BENATO IT Session 4 – Block 3 – Question 6 Barcelona 12-15 May 2003 THE ISLANDING PROBLEM PASSIVE PROTECTIONS AS DEMONSTRATE THE POSSIBILITY OF FAILING.

Slides:



Advertisements
Similar presentations
Conducted Immunity IEC
Advertisements

Announcements Be reading Chapters 9 and 10 HW 8 is due now.
ADVANCED MANAGEMENT OF A CLOSED RING OPERATED MV NETWORK: ENEL DISTRIBUZIONE’S P4 PROJECT. Simone Botton, Roberto Calone, Luigi D’Orazio, Alessandro Fatica,
Modeling of Reconnection of Decentralized Power Energy Sources Using EMTP ATP Ing. Dušan MEDVEĎ, PhD. Železná Ruda-Špičák, 25. May 2010 TECHNICAL UNIVERSITY.
Design of a Low-Noise 24 GHz Receiver Using MMICs Eric Tollefson, Rose-Hulman Institute of Technology Advisor: Dr. L. Wilson Pearson.
Chapter 13 Transmission Lines
Lecture 26 Distribution Systems Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
Antennas Lecture 9.
Example Problem You are measuring the EEG of a patient and accidently choose two different types of electrodes for EEG lead. One of them has a source impedance.
COST286 meeting Barcelona 14/15 April BUTE Part 1 Conducted and radiated disturbance regulations for PLC devices János Löcher; György Varjú BUTE.
Effect of Mutual Coupling on the Performance of Uniformly and Non-
New approach in functionality and testing for HV Capacitor Bank Protection Jorge Cardenas † (J.C.), Sean Cox ♣ (S.C), Petru van Wyk ♣ (P.W.), Boitumelo.
1 ENE 429 Antenna and Transmission lines Theory Lecture 4 Transmission lines.
CIGRE Study Committee B5 Colloquium, Calgary September 2005 AREVA T&D Automation Protection & Control of Series Compensated Networks Z Q Bo PART.
POWER SYSTEM PROTECTION
KD Relay Application: Compensator distance relay that provides a single zone of phase protection for all three phases. It provides tripping for phase to.
12 Transmission Lines.
A PRACTICAL TRAINING SEMINAR ON PLCC
Frankfurt (Germany), 6-9 June 2011  PV in Spain: Basically Large plants connected to MV or HV Mainly in rural areas (generation exceeds consumption) 3,000.
Developing fast clock source with deterministic jitter Final review – Part A Yulia Okunev Supervisor -Yossi Hipsh HS-DSL Laboratory, Dept. of Electrical.
Passive Devices (3 port network) S-matrix of 3 port networks (1) All ports are matched and network is reciprocal (2) can be lossless? 3 Port Network can.
MV Network Operation and Control Barcelona May 2003 Eugenio Di Marino Italy Session 3 Alpha 1 Block 1.
1.  Transmission lines or T-lines are used to guide propagation of EM waves at high frequencies.  Examples: › Transmitter and antenna › Connections.
Lecture 22 Unbalanced Faults and Power System Protection Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
Nelson Kagan BR Session 4 – Block 3 – Planning – Paper #66 Barcelona May Technical Assessment for the Installation of Dispersed Generation.
ENE 428 Microwave Engineering
Lecture 22 Unbalanced Faults and Power System Protection Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
Announcements Read Chapters 10 and 11
POWER HOUSE.
Submitted to: Submitted by:
O. MÄKINEN FI Session 3 Block 3 Barcelona May What is an intermittent earth fault (IE/F)? Insulation Conductor Screen Insulation break-down.
Department of Electrical Engineering
A Training Presentation On 220 KV GSS CHOMU,JAIPUR
Electrical Principles 1 1 G5 - ELECTRICAL PRINCIPLES [3 exam questions - 3 groups] G5A - Reactance; inductance; capacitance; impedance; impedance matching.
Electrical Engineering
A SEMINAR ON 400 KV GSS(RRVPNL) BIKANER.
Submitted To:- Submitted By:- Mr.
Vaughan Roberts UK Session 4 – Block 4 Barcelona May ACTIVE NETWORKS FOR THE ACCOMMODATION OF DISPERSED GENERATION.
BASIC INSTRUMENTS - oscilloscopes
1.  Transmission lines or T-lines are used to guide propagation of EM waves at high frequencies.  Distances between devices are separated by much larger.
Protection of Power Systems
البحث السابع بحث منفرد منشور فى مؤتمر دولى متخصص (منشورة التحكيم علي البحث الكامل) Adel A. Elbaset 13th International Middle East Power System Conference,
EE 2353 HIGH VOLTAGE ENGINEERING Faculty Name :A.JAIBUNISHA Faculty Code : EE 58 Designation : LECTURER Department : EEE.
Chapter 2 Overview 1.
PLCC OVERVIEW :PRESENTED BY BIMAL NANDA
J.PRAKASH.  The term power quality means different things to different people.  Power quality is the interaction of electronic equipment within the.
Power System Protective Relaying-Part One
STUDY OF ELEMENTS OF A 220/132/33KV SUBSTATION
Design a protection System of 220/33kV Grid Station United Arab Emirates University College of Engineering Saif Mohammed AL Aryani Ahmed Soruor.
Lossy Transmission Lines
Lab2: Smith Chart And Matching
Lecture 2 Transmission Line Characteristics
Applied EM by Ulaby, Michielssen and Ravaioli
Access Networks Exercises
CMA46 Questions & Answers.
Luka Strezoski Marija Prica
Introduction What is an oscilloscope?.
Basics of electrical engineering
Design of Electric Power Systems and Utilities
Peter van Oirsouw (Phase to Phase)
EHV Transmission Equipments
Exercise 8 Power systems.
PLC-Based Anti-Islanding and Fault Locating System Concept A
Power System Protective Relaying-Part One
Lossy Transmission Lines
IMPEDANCE MATCHING & SMITH CHART
DISCRETE ASCENT OPTIMAL PROGRAMMING APPLIED TO NETWORK CONFIGURATION IN ELECTRICAL DISTRIBUTION SYSTEMS B. A. Souza H. A. Ferreira H. N. Alves.
ENE 428 Microwave Engineering
lossless, reciprocal, and matched at all port
HIGH VOLTAGE ENGINEERING Presented By P.Sindhu Asst.Prof EEE Dept
Presentation transcript:

BENATO IT Session 4 – Block 3 – Question 6 Barcelona May 2003 THE ISLANDING PROBLEM PASSIVE PROTECTIONS AS DEMONSTRATE THE POSSIBILITY OF FAILING THE ISLAND DETECTION PASSIVE PROTECTIONS AS Max/min voltage relaying Over/under frequency relaying Rate of change of frequency relays Phase displacement monitoring DEMONSTRATE THE POSSIBILITY OF FAILING THE ISLAND DETECTION HV Busbar MV Busbar After system switching operation, a section of the utility network remains connected to the DG !

BENATO IT Session 4 – Block 3 – Question 6 Barcelona May 2003 DLC-BASED PROTECTION SCHEME Under normal conditions, guard frequency detected by RX Guard frequency injected at MV busbar

BENATO IT Session 4 – Block 3 – Question 6 Barcelona May 2003 When the breaker is opened there is a loss of guard frequency for the DG receiver there is a loss of guard frequency for the DG receiver

BENATO IT Session 4 – Block 3 – Question 6 Barcelona May 2003 FEASIBILITY OF DLC PROTECTION THE CARRIER SIGNAL PROPAGATION IN MV NETWORKS CAN FIND DIFFICULTIES DUE TO:  overhead and cable line attenuation;  the presence of capacitor banks;  different line segments;  branching;  mismatching and standing wave patterns.

BENATO IT Session 4 – Block 3 – Question 6 Barcelona May 2003 DEVELOPMENT OF A TOOL FOR THE CARRIER SIGNAL TRANSMISSION ANALYSIS STANDING WAVE CONDITIONS OPTIMAL MISMATCHING ZONE Cable Lines Z M = 460  Overhead Lines Z M = 3000  Combination of OHL and CL Z M = 1500 

BENATO IT Session 4 – Block 3 – Question 6 Barcelona May 2003 OVERHEAD AND CABLE LINE ATTENUATION Attenuation as a function of receiver impedance Z M Attenuation as a function of receiver impedance Z M m MV overerhead line ACSR  =15.85 mm CC  =10.70 mm Conductors less than 0.5 [dB/km] about 1.5  4 [dB/km]

BENATO IT Session 4 – Block 3 – Question 6 Barcelona May 2003 EXAMPLE OF A CAPACITIVE COUPLING DEVICE Electric circuit The Coupling Capacitance :

BENATO IT Session 4 – Block 3 – Question 6 Barcelona May 2003 URBAN FEEDER MEASUREMENT CAMPAIGN I Comparison between computed and measured values ATTENUATION at 72 kHz = 20 db GOOD AGREEMENT !

BENATO IT Session 4 – Block 3 – Question 6 Barcelona May 2003 RURAL RADIAL FEEDER MEASUREMENT CAMPAIGN II This measurement campaign seems to be representative of the DLC transmission length limit without the use of repeater devices. TX: 20 db on 75  RX: db ATTENUATION: 70 db

BENATO IT Session 4 – Block 3 – Question 6 Barcelona May 2003 CONCLUSION A novel protection method to prevent DG islanding; A novel protection method to prevent DG islanding; A suitable analysis procedure has been developed; A suitable analysis procedure has been developed; Good agreement of test results with the theoretical calculations  (accuracy of the multiconductor matrix procedure); Good agreement of test results with the theoretical calculations  (accuracy of the multiconductor matrix procedure); Distance limit between TX and RX about 10  15 km for a typical Italian radial branched MV feeder; Distance limit between TX and RX about 10  15 km for a typical Italian radial branched MV feeder; (If longer distances are needed, the use of repeaters must be taken into consideration). (If longer distances are needed, the use of repeaters must be taken into consideration).