1 Monophase Measurements on Prototype Pixel Structures D. Bintinger, M. Gilchriese, J. Taylor and J. Wirth and contributions from D. Cragg, E. Perrin and.

Slides:



Advertisements
Similar presentations
Heat Transfer to Solids in a Flowing Fluid
Advertisements

Estimation of Convective Heat Transfer Coefficient
So Far: Conservation of Mass and Energy Pressure Drop in Pipes Flow Measurement Instruments Flow Control (Valves) Types of Pumps and Pump Sizing This Week:
Chapter 4.2: Flow Across a Tube Bundle Heat Exchanger (Tube Bank)
Chapter 3.2: Heat Exchanger Analysis Using -NTU method
Chapter 2: Overall Heat Transfer Coefficient
Example 1:- An annular alloyed aluminum (k = 180 W/m . K ) fin of rectangular profile is attached to the outer surface of a circular tube having an outside.
Internal Flow: Heat Transfer Correlations
M. Gilchriese Evaporative Cooling Tests of Pixel Disk Sectors June 2000 E. Anderssen, M. Gilchriese, F. Goozen, F. McCormack, J. Taylor, T. Weber, J. Wirth.
A discussion paper for the Absorber Review pre-meeting on February 11 th 2003 On 3-D Fluid Flow calculations on the 22cm Absorber Window By Stephanie Yang.
Kern Method of SHELL-AND-TUBE HEAT EXCHANGER Analysis
Heat Convection : Cylinder in Cross Flow P M V Subbarao Associate Professor Mechanical Engineering Department IIT Delhi A Common Industrial Application.
M. Yoda, S. I. Abdel-Khalik, D. L. Sadowski and M. D. Hageman Woodruff School of Mechanical Engineering Extrapolating Experimental Results for Model Divertor.
Kern Method of SHELL-AND-TUBE HEAT EXCHANGER Analysis
CHE/ME 109 Heat Transfer in Electronics
IBL temperature analyses Bart Verlaat 22 April
Assignment No. 1 [Grup 8] Figure below shows a portion of a hydraulic circuit. The pressure point B must be 200 psig when the volume flow rate is 60 gal/min.
INTRODUCTION to the DESIGN and FABRICATION of IRON- DOMINATED ACCELERATOR MAGNETS Cherrill Spencer, Magnet Engineer HOMEWORK PROBLEM for Lecture # 2 of.
Fouling Factor: After a period of operation the heat transfer surfaces for a heat exchanger become coated with various deposits present in flow systems,
1 Calorimeter Thermal Analysis with Increased Heat Loads September 28, 2009.
Heat Transfer Equations For “thin walled” tubes, A i = A o.
Calorimeter Analysis Tasks, July 2014 Revision B January 22, 2015.
Design Formulae for Mingled Shell-side stream P M V Subbarao Professor Mechanical Engineering Department I I T Delhi A Confluence Model for A Circuitous.
20 th June 20111Enrico Da Riva, V. Rao Project Request and Geometry constraints June 20 th 2011 Bdg 298 Enrico Da Riva,Vinod Singh Rao CFD GTK.
Material Measurement Laboratory Cryogenic Engineering Conference :45 AM Single-phase ambient and cryogenic temperature heat transfer.
VG1 i T i March 9, 2006 W. O. Miller ATLAS Silicon Tracker Upgrade Upgrade Stave Study Topics Current Analysis Tasks –Stave Stiffness, ability to resist.
30 th June 20111Enrico Da Riva, V. Rao Parametric study using Empirical Results June 30 th 2011 Bdg 298 Enrico Da Riva,Vinod Singh Rao CFD GTK.
Convection: Internal Flow ( )
A proposal of ion and aerosol vertical gradient measurement (as an example of application of the heat transfer equations) H. Tammet Pühajärve 2008.
Heat Transfer Equations. Fouling Layers of dirt, particles, biological growth, etc. effect resistance to heat transfer We cannot predict fouling factors.
M. Gilchriese U.S. Pixel Mechanics Overview M. G. D. Gilchriese Lawrence Berkeley National Laboratory April 2000.
Heat Transfer Equations For “thin walled” tubes, A i = A o.
Simple CFD Estimate of End Flange Tuner Finger Cooling.
M. Gomez Marzoa1 WG4 Meeting - 12th December 2012 Update on stave thermal testing Claudio BORTOLIN Enrico DA RIVA Corrado GARGIULO Manuel GOMEZ MARZOA.
HW #4 /Tutorial # 4 WRF Chapter 18; WWWR Chapter 19 ID Chapter 6 Tutorial # 4 WWWR #19.1,19.4, WRF# ID # To be discussed during the week.
Internal Flow: Heat Transfer Correlations. Fully Developed Flow Laminar Flow in a Circular Tube: The local Nusselt number is a constant throughout the.
M. Yoda, S. I. Abdel-Khalik, D. L. Sadowski, B. H. Mills and M. D. Hageman G. W. Woodruff School of Mechanical Engineering Correlations for Divertor Thermal-Hydraulic.
Report on testing Snake2 u-channel. P. Jalocha & J. Buytaert. 8 June 2015.
E. Da Riva/M. Gomez Marzoa1 WG4 Meeting - 27th June 2012 Air Cooling by means of carbon fiber structure Enrico DA RIVA (EN-CV-PJ) Manuel GOMEZ MARZOA (EN-CV-PJ)
Cooling of GEM detector CFD _GEM 2012/03/06 E. Da RivaCFD _GEM1.
COOLING BY EVAPORATION OF PERFLUOROCARBONS Why evaporate? 1. To enhance the heat transfer per unit area The heat transfer coefficient increases significantly.
Aachen Status Report: CO 2 Cooling for the CMS Tracker at SLHC Lutz Feld, Waclaw Karpinski, Jennifer Merz and Michael Wlochal RWTH Aachen University, 1.
Exercises for Q1. Insulated copper tube A thin walled 10 mm copper tube is used to transport a low-temperature refrigerant with a temperature that is.
Date of download: 5/28/2016 Copyright © ASME. All rights reserved. From: Forced Convection Heat Transfer in Spray Formed Copper and Nickel Foam Heat Exchanger.
Heat Transfer by Convection
Heat Transfer Su Yongkang School of Mechanical Engineering # 1 HEAT TRANSFER CHAPTER 7 External flow.
7 February 2012 Annekathrin Frankenberger (HEPHY Vienna) Open CO 2 Cooling System at the beam test Belle II SVD-PXD Meeting.
Heat transfer mechanism Dhivagar R Lecture 1 1. MECHANISMS OF HEAT TRANSFER Heat can be transferred in three different ways: conduction, convection, and.
Heat Transfer Su Yongkang School of Mechanical Engineering # 1 HEAT TRANSFER CHAPTER 8 Internal flow.
19-SEP-2012 «BE-RF-PM» Modelling of hydraulic system of CLIC prototype module type 0 Shoaib Azhar.
Internal Flow: General Considerations. Entrance Conditions Must distinguish between entrance and fully developed regions. Hydrodynamic Effects: Assume.
Internal Flow: Heat Transfer Correlations Chapter 8 Sections 8.4 through 8.8.
Date of download: 9/26/2017 Copyright © ASME. All rights reserved.
Internal Flow: Heat Transfer Correlations
DESIGN OF SHELL AND TUBE HEAT EXCHANGER
HW #4 /Tutorial # 4 WRF Chapter 18; WWWR Chapter 19 ID Chapter 6
Conservation of Mass and Energy
Aachen Status Report: CO2 Cooling for the CMS Tracker
CFD-Team Weekly Meeting - 8th March 2012
From: Design of a Cooling Guide Catheter for Rapid Heart Cooling
Aachen Status Report: CO2 Cooling for the CMS Tracker at SLHC
Ultra-light carbon fiber structures: evaporative tests
Detector Technology Group
Fundamentals of Heat Transfer
Aachen Status Report: CO2 Cooling for the CMS Tracker
Heat-transfer Equipment
Internal Flow: General Considerations
Fundamentals of Heat Transfer
Heat Transfer Correlations for Internal Flow
Internal Flow: Heat Transfer Correlations Chapter 8 Sections 8.4 through 8.8.
Presentation transcript:

1 Monophase Measurements on Prototype Pixel Structures D. Bintinger, M. Gilchriese, J. Taylor and J. Wirth and contributions from D. Cragg, E. Perrin and V. Vacek May 1999

2 Setup C 6 F 14 cooled to about -25C or higher and circulated by pump. Pressure sensors on inlet and outlet(two types => two measurements) Temperature sensors on inlet/outlet and on stave structure Typical ambient temperature held at -10C. Measurements taken at –Different power - about{80(nominal), 100(“worst case”), 120 Watts} –Flows up to about 30 cc/s –Inlet temperatures down to about -25C –We normalize measurements taken with inlet T close to -20 o C and -25 o C to these values

3 Prototype Stave

4

5

6

7

8 Comparison With Calculations Comparison made using C 6 F 14 properties as provided by 3M –Bulk fluid temperature rise passing through stave  T bulk –At power of 102 W and flow of 30 cc/s, the measured “silicon” temperature at the center of a stave is -9.3 o C for inlet temperature of -20 o C. –Bintinger and Vaclav using Gnielinski’s equation predict the wall of the cooling tube to be at o C. (A local heat transfer coefficient of 3600 W/m 2 K is implied.) The difference of 4.3 o C is attributed to the temperature drop across the stave structure and is in good agreement with FEA estimate of 3.9 o C. –To compare with measurements, we use the 4.3 o C drop to add to the calculated value - see next page. –Calculations were done at -20 o C and -30 o C and measurements were taken with inlet temperatures close to -20 o C and -25 o C and then corrected to these values.

9 Calculated Temperature and Measurements Tsilicon calculated at center of stave assuming 4.3 o C gradient in stave structure

10 For a power of 80W and inlet T of -20C we need flow of >18 cc/s For a power of 102W and inlet T of -20C we need flow of>26 cc/s For a power of 102W and inlet T of -25C we need flow of> about 16 cc/s For a power of 123W and inlet T of -20C we need flow of> about 45 cc/s For a power of 123W and inlet T of -25C we need flow of> about 30 cc/s

11 Calculated Midpoint Stave Temperature vs Power for 25 cc/s Flow and Comparison with Data

12 Pixel Sector Prototype Temperature measurements using liquid C 6 F 14 were done on prototype sector previously measured using water-methanol. The maximum temperature for different power and flow conditions is given on the next page.

13 Maximum Observed Temperature on Pixel Sector vs Power and Flow of C 6 F 14 For a power of 36W and inlet T of -20C we need flow of >5 cc/s For a power of 48W and inlet T of -20C we need flow of>13 cc/s For a power of 60W and inlet T of -25C we need flow of>about 8 cc/s

14 Pressure Drop in Stave vs Flow We derive an effective hydraulic diameter of about 2.9 mm for the stave from measurements. The effects of inlet and outlet tubing(16cm of 3.5 mm ID) were removed(by calculation) to obtain the pressure across the stave. The plot above shows data and calculation for 2.9 mm hydraulic diameter and a calculation for 3.5mm hydraulic diameter.

15 Calculated Velocity in Stave vs Flow

16 Pressure Drop in Sector vs Flow The inner dimension of the sector tube are approximately 2.1 mm x 4.1 mm with 5 tight U bends.

17 Pressure Measurements in Long Tube Pressure measurements were made on a 3m long copper tube with 6.35mm ID to compare with calculations

18 Total Circuit Pressure Using the effective hydraulic diameter of 2.9mm for the stave and inlet/outlet tubing sizes and routing(bends), the total circuit pressure from and to PPB3 was calculated. Two different piping configurations were compared(IDs shown below) Baseline Layout“Maximum” Layout Pixel->PPB1 5.1mm 6.0mm PPB1->PPB2 6.9mm 8.0mm PPB2->PPB3 13mm 13mm Two staves per circuit are assumed. Little difference in pressure for colder fluid - see plot next page Head pressure(about 6.1m = 1bar) or effect of operating closed system must be added(or subtracted) from circuit pressure shown. Circuit pressure calculations were compared to those of D. Cragg and agreed to 2-3%.

19 Circuit Pressure vs Stave Flow

20 Other Considerations C 6 F 14 (or any fluorinert) is a degreasing agent. We tested the following thermal greases for resistance to immersion in C 6 F 14. AI Technology CGL 7018no effect up to 24 hours(stopped) Dow Corning DC340no effect up to 24 hours(stopped) Thermagon T431 Sil-less Greaseno effect up to 24 hours(stopped) The radiation length of C 6 F 14 is 19.3 cm at -20 o C. Compared to evaporative C 4 F 10 as estimated in the Pixel TDR, using liquid C 6 F 14 would add about 0.2% X 0 per barrel layer at normal incidence. All flow with C 6 F 14 is turbulent. If the stave hydraulic diameter were increased, the fluid velocity would decrease and the film temperature gradient is predicted to increase. With a hydraulic diameter of 2.9 mm, the pressure drop across the stave is a significant fraction of the total circuit pressure.

21 Summary for Stave For baseline pipe sizes(5.1, 6.9, 13 mm ID) –For -20 o C inlet temperature 80W stave power=>2.2 bar circuit pressure 100 W=>4.0 bar 120 W=>big number –For -25 o C inlet temperature 80W stave power=><1 bar circuit pressure 100 W=>1.5 bar 120 W=>4.2 For maximum pipe sizes(6.0, 8.0, 13 mm ID) –For -20 o C inlet temperature 80W stave power=>1.5 bar circuit pressure 100 W=>2.5 bar 120 W=>big number –For -25 o C inlet temperature 80W stave power=><1 bar circuit pressure 100 W=>1.0 bar 120 W=>2.9 The circuit pressure at the stave is one-half of the circuit pressure

22 Conclusions Prototype pixel stave and sector structures have been successfully cooled with liquid C 6 F 14 Calculations using fluid properties are in reasonable agreement with measurements of pressures and temperatures and can be used with some confidence to predict system performance. For a stave power of about 90W, an inlet temperature of -20 o C or less is necessary to provide cooling at a reasonable circuit pressure(about 3 bar) with current piping sizes. For the same power density on the sector the flow requirements are lower and hence the circuit pressures will be less. Higher stave power than about 100W implies higher pressure operation, lower inlet temperatures or bigger piping or some combination of these to meet temperature requirements.