Lecture Objectives: Introduce Low temperature Energy Systems – Stirling engines Energy mesurment
4
Low temperature energy systems Waist heat is part of almost every CHP Many new micro CHP system use Stirling engine http://www.viessmann.com
5
Stirling cycle Closed Cycle Engine No phase change Working fluid: air, hydrogen, or helium
6
Stirling engine Theoretical efficiency of up to 25% (for 500ºC) Real efficiency in residential application between 6-8%
7
When using gas good for micro-generation where heat is needed around the year
8
Thermal energy measuring technique for energy management systems Measuring of temperatures Water, glycol, steam, air,…. Measuring of flow rates same list of fluid Issues: Accuracy Frequency Time integration
9
9 Resistance Temperature Devices Resistance temperature devices (RTDs) 10 year ago -most commonly applied T-sensing device Nearly linear (positive) T coefficient of metals Platinum = very popular will not oxidize (change resistance) --- stable highly accurate Thin-film platinum RTDs = ± 0.1 o K Also: rhodium-iron, nickel, tungsten, copper Simple circuit design w/ good sensitivity Requires transducers Response time depends on ……
10
10 Thermistors Themistors = thermal resistors Element: semi-conductor compounds (metal oxides) Change resistance w/ T (negative T coefficient) Significant change in R vs. T relative to RTDs RTDs: order 0.1 ohm/ o C Thermistors: order 10 ohm/ o C Highly non-linear T vs. R curve see ASHRAE PDS IV document (pg. 2-9)
11
11 RTD vs. Thermistor
12
12 Thermocouples Two wires of dissimilar metals joined at two ends – solder, weld, twist One end heated – small current generated V based on temperature difference and material props V proportional to T difference Voltage often order µV (e.g., 50 µV/ o C) Less precise than RTDs Thermopiles = bunch of thermocouples (to order mV) See Table 2 of ASHRAE Handbook Ch 14
13
13 Thermocouples Gas hot water heater - Pilot flame sensor
14
14 Type of thermocouples T - Copper - Constant K – Al - Chromium
15
Turbine flow meters
16
Vortex flowmeter For given geometry V~f You measure sped of pressure oscillations (frequency)
17
Doppler/Transit-Time Ultrasonics
18
Magnetic