Teknologi Pusat Data 12 Data Center Site Infrastructure Tier Standard: Topology Ida Nurhaida, ST., MT. FASILKOM Teknik Informatika.

Slides:



Advertisements
Similar presentations
Chapter 3: Planning a Network Upgrade
Advertisements

Valley City State University | Facilities Services
Technical Committees – the Brains of ASHRAE Section 1.0 — Fundamentals and General.
The Data Centers, LLC Wolf Technology Center 1 Campus
Business Plug-In B4 MIS Infrastructures.
VSE Corporation Proprietary Information
Preparing for Power Outages Like any other part of the infrastructure, electrical power to the campus can fail, either as an isolated incident (e.g., tripped.
Chapter 19: Network Management Business Data Communications, 5e.
Fully Compliant Cloud Based Repository Lessons along the way Mark Ellis, Electronic Records Management Consultant April 8th, 2014.
NERC Lessons Learned Summary December NERC lessons learned published in December 2014 Three NERC lessons learned (LL) were published in December.
Data Center Site Infrastructure Tier Standard: Topology Dr. Natheer Khasawneh Sadeem Al-Saeedi (8276)
Achieving Data Center Availability along with Efficiency by Management Systems Shimon Katz, Data Center Project Manager ELECTRICITY 2012 – Eilat, Israel.
Telenor Tier 3 Data Center April About Telenor Tier 3 Data Center Telenor built it´s own Data Centar in accordance with the latest industrial standards.
Industrial Ventilation - A major control measure Dr. AA, UTM.
1 Northwestern University Information Technology Data Center Elements Research and Administrative Computing Committee Presented October 8, 2007.
1 ITC242 – Introduction to Data Communications Week 12 Topic 18 Chapter 19 Network Management.
Location of the theme gray Location of the theme blue ZTE Proprietary On Reliability of COTS Hardware Dr. Li Mo Chief Architect, CTO Group.
CHAPTER FIVE INFRASTRUCTURES SUSTAINABLE TECHNOLOGIES CHAPTER FIVE INFRASTRUCTURES SUSTAINABLE TECHNOLOGIES Copyright © 2015 McGraw-Hill Education. All.
™ כותרת Myths and Misconceptions in Datacenter Rating Shimon Katz, Data Center Project Manager ELECTRICITY 2013– Jerusalem, Israel.
©Ian Sommerville 2004Software Engineering, 7th edition. Chapter 2 Slide 1 Systems engineering 1.
John Graham – STRATEGIC Information Group Steve Lamb - QAD Disaster Recovery Planning MMUG Spring 2013 March 19, 2013 Cleveland, OH 03/19/2013MMUG Cleveland.
CHAPTER OVERVIEW SECTION 5.1 – MIS INFRASTRUCTURE
MFGE 404 Computer Integrated Manufacturing CIM A T I L I M U N I V E R S I T Y Manufacturing Engineering Department Lecture 7– Flexible Manufacturing Systems.
CHAPTER FIVE INFRASTRUCTURES SUSTAINABLE TECHNOLOGIES
CHAPTER FIVE INFRASTRUCTURES: SUSTAINABLE TECHNOLOGIES
data center classifications or ratings
Fatigue Management Rule Russell Smith Nuclear Energy Institute (NEI)
NHUG - Boston - 08/04/20101 Considerations for Operability of Chillers and Chilled Water Systems NHUG Summer Meeting August 4, 2010 Tim Mitchell Component.
Co-location Sites for Business Continuity and Disaster Recovery Peter Lesser (212) Peter Lesser (212) Kraft.
1 Nassau Community CollegeProf. Vincent Costa Session 7 Infrastructures Sustainable Technologies CMP 117 Business Computing: Concepts &Applications.
SPS policy – Information Presentation Presentation to ROS June 16, 2004.
"1"1 Introduction to Managing Data " Describe problems associated with managing large numbers of disks " List requirements for easily managing large amounts.
E.Soundararajan R.Baskaran & M.Sai Baba Indira Gandhi Centre for Atomic Research, Kalpakkam.
Main Requirements on Different Stages of the Licensing Process for New Nuclear Facilities Module 4.5/1 Design Geoff Vaughan University of Central Lancashire,
Service Level Agreements Service Level Statements NO YES The process of negotiating and defining the levels of user service (service levels) required.
Specific Safety Requirements on Safety Assessment and Safety Cases for Predisposal Management of Radioactive Waste – GSR Part 5.
Utility Engineers, PC.  Generation  Transmission  Distribution.
Manufacturing Plant maintenance Materials management Quality management.
Introduction to switchgears
Operating Guide and Planning Guide Revision Requests Blake Williams, ROS Chair September 13, 2012.
Central AC system for Auditorium
Component 8/Unit 9aHealth IT Workforce Curriculum Version 1.0 Fall Installation and Maintenance of Health IT Systems Unit 9a Creating Fault Tolerant.
Modul ke: Fakultas Program Studi Teknologi Pusat Data 13 FASILKOM Teknik Informatika Infrastruktur Pusat Data.
FESS/Ops Shut Down Summary Week Ending 9/7/12. – FESS needs a CUB Cooling Outage for installation of Barriers in the CUB Chiller 4160 Volt Starter Cabinet.
Janko Lavrič, Data Center Plan designer team –
Utilities & Engineering Department16 Blossom St., Boston Introduction to the Hospital Emergency Power Supply System (EPSS) Jason D'Antona,
By Annick Carnino (former Director of IAEA Division of Nuclear Installations Safety) PIME, February , 2012.
Testing Requirements in the Boiler House Requirements for regular testing will vary according to national regulations, and the type of equipment installed.
Process Safety Management Soft Skills Programme Nexus Alliance Ltd.
Infrastructure Deployment Services Dell Networking Deployment Services.
C21 World (UK) Consultancy Services for Telecom Industry DATA CENTERS
Class A, B, and now N NFPA 72, 2016 Edition Dan Horon President
OSIsoft High Availability PI Replication Colin Breck, PI Server Team Dave Oda, PI SDK Team.
Austin Energy Elevated Requests for High Reliability Service South West Electric Distribution Exchange (SWEDE) May 8, 2015 David Tomczyszyn, P.E. – Distribution.
1 FOM 2.2 Tier Certification Explained Keith Klesner Senior Vice President North America Uptime Institute.
Fire Risk Assessment Judith Evans BEng(HONS) CMIOSH
Tier Certification Explained
Sub Station.
Author: Nurul Azyyati Sabri
IC3 GS3 Standard COMPUTING FUNDAMENTALS Module
IOT Critical Impact on DC Design
CHAPTER OVERVIEW SECTION 5.1 – MIS INFRASTRUCTURE
Section 1.0 — Fundamentals and General
ANSI/ASHRAE 90.4 Energy Standard for Data Centers
GES SYSTEM THE IMPORTANCE OF GES SYSTEM IN BUILDING
Factors to Consider when Designing a Reliable Power Grid
Factors to Consider when Designing a Reliable Power Grid
Unit I Module 3 - RCM Terminology and Concepts
DATA CENTERS C21 Engineering Consultancy Services for Telecom Industry
Presentation transcript:

Teknologi Pusat Data 12 Data Center Site Infrastructure Tier Standard: Topology Ida Nurhaida, ST., MT. FASILKOM Teknik Informatika

Data Center Site Infrastructure Tier Standard: Topology Dr.Natheer Khasawneh Maysoon R.Isleem

Agenda 1 2 3 4 4 Introduction Tier Classification Definitions Engine-Generator Systems 4 Ambient Temperature Design Points 4 Tier Requirements Summary

Introduction The object of the institute tier standard: topology is to comparing the functionality, capacity, and expected availability (or performance) of a particular site infrastructure design topology against other sites, or for comparing a group of sites. Describes criteria to differentiate four classifications of site infrastructure topology based on increasing levels of redundant capacity components and distribution paths. Focuses on the definitions of the four tiers and the performance confirmation tests for determining compliance to the definitions.

Introduction The Tier Classifications created to consistently describe the site-level infrastructure required to sustain data center operations. Data centers are dependent upon the successful and integrated operation of at least 16 separate site infrastructure subsystems. Every subsystem and system must be consistently deployed with the same site uptime objective to satisfy the distinctive Tier requirements

Introduction The tier topology rating for an entire site is constrained by the rating of the weakest subsystem that will impact site operation. The purpose of this standard is to equip design professionals, data center operators, and non-technical managers with an objective and effective means for identifying the anticipated performance of different data center site infrastructure design topologies.

Site Infrastructure Tier Standards Tier I: Basic Site Infrastructure Tier II: Redundant Site Infrastructure Capacity Components Tier III: Concurrently Maintainable Site Infrastructure Tier IV: Fault Tolerant Site Infrastructure

Tier I: Basic Site Infrastructure The fundamental requirement A Tier I basic data center has non-redundant capacity components and a single, non-redundant distribution path serving the computer equipment. The performance confirmation tests There is sufficient capacity to meet the needs of the site. Planned work will require most or all of the site infrastructure systems to be shut down affecting computer equipment, systems, and end users.

Tier I: Basic Site Infrastructure The operational impacts The site is susceptible to disruption from both planned and unplanned activities. Operation (Human) errors of site infrastructure components will cause a data center disruption. An unplanned outage or failure of any capacity system, capacity component, or distribution element will impact the computer equipment.

Tier I: Basic Site Infrastructure The site infrastructure must be completely shut down on an annual basis to safely perform necessary preventive maintenance and repair work. Urgent situations may require more frequent shutdowns. Failure to regularly perform maintenance significantly increases the risk of unplanned disruption as well as the severity of the consequential failure.

Tier I: Basic Site Infrastructure Requirements Tier 1 Single non-redundant distribution path serving the IT equipment Non-redundant capacity components Basic site infrastructure guaranteeing 99.671% availability

Tier II: Redundant Site Infrastructure Capacity Components The fundamental requirement A Tier II data center has redundant capacity components and a single, non-redundant distribution path serving the computer equipment. The performance confirmation tests Redundant capacity components can be removed from service on a planned basis without causing any of the computer equipment to be shut down. Removing distribution paths from service for maintenance or other activity requires shutdown of computer equipment.

Tier II: Redundant Site Infrastructure Capacity Components The operational impacts The site is susceptible to disruption from both planned activities and unplanned events. Operation (Human) errors of site infrastructure components may cause a data center disruption. An unplanned capacity component failure, outage or failure of any capacity system or distribution element will impact the computer equipment.

Urgent situations may require more frequent shutdowns. Tier II: Redundant Site Infrastructure Capacity Components The site infrastructure must be completely shut down on an annual basis to safely perform preventive maintenance and repair work. Urgent situations may require more frequent shutdowns. Failure to regularly perform maintenance significantly increases the risk of unplanned disruption as well as the severity of the consequential failure.

Tier II: Redundant Site Infrastructure Capacity Components Requirements Tier 2 Fulfils all Tier 1 requirements Redundant site infrastructure capacity components guaranteeing 99.741% availability

Tier III: Concurrently Maintainable Site Infrastructure The fundamental requirements A Concurrently Maintainable data center has redundant capacity components and multiple independent distribution paths serving the computer equipment. Only one distribution path is required to serve the computer equipment at any time. All IT equipment is dual-powered and installed properly to be compatible with the topology of the site’s architecture. Transfer devices, such as point-of-use switches, must be incorporated for computer equipment that does not meet this specification. .

The performance confirmation tests Tier III: Concurrently Maintainable Site Infrastructure The performance confirmation tests Each and every capacity component and element in the distribution paths can be removed from service on a planned basis without impacting any of the computer equipment. There is sufficient permanently installed capacity to meet the needs of the site when redundant components are removed from service for any reason.

Tier III: Concurrently Maintainable Site Infrastructure The operational impacts The site is susceptible to disruption from unplanned activities. Operation errors of site infrastructure components may cause a computer disruption. An unplanned outage or failure of any capacity system will impact the computer equipment. An unplanned outage or failure of a capacity component or distribution element may impact the computer equipment.

Tier III: Concurrently Maintainable Site Infrastructure Planned site infrastructure maintenance can be performed by using the redundant capacity components and distribution paths to safely work on the remaining equipment. During maintenance activities, the risk of disruption may be elevated.

Tier III: Concurrently Maintainable Site Infrastructure Requirements Tier 3 Fulfils all Tier 1 and Tier 2 requirements Multiple independent distribution paths serving the IT equipment All IT equipment must be dual-powered and fully compatible with the topology of a site’s architecture Concurrently maintainable site infrastructure guaranteeing 99.982% availability

Tier IV: Fault Tolerant Site Infrastructure The fundamental requirements A Fault Tolerant data center has multiple, independent, physically isolated systems that provide redundant capacity components and multiple, independent, diverse, active distribution paths simultaneously serving the computer equipment. The redundant capacity components and diverse distribution paths shall be configured such that “N” capacity is providing power and cooling to the computer equipment after any infrastructure failure.

Tier IV: Fault Tolerant Site Infrastructure All IT equipment is dual powered and installed properly to be compatible with the topology of the site’s architecture. Transfer devices, such as point-of-use switches, must be incorporated for computer equipment that does not meet this specification. Complementary systems and distribution paths must be physically isolated from one another (compartmentalized) to prevent any single event from simultaneously impacting both systems or distribution paths. Continuous Cooling is required.

Tier IV: Fault Tolerant Site Infrastructure The performance confirmation tests A single failure of any capacity system, capacity component, or distribution element will not impact the computer equipment. The system itself automatically responds (‘self heals’) to a failure to prevent further impact to the site

Tier IV: Fault Tolerant Site Infrastructure The operational impacts The site is not susceptible to disruption from a single unplanned event. The site is not susceptible to disruption from any planned work activities. Each and every capacity component and element in the distribution paths can be removed from service on planned basis without impacting any of the computer equipment. There is sufficient capacity to meet the needs of the site when redundant components or distribution paths are removed from service for any reason.

Tier IV: Fault Tolerant Site Infrastructure The site infrastructure maintenance can be performed by using the redundant capacity components and distribution paths to safely work on the remaining equipment. During maintenance activity where redundant capacity components or a distribution path shut down, the computer equipment is exposed to an increased risk of disruption in the event a failure occurs on the remaining path. This maintenance configuration does not defeat the Tier rating achieved in normal operations. Operation of the fire alarm, fire suppression, or the emergency power off (EPO) feature may cause a data center disruption.

Requirements Tier 4 Tier IV: Fault Tolerant Site Infrastructure Fulfils all Tier 1, Tier 2, and Tier 3 requirements All cooling equipment is independently dual-powered, including chillers and Heating, Ventilating and Air Conditioning (HVAC) systems Fault tolerant site infrastructure with electrical power storage and distribution facilities guaranteeing 99.995% availability

Engine-Generator Systems Tier III and IV engine-generator systems are considered the primary power source for the data center. Site on Engine-Generator Power A Tier III or IV engine-generator system, along with its power paths and other supporting elements, shall meet the Concurrently Maintainable and/or Fault Tolerant performance confirmation tests while they are carrying the site on engine-generator power.

Engine-Generator Systems Manufactures’ Run Time Limitation Engine generators for Tier III and IV sites shall not have a limitation on consecutive hours of operation when loaded to “N” demand. Engine generators that have a limit on consecutive hours of operation at “N” demand are appropriate for Tier I or II. Regulatory Run Time Limitation Engine-generator systems often have an annual regulatory limit on operating hours driven by emissions. These environmental limits do not impact the consecutive hours of operation constraint established in this section.

Ambient Temperature Design Points Extreme Annual Design Conditions The capacity of all equipment that rejects heat to the atmosphere shall be determined at the Extreme Annual Design Conditions that best represents the data center location in the most recent edition of the ASHRAE Handbook Fundamentals. Computer Room Set points The capacity for computer room cooling equipment shall be determined at the return air temperature, and relative humidity established by the owner for steady state data center operations.

Tier Requirements Summary