Uponor for Radiant Cooling Systems 102. Outline Fundamentals review FEA Analysis Case Studies Piping CCN Controls Web Link to Uponor DC Specifications.

Similar presentations


Presentation on theme: "Uponor for Radiant Cooling Systems 102. Outline Fundamentals review FEA Analysis Case Studies Piping CCN Controls Web Link to Uponor DC Specifications."— Presentation transcript:

1 Uponor for Radiant Cooling Systems 102

2

3 Outline Fundamentals review FEA Analysis Case Studies Piping CCN Controls Web Link to Uponor DC Specifications Submittals Design Request Form

4 Fundamentals review Load – 12 to 14 Btuh/sqft, up to 32 Btuh/sqft Surface Temperature – 66 o F  67deg occupied, 65 unoccupied (ASHRAE 55 -2004) Average Water Temperature – 55 to 58 deg Dew Point – safety factor, keep water temperature 2 deg. Above dew point Spacing – 6 OC (max 9 OC) Loop Lengths – 300 - 350 ft for 5/8” Energy Equation – Btuh = 500 x gpm x dt Size of pipe – 5/8” typical Design differential temperatures  5 o F - 8 o F for cooling

5 FEA Analysis

6 Case Study Link Urban Outfitters HQ Uponor Radiant Heating /Cooling 53 Tons of Cooling 630 MBH of Heating Central Heating and Cooling Plant to Serve the Campus http://www.esmagazine.com/Articles/Cover_Story/BNP_GUID_9-5-2006_A_10000000000000178651

7 URBN - Building 543 Challenges North / south glass High clerestory glass Open mall area Humidity producers Large volumes Aesthetic demands

8 URBN - Building 543 Solutions Radiant heating and cooling slab Air side cooling for humidity control Draft barriers at occupied zones Vertical discharge diffusers

9 URBN – Slab details 53 tons of cooling 630 MBH of heating 14 manifolds, each with up to 10 loops at ~ 350 ft each loop Thermal breaks at radiant slab edge Embedded floor surface temperature sensors Space dew point sensors

10 URBN – Loop layout

11

12 URBN Solutions

13

14 Case Study Link Uponor Distribution Center Radiant Heating/Cooling AquaPEX Plumbing System 285,000 Sq Ft | LEED Silver Best in Real Estate Award 2009 http://twincities.bizjournals.com/twincities/stories/2009/04/20/focus17.html

15 Uponor DC - Challenges Office next to warehouse Floor to ceiling windows Cubicles Carpet Solar gain Lobby Pressurization problems

16 Uponor DC - Solutions Radiant heating and cooling slab Air side for latent, portion of sensible and ventilation load  RTU CCN controlling Radiant system and communicating with BAS system

17 Piping – Water temperature mixing

18

19 Piping – Mixing with htg / clg switch over

20 Piping – Primary (building) / Secondary Hot Water Chilled Water Primary Pump

21 CCN Controls – Zoning by pump A ( < 3 amp )

22 CCN Controls – Zoning by pump B ( > 3 amps)

23 CCN Controls – Zoning by valve with common pump (1 or 2 pumps)

24 CCN Controls – Zoning by thermal actuator on manifold

25 CCN Controls – Zoning

26 CCN – Zoning + water temperature control

27

28 CCN – Communication available to BAS CCN Thermostats  Mode  Temperatures – Operative – Slab – Humidity  All physical and software points – i.e. mixing valve position – Pump status – Supply and return temperatures

29 Specification

30 Submittals

31 Questions? Thank you