Download presentation
Presentation is loading. Please wait.
Published byClyde Watkins Modified over 8 years ago
1
Hao Zhu Dept. of Electrical & Computer Engineering University of Illinois, Urbana-Champaign haozhu@illinois.edu ECE 498HZ: Power Distribution System Analysis Chapter 7: Voltage Regulation February 18, 2016
2
Voltage More Crucial in Distribution Systems! A variety of automatic control mechanisms enforced to main voltageD 2 LTC Transformers Step-voltage regulators Shunt capacitors
3
Voltage Standards ANSI (American National Standards Institute) 3 System voltage: RMS phasor of every portion of the system - Nominal system voltage - Max system voltage Service voltage: at connected points with users Utilization voltage: at connected points with equipment - Nominal utili. voltage Service V System V Utili. V
4
3-wire 120/240V Service Favorable zone (Range A) –Nominal utilization voltage = 115 V –Maximum utilization and service voltage = 126 V –Minimum service voltage = 114 V –Minimum utilization voltage = 110 V Tolerable zone(Range B) –Nominal utilization voltage = 115 V –Maximum utilization and service voltage = 127 V –Minimum service voltage = 110 V –Minimum utilization voltage = 107 V 4
5
Voltage Unbalance For the metrics (all defined for volt. magnitudes) For normal operations, V unbalance <= 3% 5
6
Step-Voltage Regulators 1-phase or 3-phase 1-phase can be used to form Y- or Δ- connection Basically autotransformer + LTC –Varying tap (number of turns) of the series winding 6
7
Two-winding Transformer 7 Equivalent Circuit
8
General Constants (Same to Line Models) 8
9
To Do Ladder Iterations 9
10
“Step-up” Autotransformer Connecting H1 to X2 Source: H1 and H2 Load: X1 and H2 10
11
General Constants 11
12
Step-down Autotransformer 12
13
For Both Types 13
14
Autotransformer Ratings 14
15
Step-voltage Regulators 15
16
Tap Changing Details 16 switching sequence Preventive autotransformer presents high impedance to circulating current and low impedance to parallel currents A on B off C on A on B on C off A off B on C on
17
It’s a Local Control 17
18
Control Settings Voltage level: a desired voltage (say 120V) at a “load center” Bandwidth: allowed deviation from the set voltage level (+/-1V) Time delay: to stabilize the changing operations Line drop compensator (LDC): to account for the line voltage drop between the regulator and the load center (detailed later) 18
19
Single-phase Step-voltage Regulators 19 “Raise” mode “Lower” mode
20
Generalized Constants 20
21
Line Drop Compensator (LDC) 21
22
LDC Design 22 Typically 120V Typically a few Amps
23
Example 7.4 23
24
Examples 7.5 and 7.6 Load center: 2500kVA at 4.16kV and 0.9 PF (lagging) Use the compensator settings from Ex. 7.4 Voltage level = 120V with bandwidth = 2V To solve: the tap position Based on this tap position, solve for the actual load center voltage 24
25
Three-phase Voltage Regulators Use the abbreviated circuit of Type-B single-phase voltage regulator 25
26
Wye-Connected Regulators 26
27
Example 7.7 Recall the ladder power flow Example 6.5 Generalized matrices for the line Power flow solution To solve: compensator designs? tap positions? Ladder with Vreg? 27
28
Ladder Iterations Now we have two components: the Vreg and the line Forward sweep: Vreg -> Line Backward sweep: Line -> Vreg 28
Similar presentations
© 2024 SlidePlayer.com. Inc.
All rights reserved.