Objectives Analyze Rotary Heat Exchangers Use Psychometric chart - Start Air Distribution Systems - Diffuser selection
Sensible and Enthalpy Wheels http://doas-radiant.psu.edu/4428.pdf
Example of Dual Wheel System
Psychrometrics of sensible and enthalpy wheel Example NMS Building HVAC system: Fans Enthalpy wheel Exhaust air Sensible wheel D A C B 1 2 Return air form building Fresh air Hot and fresh air to building Filters 7 Preheater 6 5 4 3 Heating coil Cooling coil Cool and fresh air to building
Air Distribution System Design Describe room distribution basics Select diffusers Supply and return duct sizing
Designing Room Airflow Very complex problem Pumped flow, buoyant flow (or mixed flow) What non-dimensional parameters govern each regime? Archimedes number = Ar = gβLΔT/v2 L = characteristic length (m, ft) g = acceleration due to gravity (m/s2, ft/min2) T = absolute temperature (K, °R) β = 1/T (1/K, 1/ °R) v = kinematic viscosity (m2/s, ft2/min)
Computational Fluid Dynamics
CFD in Air Distribution Design Contaminant concentration in a kitchen
Buoyancy driven flow: Example of airflow in a stairway Heater (radiator)
Forced driven air flow Diffusers Grill (side wall) diffusers Linear diffusers Vertical Horizontal one side
Diffusers types Valve diffuser swirl diffusers ceiling diffuser wall or ceiling floor
Low mixing Diffusers Displacement ventilation
18.7
Diffuser Selection Procedure Select and locate diffusers, divide airflow amongst diffusers V = maximum volumetric flow rate (m3/s, ft3/min) Qtot = total design load (W, BTU/hr) Qsen = sensible design load (W, BTU/hr) ρ = air density (kg/m3, lbm/ft3) Δt = temperature difference between supply and return air (°C, °F) Δh = enthalpy difference between supply and return air (J/kg, BTU/lbm)
Find Characteristic Length (L)
Indicator of Air Distribution Quality ADPI = air distribution performance index Fraction of locations that meet criteria: -3 °F < EDT < 2 °F or -1.5 °C < EDT < 1 °C Where, EDT = effective draft temperature Function of V and Δt (Eqn 18.1) EDT=(tlocal-taverage)-M(Vlocal-Vaverage) , M=7 °C/(m/s) ADPI considers ONLY thermal comfort (not IAQ)
Ideal and Reasonable Throws
Select Register Pick throw, volumetric flow from register catalog Check noise, pressure drop
Summary of Diffuser Design Procedure Find Q sensible total for the space Select type and number of diffusers Find V for each diffuser Find characteristic length Select the diffuser from the manufacturer data
Example 18.3 Qtot = 38.4 kBTU/hr Δh = 9.5 BTU/lbma Note omission in text
Reading asignement Chapter 18 18.1-18.2 (including 18.2)