and the EOL. Open has seemingly between the heat detector in suite 203 or the heat detector in suite

25 Simple Exercise - 19 Remove remaining Marrettes and short together RED and BLACK going to Suite 204. Put your DMM (on resistance) across the returning blue and brown wires. If shorted (0 Ω) -> the wires intact & connected to the detector -> wires to Suite 204 OK 25

26 Simple Exercise

27 Simple Exercise - 21 Apply same routine and find there is an open -> DMM ’ s resistance is infinity. 27

28 Simple Exercise

29 Simple Exercise - 23 Access 203 Dismount the detector & Blue wire broken off detector ’ s terminal screw, -> causes open circuit. Re-strip & re-connect blue wire Remake the connections in the octagon box Re-mount the heat detector. Check to see that the FACP is clear. 29

30 Discussion How to troubleshoot an open on a Class A circuit? Typically a Class A looks like this: 30

31 Discussion 1) There are 4 wires associated with the Class A “ loop ”, 2 leaving the panel and 2 returning. 2) The EOL function is inside the FACP. 3) The circuit is actually working like a Class B loop, in the normal mode. 4) The arrows represent 2 “ switches ” that are “open state” 31

32 Discussion When open occurs relay causes switches to close Feeds the voltage to the other side of the open 32

33 Discussion An open/break occurred. 1) FACP senses drop in current on loop and closes the two “ switches ” (as indicated by the arrows). 2) Now we have +24VDC being supplied to the 4 th terminal, and the 0VDC reference being supplied to the 3 rd terminal. 3) The FACP is now back feeding the operating voltage and current to the devices beyond the break. 4) ALL DEVICES CONTINUE TO FUNCTION. 33

34 Discussion All devices work -> smoke detectors flash LED ’ s -> location of break more difficult to find 34

35 end of presentation