EXTRACTION OF HIGH VOLUME CRYOGENIC HEAT LOAD
Ronald den Heijer, Tushar Bhowmick ICEC 2016 6-11 January 2016
2
Contents Cryogenic closed loop Closed loop cooling systems @ IPR
IPR Liquid Nitrogen 80K Boosting System IPR 80K Helium Gas Supply system Conclusion
3
Cryogenic Closed Loop conditioning cold source transferring recycling
using (application) recycling cold source
4
Liquid Nitrogen 80K Boosting System
Cooling the thermal shields of SST-1 Tokamak Reactor: Cold source : liquid nitrogen Coolant: Subcooled liquid nitrogen in a closed loop Net heat load : 20kW LN2 temperature inlet : 80K outlet : max 90K High efficiency LN2 pumps : 30% Available floor space : 2,25m*2,25m
5
P&ID Liquid Nitrogen 80K Boosting System
6
Liquid Nitrogen 80K Boosting System @ IPR
7
Liquid Nitrogen 80K Boosting System
Installed and Commissioned November 2014 Results: Net heat load during testing: >20 kW LN2 temperature: inlet <80K outlet <90K LN2 pressure: Mpa (g) Flow rate subcooled LN2: 100 lpm Pump efficiency: 32%
8
80K Helium Gas Supply System @ IPR
Cooling Cryo-adsortpion Cryopump: Cold Source : Bulk Liquid Nitrogen Helium gas as coolant in a closed loop He temperature inlet pump : 80 K outlet pump : 85 K Net heat load : 5.5 kW Helium flow rate : 210 g/s Operational He pressure : 16 Mpa (a) Net pressure drop at 210 g/s : MPa High efficiency pumps : approx. 50 %
9
PFD 80K Helium Gas Supply System
10
YETI gas circulator: design requirements
Helium gas flow : 210g/s Helium pressure : 1.65 Mpa (a) Pressure build up : MPa Efficiency : 50%
11
YETI design: Flow
12
YETI Design: Dynamics
13
YETI Design: Thermal and Contraction
14
YETI CIRCULATOR
15
YETI Performance
16
80K Helium Gas Supply System (NL)
17
80K Helium Gas Supply System (NL)
18
80K Helium Gas Supply System @ IPR Results:
Installed and commissioned December 2015 Helium gas in a closed loop 1.65 MPa (a) He temp. inlet Cryopump : <80 K outlet : <85 K Net heat load : 5.5 kW Helium flow rate : 210 g/s Net pressure drop at 210 g/s : 0.082>0.055 Mpa Efficiency pumps : approx 50 %
19
Conclusion (1) Liquid nitrogen 80K Boosting System:
The Liquid Nitrogen 80K Boosting System performs as per requirement of IPR or better. In steady state a heat load of >20 80K was removed successfully The overall system efficiency is 89%
20
Conclusion (2) 80K Helium Gas Supply System:
The 80K Helium Gas Supply system performs as per requirements of IPR or better In steady state the heat load of 80K was successfully removed The allowable pressure drop is higher than required: MPa instead of 0.05 MPa The system efficiency is 61%
21
EXTRACTION OF HIGH VOLUME CRYOGENIC LOAD made by CryoZone
22
Questions and Queries are most welcome
Thank You Questions and Queries are most welcome