ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.

Slides:



Advertisements
Similar presentations
Announcements Be reading Chapters 9 and 10 HW 8 is due now.
Advertisements

Announcements Be reading Chapters 8 and 9
ECE 530 – Analysis Techniques for Large-Scale Electrical Systems
Lecture 3 Three Phase, Power System Operation Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
Announcements Be reading Chapter 6, also Chapter 2.4 (Network Equations). HW 5 is 2.38, 6.9, 6.18, 6.30, 6.34, 6.38; do by October 6 but does not need.
ECE 333 Renewable Energy Systems Lecture 14: Power Flow Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
Transient Excitation of First-Order Circuits
ECE 333 Renewable Energy Systems Lecture 13: Per Unit, Power Flow Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois.
Announcements Be reading Chapters 1 and 2 from the book
Announcements Be reading Chapter 3
EE 369 POWER SYSTEM ANALYSIS
Lecture7 Development of Transmission Line Models Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
EE369 POWER SYSTEM ANALYSIS Lecture 6 Development of Transmission Line Models Tom Overbye and Ross Baldick 1.
ECE 576 – Power System Dynamics and Stability
Transmission Line “Definition” General transmission line: a closed system in which power is transmitted from a source to a destination Our class: only.
ECE 530 – Analysis Techniques for Large-Scale Electrical Systems
Announcements For lectures 8 to 10 please be reading Chapter 3
Announcements Please read Chapter 3 H4 is 4.34, 4.41, 5.2, 5.7, 5.16
ECE 476 Power System Analysis Lecture 7: Transmission Line Parameters Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois.
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
ECE 476 Power System Analysis Lecture 5:Transmission Line Parameters Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois.
Announcements Please read Chapter 4 HW 1 is due now
Lecture 6 Development of Transmission Line Models Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
Announcements Please read Chapter 3; start on Chapter 6
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
Lecture 6 Development of Transmission Line Models Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
University of Illinois at Chicago ECE 423, Dr. D. Erricolo, Lecture 19 University of Illinois at Chicago ECE 423, Dr. D. Erricolo, Lecture 19 Frequency.
Lecture 18 Fault Analysis Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye University of Illinois at Urbana-Champaign 1 Lecture 26: Modal Analysis,
ECE 476 Power System Analysis Lecture 11: Ybus, Power Flow Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
ECE 576 – Power System Dynamics and Stability
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign
Announcements Read Chapters 8 and 9
Announcements Read Chapters 8 and 9 HW 9 quiz today
Announcements Please read Chapters 1 and 2
ECE 476 Power System Analysis Lecture 22: System Protection, Transient Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.
Announcements Read Chapters 10 and 11
ECE 476 Power System Analysis Lecture 14: Power Flow Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
Announcements Read Chapters 11 and 12 (sections 12.1 to 12.3)
ECE 576 – Power System Dynamics and Stability
ECE 530 – Analysis Techniques for Large-Scale Electrical Systems
ECE 476 Power System Analysis Lecture 18: LMP Markets, Symmetrical Faults and Components Prof. Tom Overbye Dept. of Electrical and Computer Engineering.
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
Lecture 5 Development of Transmission Line Models Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
Lecture 19 Fault Analysis, Grounding, Symmetrical Components Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM.
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
ECE 576 – Power System Dynamics and Stability
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye University of Illinois at Urbana-Champaign 1 Lecture 23: Small Signal.
Announcements Please read Chapters 11 and 12
Announcements Please read Chapters 4 and 5 (skim 4.7, 4.11, 4.12)
Announcements Please read Chapters 4 and 5 Quiz today on HW 2
Announcements Design Project has firm due date of Dec 4
Announcements Please read Chapters 8 and 9
Announcements Please read Chapters 9, 10 and 11 HW 8 quiz today
Announcements Please read Chapter 3
ECE 476 POWER SYSTEM ANALYSIS
ECE 476 Power System Analysis
ECE 476 Power System Analysis
ECEN 667 Power System Stability
ECE 333 Green Electric Energy
ECE 576 – Power System Dynamics and Stability
ECEN 667 Power System Stability
Presentation transcript:

ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign 1 Lecture 3: Electromagnetic Transients

Announcements Be reading Chapters 1 and 2 Homework 1 is assigned today, due Feb 4; it is on the website Classic reference paper on EMTP is H.W. Dommel, "Digital Computer Solution of Electromagnetic Transients in Single- and Multiphase Networks," IEEE Trans. Power App. and Syst., vol. PAS-88, pp , April

Lossless Transmission Line Model These Norton equivalent represent the lossless lines 3 Both ends of the line are represented by Norton equivalents

Including Line Resistance An approach for adding line resistance, while keeping the simplicity of the lossless line model, is to just to place ½ of the resistance at each end of the line – This allows a decoupled Norton equivalent representation – Another, more accurate approach, is to place ¼ at each end, and ½ in the middle Standalone resistance, such as modeling the resistance of a switch, is just represented as an algebraic equation 4

Numerical Integration with Trapezoidal Method Numerical integration is often done using the trapezoidal method discussed last time – Here we show how it can be applied to inductors and capacitors For a general function the trapezoidal is Trapezoidal integration introduces error on the order of  t 3, but it is numerically stable 5

Trapezoidal Applied to Inductor with Resistance For a lossless inductor, This can be represented as a Norton equivalent with current into the equivalent defined as positive 6

Trapezoidal Applied to Inductor with Resistance For an inductor in series with a resistance we have 7

Trapezoidal Applied to Inductor with Resistance This also becomes a Norton equivalent. A similar expression will be developed for capacitors 8

RL Example Assume a series RL circuit with an open switch with R= 200  and L = 0.3H, connected to a voltage source with Assume the switch is closed at t=0 The exact solution is 9 R/L=667, so the dc offset decays quickly

Exact solution: RL Example Trapezoidal Solution 10 Numeric solution:

t =.0002 i(.0002) = 117.3A Exact solution i(.0002) = 117.3A Solving for i(.0002) RL Example Trapezoidal Solution 11

Full Solution Over Three Cycles 12

A Favorite Qual Problem: R=0 Case, with v(t) = Sin(2*pi*60) 13

Lumped Capacitance Model The trapezoidal approach can also be applied to model lumped capacitors Integrating over a time step gives Which can be approximated by the trapezoidal as 14

Lumped Capacitance Model Hence we can derive a circuit model similar to what was done for the inductor 15

Example 2.1: Line Closing 16 Switch is closed at time t = sec

Initial conditions:i 1 = i 2 = v 1 = v 2 =0 for t <.0001 sec Example 2.1: Line Closing Because of finite propagation speed, the receiving end of the line will not respond to energizing the sending end for at least seconds 17

Example 2.1: Line Closing 18

Need: Example 2.1: t=

Example 2.1: t= Sending End Receiving End

Instantaneously changed from zero at t =.0001 sec. Example 2.1: t=

Need: Example 2.1: t= Circuit is essentially the same Wave is traveling down the line 22

switch closed Example 2.1: t= to With interpolation receiving end will see wave 23

Need: Example 2.1: t= (linear interpolation) 24

For t i =.0006 (t =.0007 sec) at the sending end Example 2.1: t= This current source will stay zero until we get a response from the receiving end 25

Example 2.1: t= For t i =.0006 (t =.0007 sec) at the receiving end 26

Example 2.1: First Three Cycles 27 Red is the sending end voltage (in kv), while green is the receiving end voltage. Note the near voltage doubling at the receiving end

Example 2.1: First Three Cycles 28 Graph shows the current (in amps) into the RL load over the first three cycles. To get a ballpark value on the expected current, solve the simple circuit assuming the transmission line is just an inductor

Three Node, Two Line Example 29 Graph shows the voltages for 0.02 seconds for the Example 2.1 case extended to connect another 120 mile line to the receiving end with an identical load Note that there is no longer an initial overshoot for the receiving (green) end since wave continues into the second line

Example 2.1 with Capacitance Below graph shows example 2.1 except the RL load is replaced by a 5  F capacitor (about 100 Mvar) Graph on left is unrealistic case of resistance in line Graph on right has R=0.1  /mile 30

EMTP Network Solution The EMTP network is represented in a manner quite similar to what is done in the dc power flow or the transient stability network power balance equations or geomagnetic disturbance modeling (GMD) Solving set of dc equations for the nodal voltage vector V with V = G -1 I where G is the bus conductance matrix and I is a vector of the Norton current injections 31

EMTP Network Solution Fixed voltage nodes can be handled in a manner analogous to what is done for the slack bus: just change the equation for node i to V i = V i,fixed Because of the time delays associated with the transmission line models G is often quite sparse, and can often be decoupled Once all the nodal voltages are determined, the internal device currents can be set – E.g., in example 2.1 one we know v 2 we can determine v 3 32

Three-Phase EMTP What we just solved was either just for a single phase system, or for a balanced three-phase system – That is, per phase analysis (positive sequence) EMTP type studies are often done on either balanced systems operating under unbalanced conditions (i.e., during a fault) or on unbalanced systems operating under unbalanced conditions – Lightning strike studies In this introduction to EMTP will just covered the balanced system case (but with unbalanced conditions) – Solved with symmetrical components 33

Modeling Transmission Lines Undergraduate power classes usually derive a per phase model for a uniformly transposed transmission line 34

Modeling Transmission Lines Resistance is just the  per unit length times the length Calculate the per phase inductance and capacitance per km of a balanced 3 , 60 Hz, line with horizontal phase spacing of 10m using three conductor bundling with a spacing between conductors in the bundle of 0.3m. Assume the line is uniformly transposed and the conductors have a 1.5 cm radius and resistance = 0.06  /km 35

Modeling Transmission Lines Resistance is 0.06/3=0.02  /km – Divide by three because three conductors per bundle 36

Untransposed Lines with Ground Conductors To model untransposed lines, perhaps with grounded neutral wires, we use the approach of Carson (from 1926) of modeling the earth return with equivalent conductors located in the ground under the real wires – Earth return conductors have the same GMR of their above ground conductor (or bundle) and carry the opposite current Distance between conductors is 37

Untransposed Lines with Ground Conductors The resistance of the equivalent conductors is R k' =9.869    f  /m with f the frequency, which is also added in series to the R of the actual conductors Conductors are mutually coupled; we'll be assuming three phase conductors and N grounded neutral wires Total current in all conductors sums to zero 38

Untransposed Lines with Ground Conductors The relationships between voltages and currents per unit length is Where the diagonal resistance are the conductor resistance plus R k' and the off-diagonals are all R k' The inductances are with D kk just the GMR for the conductor (or bundle) 39 D kk' is large so D km'  D kk'

Untransposed Lines with Ground Conductors This then gives an equation of the form Which can be reduced to just the phase values We'll use Z p with symmetrical components 40

Example (from 4.1 in Kersting Book) Given a 60 Hz overhead distribution line with the tower configuration (N=1 neutral wire) with the phases using Linnet conductors and the neutral 4/0 6/1 ACSR, determine Z p in ohms per mile – Linnet has a GMR = ft, and R =  /mile – 4/0 6/1 ACSR has GMR= ft and R=0.592  /mile – R k' =9.869    f  /m is  /mile at 60 Hz – Phase R diagonal values are =  /mile – Ground is  /mile 41 Figure 4.7 from Kersting

Example (from 4.1 in Kersting Book) Example inductances are worked with  = 100  -m Note at 2789 ft, D kk' is much, much larger than the distances between the conductors, justifying the above assumption 42

Example (from 4.1 in Kersting Book) Working some of the inductance values Phases a and b are separated by 2.5 feet, while it is 5.66 feet between phase a and the ground conductor 43 Even though the distances are worked here in feet, the result is in H/m because of the units on  0

Example (from 4.1 in Kersting Book) Continue to create the 4 by 4 symmetric L matrix Then Z = R + j  L Partition the matrix and solve The result in  /mile is 44

Modeling Line Capacitance For capacitance the earth is typically modeled as a perfectly conducting horizontal plane; then the earth plane is replaced by mirror image conductors – If conductor is distance H above ground, mirror image conductor is distance H below ground, hence their distance apart is 2H 45

Modeling Line Capacitance The relationship between the voltage to neutral and charges are then given as P's are called potential coefficients Where D km is the distance between the conductors, H km is the distance to a mirror image conductor and 46

Modeling Line Capacitance Then we setup the matrix relationship And solve 47

Continuing the Previous Example In example 4.1, assume the below conductor radii Calculating some values 48

Continuing the Previous Example Solving we get 49

Frequency Dependence We might note that the previous derivation for L assumed a frequency. For steady-state and transient stability analysis this is just the power grid frequency As we have seen in EMTP there are a number of difference frequencies present, particularly during transients – Coverage is beyond the scope of 576 – An early paper is J.K. Snelson, "Propagation of Travelling on Transmission Lines: Frequency Dependent Parameters," IEEE Trans. Power App. and Syst., vol. PAS-91, pp ,