Download presentation
Presentation is loading. Please wait.
Published byMitchell Pope Modified over 8 years ago
1
LCD Wiring Diagram Presentation 42-2113-1-B / 42-2113-2-B
2
Power Off-On Switch 120V Power Supply
3
Power Switch ON
4
24 Volt Transformer Powered
5
Low Operator
6
Call for Heat
7
Pump Relay Energized
9
Pump Contact Closes
10
Pump Energizes
12
Flow Switch Makes
13
Fan Manager Energizes
15
Fan Contact Closes
16
Fan Energized on Low Speed
18
Low Air Pressure Switch Makes
19
Pre-purge Relay Energizes
21
Low Pilot Gas Valve & R7 Relay Energized
23
R7 Contact Makes
24
Spark Generator Energizes
26
Flame Rod Senses Pilot
27
Gas Valve Energized on Low R7 Relay Drops Out Via R8 Relay
29
R8 Contact Makes
30
Safety Solenoid Energizes R7 Contact Drops Out Spark
32
High Operator Calls Second Stage
33
High Speed Blower Relay Energizes
35
Blower Ramps to High Speed
37
High Pressure Air Switch Makes
38
High Fire Relay Energizes
40
Gas Valve Energized on High Pilot Valve Energized on High
41
Loss of Pilot Flame
42
Retry After 5- Min. Wait
43
Flame Safeguard in Lockout Mode Alarm Contacts Close R1 Energizes Unit Failed to Light
45
R1 Contact Breaks
46
Fan Manager Times Out
48
Fan Drops Out
50
Pressure Switches Break
52
Reset Button Pressed
53
Pilot Ignition Retry Successful
54
High Fire Established
56
Call for Heat Drops Out
57
Blower Post Purge Times Out
58
Pump Purge Times Out
59
THANK YOU! We look forward to working closely with all of you in the near future:
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.