BE – RF CLEX TBM Cooling System Software Perspective (DAQ and analysis) A. Zelios, BE - RF1 A. Zelios A. Vamvakas.

Similar presentations


Presentation on theme: "BE – RF CLEX TBM Cooling System Software Perspective (DAQ and analysis) A. Zelios, BE - RF1 A. Zelios A. Vamvakas."— Presentation transcript:

1 BE – RF CLEX TBM Cooling System Software Perspective (DAQ and analysis) A. Zelios, BE - RF1 A. Zelios A. Vamvakas

2 A. Zelios, BE - RF2 Overview - Contents Hardware o LabVIEW equipment o Sensors  Naming - Variables Software o LabVIEW o SILECS o FESA o TIMBER Future Work

3 A. Zelios, BE - RF3 Hardware – LabVIEW equipment For the purposes of Data acquisition and system control the following equipment is installed: cRIO – 9065 o IP : 172.18.211.27 on the Technical Network (TN) o DNS Name: cfx-2010-acltbmcs NI – 9149 o IP : 172.18.211.28 (TN) o DNS Name: cltbmcs2.cern.ch The reasons behind this choice are hierarchically the following: Reliability Precision Compact Dimensions Extensible

4 A. Zelios, BE - RF4 Hardware - Sensors

5 A. Zelios, BE - RF5 Hardware - Sensors

6 A. Zelios, BE - RF6 Variable Names CCDB Cooling System PartsControl of Valves (names)FlowmetersTemperature Sensors DBQCM.CtrlValve.DBQCM.FlowMeter_DBQ CM.Temperature.DBQ.IN CM.Temperature.DBQ.MID CM.Temperature.DBQ.OUT PETSCM.CtrlValve.PETSCM.FlowMeter_PETS CM.Temperature.PETS.IN CM.Temperature.PETS1.ON CM.Temperature.PETS.MID CM.Temperature.PETS2.ON CM.Temperature.PETS.OUT SAS CM.CtrlValve.SAS1CM.FlowMeter_SAS1 CM.Temperature.SAS1.IN CM.Temperature.SAS1.ON CM.Temperature.SAS1.OUT CM.CtrlValve.SAS2CM.FlowMeter_SAS2 CM.Temperature.SAS2.IN CM.Temperature.SAS2.ON CM.Temperature.SAS2.OUT WG CM.Temperature.WG1 CM.Temperature.WG2 RFNL CM.Temperature.RFNL1 CM.Temperature.RFNL2 Ambient CM.Temperature.Ambient1 CM.Temperature.Ambient2 More information regarding the devices: http://ccdb.cern.ch

7 A. Zelios, BE - RF7 Software - LabVIEW LabVIEW For the purposes of the LabVIEW project which was developed for the cRIO equipment the most essential part was RADE RADE stands for Rapid Application Environment based on LabVIEW, which is a solution developed in CERN in order to develop expert tools and test facilities integrated with the CERN control infrastructure. Sources: https://svn.cern.ch/reps/mtaGen/CLEXcooling system

8 A. Zelios, BE - RF8 Software - SILECS What is SILECS? A framework created in CERN for Ethernet communication among heterogeneous set of controllers by providing the user with a configuration tool and communication library with hardware independent API. More info at: https://wikis/display/SIL/Introductionhttps://wikis/display/SIL/Introduction Sources: https://svn.cern.ch/reps/SILECS-DATA/trunk/1.m.p/design/FM_CLTBMCS_3.0.0/ https://svn.cern.ch/reps/SILECS-DATA/trunk/1.m.p/design/CV_CLTBMCS_3.0.0/ https://svn.cern.ch/reps/SILECS-DATA/trunk/1.m.p/design/TempSensors_3.0.0/ https://svn.cern.ch/reps/SILECS-DATA/trunk/1.m.p/design/SilecsHeader_1.0.0/ https://svn.cern.ch/reps/SILECS-DATA/trunk/1.m.p/deploy/cfx-2010-acltbmcs

9 A. Zelios, BE - RF9 Software - FESA What is FESA? It’s a Front-End Software Architecture (FESA) framework in order to design, develop and test real-time control software for front-end computers (FEC). More info about FESA here -> https://wikis/display/FESA3/Project) FEC used for this project: cfc-2013-a12gts2 Sources: https://svn.cern.ch/reps/acc-fesa/trunk/fesa-class/CV_CLTBMCS https://svn.cern.ch/reps/acc-fesa/trunk/fesa-class/FM_CLTBMCS https://svn.cern.ch/reps/acc-fesa/trunk/fesa-class/TempSensors https://svn.cern.ch/reps/acc-fesa/trunk/fesa-deploy-unit/CV_CLTBMCS_DU https://svn.cern.ch/reps/acc-fesa/trunk/fesa-deploy-unit/TempSensors_DU

10 A. Zelios, BE - RF10 Software - TIMBER What is TIMBER TIMBER is a generic Java application for browsing, visualizing and downloading logged data.

11 A. Zelios, BE - RF11 Future Work GUI using JAPC in order to facilitate the control and the overview of the cooling system Alarm System (LASER) which will be activated either when the temperature or the water flow is too low Suggestions for improvement are always welcome!